__ _

1

~ '

June 28, 1989 i

Dr. Robert C. Nelson, Lt. Col., USAF q

Executive Officer, TNRSSG Directorate of Nuclear Surety Kirtland Air Force Base, New Mexico 87117-5000

Dear Lt. Col. Nelson:

SUBJECT:

COMMENTS ON THE STATIONARY NEUTRON RADIOGRAPHY SYSTEM (SNRS)

As requested in your letter of December 2,1988, we have reviewed the Generel Atomics digital instrumentation and control console for the SNRS which is being installed at McClellan Air Force Base in California. The staff had determined that the General Atomics Microprocessor Based Instrumentation and Control System is acceptable for use in TRIGA research reactors if the following conditions are met:

(1) The power monitoring and scram circuits do not exclusively consist of NM-1000 units.

(2) The watchdog timer circuit scrams and NM-1000 power level scram are incorporated into the reactor Technical Specifications.

The staff has determined that your instrument and control system meets these conditions. Because your facility is not licensed by the NRC, these comments are not binding on the Air Force and no response is required.

If you have any questions concerning this review, please contact me at FTS 492-1121 or 301-492-1121.

Sincerely, original signed by Alexander Adams, Jr., Project Manager Standardization and Non-Power Reactor Project Directorate Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation Distribution:

~ Docket Filei OGC NRC & Local PDRs E. Jordan Reeding B. Grimes J. Stewart ACRS (10)

E. Hylton A. Adams L

'P PDS PDhN SICB hJStewart ton At a

@g Chiller 6/ /89 6

. 89 6/d/89 6/20/89

%pl 8907110002 890628 PDR ORG NGRB PDC

4, UNITED STATES

,[

g NUCLEAR REGULATORY COMMISSION

(

WASHINGTON, D. C. 20555 E

%,,,,p' June 28, 1989 Dr. Robert C. Nelson, Lt. Col., USAF Executive Officer, TNRSSG Directorate of Nuclear Surety Kirtland Air Force Base, New Mexico 87117-5000

Dear Lt. Col. Nelson:

SUBJECT:

COMMENTSONTHESTATIONARYHEUTRONRADIOGRAPHYSYSTEM(SNRS)

As requested in your letter of December 2,1988, we have reviewed the General Atomics digital instrumentation and control console for the SNRS which is being installed at McClellan Air Force Base in California. The staff had determined that the General Atomics Microprocessor Based Instrumentation and Control System is acceptable for use in TRIGA research reactors if the following

, conditions are met:

-(1) The power monitoring and scram circuits do not exclusively consist of NM-1000 units.

(2) The watchdog timer circuit scrams and NM-1000 power level scram are incorporated.into the reactor Technical Specifications.

The staff has determined that your instrument and control system meets these conditions. Because your facility is not licensed by the NRC, these comments are not binding (,n the Air Force and no response is required.

If you have any questions concerning this review, please contact me at FTS 492-1121 or 301-492-1121.

Sincerely, t

Alexander Adams, Jr. Pr ect Manager Standardization and Hon, ower Reactor Project Directorate Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation l

L___ _ --