ML20237K020

From kanterella
Jump to navigation Jump to search
Record of 870513 Telcon W/S&W & Util Re Insp Requirements for Pipe Supports for Plant.S&W Does Not Consider Insp of Designs to Be Warranted
ML20237K020
Person / Time
Site: Comanche Peak  
Issue date: 05/13/1987
From: Williams N
CYGNA ENERGY SERVICES
To:
References
CON-84056 NUDOCS 8709040161
Download: ML20237K020 (2)


Text

i

-. 1-hg con

, qQL, 1

(2 Commun,ications 0

. _ = = _ _

AM' M Report Illlllllllllllllillllilllillit t

Company: CES

  • Teiecon o Conference Report Project:

Job No.,84056 CPSES IAP Phase 4 U***

g /13 /s7 subject; Timi Inspection Requirements for Pipe Supports Place:

2 d0 p.m.

"*" *'" Item 4, SWEC NA-1140 Report Bannockburn, IL R. Klause, W. Evans, R. Read, D. Boe SWEC o,

J. Muffett TV o,

s. Tomminalli Cyana item Comments

(

Reg'd Action By SWEC spoke to Mark Bressler, Chairman of the ASME NF 4

committee concerning the issue of through thickness stresses and inspection. ASME eliminated the reduced through thickness allowables after 1974 because the lower allowables resulted in poor design in that larger welds, were being specified.

Further, the NF 5200 inspection requirements were not added to address lamellar tearing and that pipe supports are exempted per NF-4431. SWIC investigated material requirements which remained unchanged from 1974 to 1984. Therefore, SWEC does not consider inspection of these designs to be warranted.,

Cygna requested SWEC to reconsider, especially since only a few supports are involved.

I 8709040161 070513 PER ADOCK 05000445 G

PDR l

s>smeo-q/gf Whm e.se ot s

1 1

Se}AttachedDistrbutionSheet, Distnbution-1020 00

1 9

I L

/

J DISTRIBUTION LIST s

Mr. J.

Redding Mr.

L.

Nace

- Mr. W.

Counsil Mr.

J.

Muffett Mr.s. Pigott D

l Ms.

A. Vietti-Cook

.:Mi'C'EGr ime s...

Mr.

E.

Siskin l

Mr.

B.

Ramsey Ms.

N. Williams l

Mr. C. Wong Mr.

R.

Pascaretta Pro 3ect F11e l

l l

I l

t l

L. -

r I

l

\\

l l

l L

I i

l l

l