ML20245F034

From kanterella
Jump to navigation Jump to search
Responds to Request for Addl Info Re Implementation of 10CFR50.62, ATWS Rule, RPT Control Circuitry Will Be Modified to Provide Capability to Perform Periodic Surveillance Tests During Normal Plant Operation
ML20245F034
Person / Time
Site: LaSalle  
Issue date: 04/28/1989
From: Morgan W
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 8905020241
Download: ML20245F034 (2)


Text

y Y

4' 7

\\ Comm:nwrith Edison-

  • (

_ /.72 West Adams Street, Chicago Illinois '

8

) Address Reply to: Post Othee Box 767

\\

1'?%/ ! Chicago, Illinois 60690 0767 4

e April 28,.1989 l

L E

U.S.' Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 i

Subject:

LaSalle County Station Units 1 and 2 Implementation of 10 CFR 50.62, ATWS Rule -

Response to Request for Additional Information NRC Docket Nos. 50-37; and 50-374 References (a):

P.C. Shemanski letter to H.E. Bliss dated January 5, 1989.

(b):

W.E. Morgan letter.to U.S. NRC dated February 24, 1989.

Dear Sir Reference (a) provided the Safety Evaluation regarding LaSalle County

. Station Units 1 and 2 compliance with ATWS itule 10 CFR 50.62.

Additionally, this. letter' requested that Commonwealth Edison submit its proposed resolution

- of.certain remaining open items.

Reference (b) provided this information and stated that.the two issues concerning 1-ATWS/RPT System Testability at Power and ATWS/RPT one-out-of-two (1:2) Logic Design, required further review and that the results of this review would be transmitted by April 28, 1989.

Based on the requirements outlined in Reference (a) and the results

' of Commonwealth Edison's review, LaSalle Station has commited to the following:

- The RPT control circuitry will be modified to provide the capability to perform periodic surveillance tests during

~

normal plant operation up to and including the actuating relay.

The RPT logic design will be modified to "one-out-of-two" taken twice replacing the existing "one-out-of-two" trip scheme.

w N

D e

t 3p Y:

W~

p

.t l ! b 2..

,, US.NRC April 28, 1989 LaSalle Station wJil procure all new devices safety-related and engineer these design changes as. safety-related modifications. The detailed design and procurement of equipment will require an estimated 40 weeks.

Due to the enmplexity of the modification, these modifications will be scheduled to be c 1 leted by the end of the fourth refueling outage of each unit (Unit 1, June 1991} (Unit 2, March, 1992).

l If you have any questions regarding this subject, please refer them to this office.

Very truly yours, W

,A y

W.

E. Morgan Nuclear Licensing Administrator Im cc P.C. Shemanski - NRR LaSalle Resident Inspector 0100T

_ - _ _ _ _ _ _ _ _ - _ - -