.TENNES'SEE VALLEY AUTHORITY CHATTANOOGA. TENNESSEE 374ot l
t?
{
- 5N 157B. Lookout Place
~
elVN 301989 l
1L U.S. Nuclear, Regulatory, Commission
~ ATTN; -Document' Control Desk-i Washington... D.C.L 20555 Gentlemen:
i i
In the Matter of1
)
Docket Nos. 50-327 Tennessee Valley Authority
)
50-328
-SEQUOYAH NUCLEAR PLANT-(SQN) UNITS 1 AND 2 - HEATING, VENTILATING, AND AIR CONDITIONING-(HVAC) DUCT SUPPORT CALCULATIONS - UNRESOLVED ITEM 88-12-07 Qi--)
Reference:
'TVA letter to'NRC dated March 15, 1989
-This letter documents the June 12, 1989', conversation between T. M. Cheng, of
,NRC,=and R. O. Hernandez, of TVA.
t The -referenced ' letter requested HRC's concurrence in using 5 percent damping s
for operating basis earthquake (OBE) and 6 percent damping for safe shutdown
[ earthquake.(SSE) for. companion-angle construction and 9 percent damping for OBE a'nd SSE'for-pocket-lock-type construction of.HVAC ducting systems.
TVA-
- now proposes, however, to' limit. damping values to 4 percent for OBE and
- S percent for'SSE for nonwelded companion-angle duct construction and 7l percent for OBE and SSE for pocket-lock-type construction for the long-term design of HVAC systems at SQN.-
NRC's written concurrence is' requested for these new values.
No new commitments'are contained in this letter. Please direct questions concerning this iscue to B. S. Schofield at (615) 843-6172.
Very truly yours, TENNESSEE VALLEY AUTHORITY i
,q.
Managg Nuclear Ligensing and Regulatory Affairs cc:
See page 2 003D I
!n 1
890706,0090 890630 PDR-ADOCK 05000327 P
PDC An Equal Opportunity Employer
JUN 301989 -
U.S. Nucinar Regulatory Commission I
t-cc:
Ms. S. C. Black, Assistant Director for Projects -
TVA Projects Division U.S. Nuclear Regulatory Commission One White Flint, North I
11555 Rockville Pike Rockville, Maryland 20852 Mr. B. A. Wilson, Assistant Director for Inspection Programs TVA Projects Division U.S. Nuclear Regulatory Commission Region II 101 Mariotta Street, NW, Suite 2900 Atlanta, Georgia 3 0 ).- i NRC Resident Inspector Sequoyah Nuclear Plant 2600 Igou Ferry Road Soddy Daisy, Tennessee 37379