Forwards List of Tubes Plugged in Facility Steam Generators During Recent Mar/Apr 1987 Inservice Insp as Required by Tech Specs.Forty-three Tubes Found to Have Svc Induced Degradation in Excess of Tech Spec Plugging Limit of 40%
ML20237J416
Person / Time
Site: Calvert Cliffs 
Issue date: 05/29/1987
From: Tiernan J
BALTIMORE GAS & ELECTRIC CO.
To: Russell W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
NUDOCS 8708260155
Download: ML20237J416 (9)


Text

Wle d ifD9ff7 A

4-BALTIMORE GASAND ELECTRIC CHARLES CENTER R O. BOX 1475 BALTIMORE, MARYLAND 21203 i

JOSEPH A.TIERNAN vies PResiocur NUCLEAR ENEROY May 29, 1987 c.

U.S. Nuclear Regulatory Commission Region I 631 Park Avenue King of Prussia, PA 19406 ATTENTION:

Mr. William T. Russell Regional Administrator

SUBJECT:

Calvert Cliffs Nuclear Power Plant Unit 2; Docket No. 50-318 Report of Steam Generator Tube Pluccing

REFERENCE:

(A) Technical Specifications, Calvert Cliffs Unit 2 ATTACHMENT:

(1) Tubes Plugged Steam Generator #21 (2) Tubes Plugged Steam Generator #22 (3) Sketch of Steam Generator Support Locations Gentlemen:

As required by Technical Specification 4.4.5.5, this letter reports the number of tubes plugged in the Calvert Cliffs Unit 2 Steam Generators during the recent March / April 1987 Inservice Inspection.

Forty-three tubes were found to have service induced degradation which exceeded the Technical Specification plugging limit of 40% loss of nominal wall thickness, 29 in Steam Generator #21 and 14 in Steam Generator #22.

The inspection results on the initial Technical Specification sample selection required 100% of each Steam Generator's tubing to be inspected.

Indications of 20% through wall degradation or greater were found on a total of 176 tubes from the 17,008 tubes examined. As stated above, 43 of these indications exceeded the plugging limit of 40% loss of nominal wall. Additionally, 18 tubes, showing eddy current g\\

h 0

0 e

/

JST hEk N

n 4

i Mr. William T.' Russell May 29,:1987 Page 2 I

of less than 40% nominal'. wall l'oss, - were plugged.

For

~

I-

-indications:

l precautionary reasons, five of the -18 tubes were-plugged due to degradation at the upper. supports, which are' suspected to be wear.

t.

Twelve tubes were plugged due.to degradation above the tube sheet,.and-one,was plugged due to degradation at the first. support.. Metallurgical-examination of U-1 tubing has' shown that the degradation-above the tube i

. sheet'is caused by Intergranular Attack (IGA).

The indication at the first. support is suspected to be ICA, also.

j These 61 tubes were. removed from service by plugging the - hot and~ cold leg tube ends with mechanical plugs.

Attachments ' (1) - and -(2) list the tubes' plugged during the 1987. Unit 2

. Refueling Outage along. with the reason for plugging the tube'.

Attachment (3) is a' sketch indicating Steam Generator support locations j

l and nomenclature.

'Should you have further questions regarding this matter, please do not hesitate to contact us.

l' Very truly yours,

)

t-l l

E-l 5

JAT/JEM/j af Attachments

.cc:

D.A. Brune, Esquire J.E. Silberg, Esquire l

(S;A. McNeil,#NRC 1 j

T. Foley,-NRC p

R.A. Capra, NRC l

e R

i s

s l'

v, AST 4

' t Page 1 of 4 ATTACHMENT (1)

Steam Generator #21 Tubes Plugged During the' Unit 2 March 1987 Outage EDE 11HE REASON FOR PLUGGING 9

33 Eddy Current Testing Indication of 96% wall'

. loss-originating on the outside diameter of

'the tube at VM + 0.0 inches.

f i

14 156

' Eddy Current Testing Indication of 42% wall loss originating on the outside diameter of i

the tube at H4 + 35.7 inches.

.19 127 Eddy Current Testing Indication of 53% wall loss originating on the outside diameter of the tube at C5 + 10.2 inches.

'25

'157 Eddy Current Testing Indication of 46% wall loss originating on the outside diameter of the tube at H2 + 21.6 inches.

4 29 45 Eddy Current Testing Indication of 46% wall loss originating on the outside diameter of the tube at Cl + 14.1 inches.

29 139 Eddy Current Testing Indication of 74% wall loss originating on the outside diameter of l

the tube at HTS-SF + 0.6 inches.

29 143 Eddy Current Testing Indication of 48% wall loss originating on the outside diameter of the tube at HTS-SF + 0.6 inches.

46 128 Eddy Current Testing Indication of 48% wall loss originating on the outside diameter of i

the tube at HTS-SF + 0.6 inches.

54 136 Eddy Current Testing Indication of 69% wall loss originating on the outside diameter of the tube at HTS-SF + 0.5 inches.

68 122 Eddy Current Testing Indication of 56% wall loss originating on the outside diameter of the tube at HTS-SF + 0.4 inches.

71 115 Eddy Current Testing Indication of 47% wall

)

loss originating on the outside diameter of the tube at HTS-SF + 0.4 inches.

J

I c,s Page 2 of 4 1

O ATTACHMENT (1)

I Steam Generator'#21 Tubes Plugged During the Unit 2 March 1987 Outage i

..EDy g}{g REASON FOR Pl.UGGING

.{

74-116-Eddy Current Testing Indication of 60% wall j

loss originating on the outside diameter of.

the tube at HTS-SF + 0.7 inches.

74

-120 Eddy Current. Testing Indication of 54% wall loss originating on the outside diameter of the tube at HTS-SF + 0.4 inches.

76.

122 Eddy Current Testing Indication of 49% wall loss originating on the outside diameter of the tube at HTS-SF + 0.5 inches.

80 114 Eddy Current Testing Indication of 49% wall loss originating on the outside diameter of the tube at HTS-SF + 0.6 inches.

81

.97 Eddy Current. Testing Indication of 61% wall loss originating on the outside diameter of the tube at HTS-SF + 0.8 inches.

85 51 Eddy Current Testing Indication of 40% wall loss originating on the outside diameter of the tube at C8 + 4.7 inches.

97 103 Eddy Current Testing Indication of 75% wall loss originating on the outside diameter of the tube at HTS-SF + 1.1 inches.

99 53 Eddy Current Testing Indication of 52% wall loss originating on the outside diameter of the tube at H2 + 1.5 inches.

112 102 Eddy Current Testing Indication of 43% wall loss originating on the outside diameter of the tube at C5 + 31.6 inches.

1

'116 120 Eddy Current Testing Indication of 42% wall loss originating on the outside diameter of the tube at CTS-SF + 1.9 inches.

120 58 Eddy Current Testing Indication of 44% wall loss originating on the outside diameter of the tube at H6 + 11.9 inches.

p ;i7 g

+

y '.

l'e Page 3 of 41 1-ATTACHMENT (1) l

' Steam Generator #21 Tubes' Plugged During the-Unit 2 Harch 1987 Outage-

ggg.

ggg

-. REASON FOR PLUGGING 1

122

'64' Eddy Current Testing Indication of 49% wall loss originating on the outside diameter of

'the tube at CTS-SF + 3.8' inches.

122 92 Eddy Current Testing Indication of 97% wall loss. originating on the outside diameter of.

the tube at HTS-SF + 1.8 inches.

.126

_108 Eddy Current Testing Indication of 87% wall

. loss originating on the outside diameter of the tube at H9 + 15.8 inches.

127-53 Eddy Current Testing Indication of 44% and 62% wall loss originating on the outside diameter of the tube at CTS-SF + 14.1 and CTS-SF + 14.4 inches, respectively, i

129 53 Eddy Current Testing Indication of 45% wall loss originating on the outside diameter of q

the tube at HTS-SF + 13.8 inches.

132 110-Eddy Current Testing Indication of 44% wall loss originating on the outside diameter of the tube at HTS-SF + 7.4 inches.

133 109

' Eddy Current Testing Indication of 53% wall j

loss originating on the outside diameter of the tube at HTS-SF + 6.7 inches.

14 28 Eddy Current Testing Indication of 27% wall loss originating on the'outside diameter of the tube at HTS-SF + 2.4 inches.

37 157 Eddy Current Testing Indication of 34% wall f

loss originating on the outside diameter of the tube at HTS-SF + 22.4 inches.

38.

32 Eddy Current Testing Indication of 39% wall l

loss originating on the outside diameter of l

the tube at HTS-SF + 1.0 inches.

40 32 Eddy Current Testing Indication of 33% wall loss originating on the outside diameter of the tube at HTS-SF + 0.9 inches.

1

[* '

l:.

r.

Page 4 of 4-

~ATTACRHENT (1)

Steam Generator #21 Tubes Plugged During the Unit 2 March 1987 Outage EQH LINE REASON FOR PLUGGING

'42

.36

. Eddy.. Current Testing Indication of 32% wall

' loss originating.on the~outside diameter of the tube at HTS-SF + 0.6 inches.

1 74 46 Eddy Current Testing Indication of 34% wall

^

loss originating on the outside diameter of the tube at VC + 0.0 inches.

88 90 Eddy Current Testing Indication of 36% wall loss originating on the outside diameter of-the' tube at HTS-SF +.1.1 inches.

'89 119 Eddy Current Testing Indication'of 28% wall loss originating on the outside' diameter of the tube at HTS-SF + 0.4 inches.

91 105 Eddy Current Testing Indication of 28% wall loss originating on the outside diameter of the tube at HTS-SF + 1.1 inches.

113 123 Eddy Current Testing Indication of 21% and l

l 27% wall loss originating on the outside diameter of the tube at CTS-SF + 0.9 and CTS-SF + 2.3-inches.

120 54 Eddy Current Testing Indication of 28% wall loss originating on the outside diameter of the tube at CTS-SF + 0.5 inches.

127 107 Eddy Current Testing Indication of 27% wall loss originating on the outside diameter of the tube at VH + 0.0 inches.

l I

l Page 1 of 2 ATTACHMENT (2)

Steam Generator #22 Tubes Plugged During the Unit 2 March 1987 Outage ROW LINE REASON FOR PLUCGING 7

59 Eddy Current Testing Indication of 61% wall loss originating on the outside diameter of the tube at Cl + 5.0 inches.

18 32 Eddy Current Testing Indication of 71% wall loss originating on the outside diameter of the tube at HTS-SF + 0.7 inches.

20 146 Eddy Current Testing Indication of 50% wall loss originating on the outside diameter of i

the tube at Cl + 12.8 inches.

31 121 Eddy Current Testing Indication of 46% wall loss originating on the outside diameter of the tube at C2 + 14.1 inches.

32 68 Eddy Current Testing Indication of 57% wall loss originating on the outside diameter of the tube at CTS-SF + 25.4 inches.

34 72 Eddy Current Testing Indication of 70% wall loss originating on the outside diameter of the tube at DC + 0.0 inches.

36 90 Eddy Current Testing Indication of 59% wall loss originating on the outside diameter of the tube at DC + 0.0 inches.

56 90 Eddy Current Testing Indication of 47% vall loss originating on the outside diameter of the tube at C3 + 21.3 inches.

76 88 Eddy Current Testing Indication of 48% wall loss originating on the outside diameter of the tube at HTS-SF + 1.5 inches.

)

81 85 Eddy Current Testing Indication of 65% wall loss originating on the outside diameter of the tube at DH + 0.0 inches.

82 96 Eddy Current Testing Indication of 43% wall loss originating on the outside diameter of the tube at HTS-SF + 0.5 inches.

Page 2 of 2.

NfTACHMENT (2)

Steam Generator #22 Tubes Plugged During the Unit 2 March 1987 Outage EQH LINE REASON FOR PLUGGING 97 67 Eddy Current Testing Indication of 42% wall loss originating on the outside diameter of the tube at C9 + 1.2 inches.

106 88 Eddy Current Testing Indication of 47% wall loss originating on the outside diameter of the tube at H7 + 22.9 inches.

117 47 Eddy Current Testing Indication of 46% wall loss originating on the outside diameter of the tube at HTS SF + 8.7 inches.

8 132 Eddy Current Testing Indication of 37% wall loss originating on the outside diameter of the tube at VM + 0.0 inches.

9 123 Eddy Current Testing Indication of 26% vall loss originating on the outside diameter of the tube at VM + 0.0 inches.

11 51 Eddy Current Testing Indication of 38% wall loss originating on the outside diameter of the tube at HTS-SF + 12.0 inches.

37 89 Eddy Current Testing Indication of 25% wall loss originating on the outside diameter of the tube at DH + 0.0 inches.

80 84 Eddy Current Testing Indication of 29% wall loss originating on the outside diameter of the tube at HTS-SF + 0.7 inches.

136 66 Eddy Current Testing Indication of 37% wall loss originating on the outside diameter of the tube at C1 + 0.0 inches.

j l

1 I

l

-- D

ATTACHMENT (3) l l

Steam Generator Drawing

"".'}75$t" VM VC

~~

OWTrasset?

TWe4 (

!\\

/ i n

p\\

g/jc,.

R 0

se cp I

c.

f

[immsassos; i

'"" 5 i

N7 C7 i

i

  1. 8 ce

='.

l

-l

=,:

MS

' CS y suppe.rn. 8.Tunnuam a g

  1. 4 Ca i

l N3 c3 l

l t

  1. 3 c2 y snaoue us c

I ll l

6 i

Tustantti His '

i ' _ cts.se EI' t$

_ _ _ _ _ _ _ _ _ _ _ - _