Amend 47 to License NPF-30,increasing Allowed Flow Variations of Control Room Emergency Ventilation Sys & Reducing Control Rom Pressurization Requirement from 1/4 to 1/8 Inch Water Gauge
ML20245L596
Person / Time
Site: Callaway 
(NPF-30-A-047, NPF-30-A-47)
Issue date: 06/27/1989
From: Hannon J
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20245L601 List:
References
NUDOCS 8907060007
Download: ML20245L596 (5)


Text

.

m

~

~ 9

f. @84q e

[j #y, 1

-~ 8,,

UNITED STATES

g.

. NUCLEAR REGULATORY COMMISSION

' h*

f j.

WASHINGTON, D. C,20655 UNIONL ELECTRIC. COMPANY a

CALLAWAY.PLANTrUNIT.1 i

DOCKET.NO. STN 50 483 L

' ~

AMENDNENT.TO.EACILITY.0PERATING LICENSE.

Amendment No. 47 License No. NPF-30

-1.

The Nuclear. Regulatory Comission (the Commission) has found that:

A..

The application for anendment filed by Union Electric Company

-(UE, the licensee) dated March 25, 1988 as supplemented by letters dated December 28, 1988 and March 31, 1989, complies with as amended (the Act)quirements of the Atomic Energy Act of 1954, the-standards and re

, and the Comission's rules and. regulations set forth'in 10 CFR Chapter I; B.-

.The facility will operate in conformity with the application, the provisions of the Act, and the rules and. regulations of the Corranission; C.

Thereisreasonableassurance(i)thattheactivitiesauthorizedby

.this emendment can be conducted without endangering the health and safety of'the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense-and security or to the health and safety of the public;~ and E.

The issuance of this anendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifica-tions as indicated in the attachment to this license amendment, and para-graph 2.C.(2) of Facility Operating License No. NPF-30 is hereby amended to read as follows:

= M " I$oOk b

@3

-P

. 9

.(2) Technical Specifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 47, and the Environmental Protection Plan -

contained in Appendix B, both of which are attached hereto, are hereby~ incorporated into the license. UE shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective upon issuance and shall be implemented within 30 days from the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION f

h Yu -

' John N. Hannon, Director Project Directorate III-3 Division of Reactor Projects - III.

IV, V and Special Projects Office of Nuclear Reactor Regulation Attachment':

- Changes to the' Technical Specifications Date of Issuance:

June 27, 1989 l

l l

c

ATTACHMENT TO LICENSE AMENDNENT.N047 OPERATING LICENSE NO..NPF-30 DOCKET NO. 50-483 Revise Appendix A Technical Specifications by removing the pages identified below and inserting the enclosed pages. The revised pages are identified by the captioned amendment number and contain marginal lines indicating the area of change. Corresponding overleaf pages are provided to maintain document completeness.

REMOVE INSERT 3/4 7-15 3/4 7-15 3/4 7-16 3/4 7-16 m

1 q

m w

~

PLANT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)-

q j

c.

At.least once per 18 months, or (1) after any structural maintenance

.on the HEPA filter or, charcoal. adsorber housings, or (2) following painting, fire or chemical., release in any ventilation zone communicating with the system by:

1)

Verifying that the Control Room Emergency Ventilation System-satisfies the in-place penetration and bypass leakage testing acceptance criteria'of less than 1% and uses the. test procedure.

' guidance in Regulatory Positions C.5.a. C.5.c, and C.S.d of.

Regulatory Guide 1.52, Revision 2, March 1978, and the system flow rate is 2000 cfm + 700 for the Filtration System and-surization'Systemwith500cfm[h0 2200cfm[

for the P going through the Pressurization System filter adsorber unit; 2)

Verifying,within 31 days after. removal, that a laboratory analysis of a representative carbon sample obtained in.accordance with Regulatory Position.C.6.b of Regulatory Guide.1.52, Revision 2, March.1978, meets the laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52. Revision 2, March 1978, for a methyl iodide penetration of less than 1%; and 3)-

Verifyingasystemflowrateof2000cfm[

for the Filtration Systemand2200cfm[

for the Pressurization System with 500cfm[h0 going through the Pressurization System filter adsorber unit during system operation when tested in accordance with ANSI N510-1975.

d.

After every 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of charcoal adsorber operation by verifying within 31 days after removal, that a laboratory analysis of a representative carbon sample obtained in accordance with Regulatory Position C.6.b of Regulatory Guide 1.52, Revision 2, March 1978, meets the laboratory testing criteria of Regulatory Position C.6.a of Regulatory Guide 1.52, Revision 2, March 1978, for a methyl iodide penetre. tion of less than 1%;

e.

At least once per 18 months by:

1)

Verifying that the pressure drop across the combined HEPA filters and charcoal adsorber banks is less than 5.4 inches Water Gauge while operating the system at a flow rate of 2000cfm[

fortheFiltrationSystemand500cfm[h0 for the Pressurization System filter adsorber unit; 1

1 l

CALLAWAY - UNIT 1 3/4 7-15 Amendment No. 47 i

_n I

7 a'

h PLANT SYSTEMS:

.J SURVEILLANCE REQUIREMENTS (Continued) 2)

Verifying that on a Control Room Ventilation Isolation or High

. Gaseous Radioactivity test. signal, the system automatically switches into a recirculation _ mode of operation with flow through the HEPA filters and charcoal adsorber banks; 3)

Verifying that the system maintains the control room at a b

positive pressure of greater than or equal to 1/8. inch Water l

Gauge relative to the outside atmosphere during system

~

operation; and 4)

Verifying that tne Pressurization System filter adsorber unit heaters' dissipate 15 t 2 kW~in the Pressurization System when tested in accordance with ANSI N510-1975.

f.

After.each complete or partial replacement of a HEPA filter bank, by verifying that the: cleanup system satisfies the in-place penetration-F and. bypass leakage testing criteria of less than 1% in accordance with ANSI N510-1975 for a DOP. test aerosol while. operating the system

'at'aflowrateof2000cfm[

for the Filtration System and 500cfm,+h0 for the Pressurization System filter adsorber unit; and L

g.

After each complete or partial replacement of a charcoal adsorber bank, by verifying that the cleanup system satisfies the in-place penetration and bypass leakage testing criteria of.less than 1%

I in accordance with ANSI N510-1975 for a halogenated hydrocarbon refrigerant test gas while operating the system at a flow rate of 2000cfm[

fortheFiltrationSystemand500cfm[h0 for the Pressurization System filter adsorber unit.

i -

L i

L l

1 I

I i

CALLAWAY - UNIT 1 3/4 7-16 Amendment No. 47 1

. _ - _. _ _ _ _ _ _ _ _ _ _ - _ _ _ -