PHILADELPHIA ELECTRIC COMPAN'Y 2301 MARKET STREET P.O. BOX 8699 PHILADELPHIA, PA 19101 (zis) sai sozo E. P. FOG ARTY June 14, 1989 noct...uUUEr" om ion Docket No. 50-352 License No. NPF-39 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

SUBJECT:

Limerick Generating Station, Unit 1 Electrical Power Systems Technical Specifications

REFERENCE:

Letter, R. J. Clark, (NRC) to G. A. Hunger, Jr. (PECo) dated May 19, 1989 Gentlemen:

This letter is to confirm our recent discussions with your staff regarding the Limerick Generating Station (LGS) Units 1 and 2 electrical power systems Technical Specifications (TS).

During the development of the LGS Unit 2 TS, certain changes to Actions "a."

and "e." of TS Section 3.8.1.1 were agreed to by your staff and Philadelphia Electric Company (PECo) representatives.

These changes are described in the enclosure to this letter and are reflected in the Unit 2 Final Draft TS which were transmitted in the referenced letter.

Upon issuance of the Unit 2 TS, PECo will implement these same changes via administrative controls established for Unit 1 operation.

These controls will remain in effect until a Unit 1 TS change request is submitted by PECo and subsequently approved by the NRC.

If any additional information is required, please let me Very truly yours, l

Q 7

cq E. P. Fogart Manager Nuclear Support Division Enclosure cc:

W. T. Russell, Administrator, Region I, USNRC T. J. Kenny, USNRC Senior Resident Inspector, LGS

,. g 8906200110 890614 PDR ADOCK 05000332 P

PDC L--____-__.

s

/

Enclosure Electrical Power Systems T.S. Section 3.8.1.1 Changes ACTION a. -

Changed the allowable out of service time (AOT) for one inoperable diesel generator from 92 days to 30 days.

ACTION e. -

Revised ACTION e. as shown below:

e.

In addition to the ACTIONS above:

1.

For two train systems, with one or more diesel generators of the above required A.C.

electrical power sources inoperable, verify within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter that at least one of the required two train system subsystem, train, components, and devices is OPERABLE and its associated diesel generator is OPERABLE.

Otherwise, restore either the inoperable diesel generator or the inoperable system subsystem to an OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

2.

For the LPCI systems, with two or more diesel generators of the above required A.C.

electrical power sources inoperable, verify within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter that at least two of the required LPCI system subsystems, trains, components and devices are OPERABLE and its associated diesel generator is OPERABLE.

Otherwise, be in at least BOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

This ACTION does not apply for those systems covered in Specifications 3.7.1.1 and 3.7.1.2.