m q
-j ATTACHMENT TO~IR 50-322/87-15 l,
p* Mooqg UNITED STATES
. [g )-(3 g NUCLEAR REGULATORY COMMISSION g
5
/<j-REGION i Q,
631 PARK AVENUE
[g '
KING OF PRUSSIA, PENNSYLVANIA 19406 I
%,.'.Ad
..+
i h
L September 28, 1987 i
MEMORANDUM i
FOR:
Mr. W. Steiger. Plant Manager FROM:
Mr. C. Warren, SRI, SNpS l
SUBJECT:
Facility Tour Findings - September 9,1987 MEMORANDUM The items on the attachment were noted during the facility tour on September 9, 1987 and are provided for your review and action as necessary. Please contact I
the onsite resident inspector when your. staff is ready to discuss the evaluation of'the items and the status of actions taken.
Please note the items,and the l
i plant's response will be addressed in a routine inspection report. ;
Thank you for your time and attention to these matters, and for you especially I
1 helpful assistance during the facility tour.
i Sincerely, 0
l Clay C. Warren l
SRI CCW:jmj cc:
Bill Russell R. Blough
,rvi-hA P
G
l' li 1
j I
\\. ?
\\
I g
-ITEMS IDENTIFIED DURIN3 REGIONAL ADMINISTRATORS F
TOUR OF SHOREHAM FACILITY HOUSEKEEPING - Numerous inctances of poor housekeeping were f ound during the walkthrough. These included stray tools, rags, nails, excess scaffolding, and other materials left astr ay f ollowing L
completion of work activities. What actions will be taken to improve post maintenance cleanup of work ar eas?
GREASING OF -
Improper lubrication practices at other plants has led to ROTATING f ai l ur et., of rotating equipment. Spec i f i call y, this is a result MACHINERY of not removing the drain plugs prior to greasing which causes the grease to cor e out along the shaft where it is then sucked into the motor. Several pumps inspected did not have drai-n plugs which wer e easily accessi b l e and some showed i ndi c a ti ons of over greasing. Attention should be directed to ensuring drain plugs are easily accessiale and personnel ar e properly trained. What changes will be implemented to prevent po ten ti al overgreasing of safety related pumps?
MISSING PIPE-- Numerous instances of open anded piping were found on high CAPS energy, or contaminated systems. All were isolable by at least one valve but attention should be di rect.ed to evaluating if caps should be installed. This is a personne] cafety and r adi ol ogi c al issue. What actions will be t a l. e n to address this issue?
L.ODSE PARTS
- Loose space parts were found stor ed in the cabinet which houses j
IN RELAY relays to control the IRM and SRM drive motors This CABINETS could be a problem during a sei smi c event. What attions wi11 be taken to nnsure technicians do not storo spare parts or tools
- nside electrical cabinet #
COMPONENT
- bhJmerous instance, cf leakage were found in the plant. Most of LE/;KAGC
&hese wera cacLing Jeahage arH meny wer e not ident! fled with deficiencv :agb Attentior. s! toul d be directed to identifying and rcoaaring 1 eair y componen:- pr i or to de/vejuping contam:netian problems. Wh a t o maramnatic i mp r ;_ v emen t. c.s i 1 1 be implemented whereby 1 eaki ng compenenti ar e att 1 east icerLified 3
if flat rep 4tirOd?
SYSTEM Boundary valve' wath potenticl 4 ar deainjng t fia SUt C tan! we w BOUNDARY found not to be 1ocied. Altent:on should be direcied ia VAL.VES NOT ensuring valves cf this type ar " :or, un t i v. den t : ~f i ed by ayatem LOCKED walidowns. What. actians wi11 Un t a ;- e n
- t. a ensure v al ve; w) Lh potential to dru i. n srfety r e.; a l e d anc / ar c on tam rw i ed m :s t s ms Wj1l nol be OpCTdted ihadVerLali3y