.,a JOSEPH M. FARLEY NUCLEAR PLANT UNIT 2'.
+
NARRATIVE SUPNARY OF~ OPERATIONS I
August, 1987
.There was one significant power reduction during the month of August.
'On 8/14/87, power was reduced to allow containment access for the inspection and repair.of motor-operated valve connections.
The unit returned to full power operation on 8/19/87.
The following major safety-related maintenance was performed in the month-of August:-
- 1.. Solenoid splices and motor-operated valve splices that were installed utilizing methods not evaluated by design for environmental qualification were re-terminated in accordance with newly approved EQ terminations on a priority basis.
2.
Leaking warm-up valves were repaired on the turbine-driven au *1iary feedwater pump.
3.
The cooler was cleaned and the bolts were replaced on the 2A I
charging pump.
4.
Miscellaneous corrective and preventive maintenance was performed on the diesel generators.
9 A f-[
8712070177 G70831 PDR ADOCK 05000364 R
- PDR, p
g
OPERATING DATA REPORT DOCKET No.. 50-364 DATE 9/1/87 COMPLETED BY J. D. Woodard
'ELEPHONE (205)899-5156 1
OPERATING STA'IUS Notes 1
- 1. Unit Name:
Joseph M. Farley - Unit 2
- 2. Reporting Period:
August, 1987
- 1) Cumulative data since
- 3. Licensed Thermal Power (MWt):
2,652 7-30-81, date of.
- 4. Nameplate Rating (Gross W e):
860
. commercial operation j
- 5. Design Electrical Rating (Net We): 829
- 6. Maximum Dependable Capacity.(Gross MWe):
864.9
- 7. Maximum Dependable Capacity (Net We):
824.1
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report, I
Give Reasons:
N/A.
j
- 9. Power Level To Which Restricted, If Any (Net Ne):
- 10. Reasons For Restrictions, If Any:
N/A N/A 1
' Itis Month Yr-to-Date Cumulative
- 11. Hours In Reporting Period 744 5,831 53,376
- 12. Number Of Hours Reactor Was Critical 744.0 5,473.6 51,829.8
- 13. Reactor Reserve Shutdown Hours 0.0 0.0 138.0
- 14. Hours Generator On-Line 744.0 5,456.7 46,307.5
- 15. Unit Reserve Shutdown Hours 0.0 -
II 7E,743 117,073,733
(
0.0 0.0
- 16. Gross Thermal Energy Generated (WH) 1,782,971
- 17. Gross Electrical Energy Generated (MWH) 566,926 4,470,550 38,479,820
- 18. Net Electrical Energy Generated (WH) 536,562 4,241,546 36,490,658
]
- 19. Unit Service Factor 100.0 93.6 86.8 1
- 20. Unit Availability Factor 100.0 93.6 86.8
- 21. Unit Capacity Factor (Using MDC Net) 87.5 88.3 83.9
- 22. Unit Capacity Factor (Using DER Net) 87.0 87.7 82.5
- 23. Unit Forced Outage Rate 0.0 6.4 4.6
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
Refueling / Maintenance outage, 10/2/87, approximately eight weeks
- 25. If Shut Down At End Of Report Period, Estimated Date of Startup:
N/A
- 26. Units In Test Status (Prior to Commercial Operation):
Fo:.ecast Achieved INITIAL CRITICALITY 05/06/81 05/08/81 INITIAL ELECTRICITY 05/24/81 05/25/81 QJMMERCIAL OPERATICN 08/01/81 07/30/81
)
I Form 2/30
u.
4
[
DOCKET No; 50-364
~
UNIT 2
I
'pA72 sentomkor 1.
1987
. D. Woodad COMPLETED BY..
(
TELEPHONE (205)'899-5156
~
i August j
510NT11 l
DAY AVERACE DAILY POWER LEVEL DAY' AVERACE DAILY POWER LEVEL j
(MWe-Net)
(MWe Net) 807 238 g
g7 2
808 gg
-239
~
'809-
- - - - -- -- - --- - -- g 9 - -
550 3
4 809 20 812
-(
)
808 811 J
3 y
812 1
6 807
, 22 807 813 7
3 g
808 24 809-
[
9 806 23-807 10 m
26 809 11 805 27 810 806 810 12 3
13 tiO9 29 807 636 10 811 14 15 260 33 812 16
_240 (NSTRUC"UONS On this funn:1. list the average daily unit power !cvelin MWe Net for each day in the reporting month. Compute to
, the neare:t whole rne;swatt.
j (9(77)
(
-l 1
.l
L D 5 t o R R O -
n A E O 9 e r F B W 9 m i 4
M S
n a 3
. E
)
i p.
3 M T D 5 a e s P
0 t r n 0
. E
. 2 n
o 5 J S J
(
o d i E
E c n t G
V C
a c E
I N
w e
R T
E o n n U
O E E Y E C
R l o n e N N M T B N E O R l i o e
(
A A R
C c
s t n e e
O R T U a t c a s T N D D i O N E o e e n a e l c
E E P K T T E C O R t p v o D ci r
C I E L I
s l i
i F u
O N L E E T T d n a t f L o
D U P T C N e i v c o S
M M
E A E c
u r
O S
V u ed r n o E e
C U
E d h e t o f L m
A R
e t t s i C
P r
a n t s t(
a S
r r I a t r s o e
- r e o a f p G a e p I
w o
ph e s -
t e S R t
r s r i r i
e e o b P y t
)
b w c t i
r n 1 i
o c o h r t e 6 h
P a m x o n v 1 x
lll Ill l I I IIl I l I II IiI Il III E f E E 0 E
T S
N N
E O
N I
O 5
T P E L
C M D B
R T
l l l
I l
l l II I Ii I iI I I IlI II lII J
O O C
L C C E
S R
U M
E G
E W
U T E O
A S D m)
P Y O K
a n S C B
D H
. r i m c a N
T A
N ll l
I l
l lIIII iIi I III i I II iII a S l r
p O
c c x S
M E
8 t
(
S i E N
E W
T S
T D
O E N O A
d: l l a O
R N T R a a m r u u o e T
P C E P
/
o n n t h U
E I V E N
h a a u t H
R L E R t M M A O S
e - - - -
T l
ll Ill lIIIIIIII I !I iII iI iI M 1 2 3 4 I
NU R
OT F
C O G A n
N E 4
o D I R i
O T t
H T N a
T U W n
E H O i
M S D ma l
ll Ill lIIII iII I I II I I I ll l I x
E N
)
e O
n s
S i
n A
a e
E B
l c
R p
ni x
o L l
l l
I ll lI III II II I I I I I I i i i I E
i
(
t t &
s c
O
)
r T r n N
e e i g I S u
t i T R l r s n e A U 0
i o e i v E i R O a
R a i U H D
(
0 F e r t l l c
yT a a p e ni t o s i lll Il llIIII i I III IIIIlI Ii I t n g r r
n e n o r t o E m e l a t i t
- p t e l a n E
ni n u u r i r e P
o uif g e m e h Y
F s q a e e p d p t T
a E M R R O A O e - - - - - - -
l l
l Il ll I I III II III I I I iI I l I R A B C D E F G R 4
l l
l I
l l
l I i I I I I I I I 1 I II I ll i I d u 1
E 8
T 0
d A
7 e
D 8
l e d c e r h o c 6
F S 0
O 0
N F S l ll 1ll l1lII Ii II I l
II Ilii i I
t N
/Y,'
JOSEPH M.'FARLEY NUCLEAR PLANT UNIT 2
'\\
s1
['
t ;g 3
NARRATIVE SlfMARY.OF OPERATIONS N
.l
]
)
August,.1987 d,,I h
./
a A',
t
'\\
.s J
-/
- r. 's.
( hpf f'
t s
.ji 0
b' s :.
\\
b There was one significant power reduction during the modh' of August.
fj h(j On 8/14/87, power wtw reduced to allow containment acce.ev for the
/
j inspection and repair of motor-operated valve connections The unit
^
s g
returned to full pwsr operation on 8/19/87.
P
/
-/;
9q-pb Thh following major adiety-related maintenance was performed in the monk i
' /' '
of August:
/
a
' h
\\
f 1.
Solenoid splices and motor-operated valve rplices that were s
installed utilizing' methods not evaluated by design,for
's environmental qualification were re-termine.tdf'in'iestdpuce with
'ks newly approved EQ terminations on a priority asis.f
\\
. \\ 'i i
? 11 2.
Leakingwarm-upvalveswererepaired>onthefu/aine-driven w
.f s
f,H.
auxiliary ' feedwater ptmp.
V
,YkA t
3.
The cooler,was cleaned and tha belta whe replaced on the 2A
' ? %},
/
t
(,i charging pump.
Miscellanedo9 ::orrective-and prebent're uh tenaned 'was performed
/f4 4.
on the diesel generators.
\\
/
^
}
I g
1 t
i l
y A.
.i; f,
5 u
}
.a
'l
. 'l 8
ii ?f "N,,1 j
u
+
)
i,
__ -_--______j
OPERATING DATA REPORT DOCKET NO.
50-364 DATE 9/1/87 COMPLETED BY J. D. Woodard TELEPIKNE (205)899-5156 OPERATING STATUS Notes l
- 1. Unit Name:
Joseph M. Farley - Unit 2 l
- 2. Reporting Period:
August, 1987
- 1) Cunulative data since 1
- 3. Licensed Thermal Power ( N t):
2,652 7-30-81, date of
- 4. Nameplate Rating (Gross Ne):
860 commercial operation
- 5. Design Electrical Rating (Net MWe): 829
- 6. Maximum Dependable Capacity (Gross MWe):
864.9
- 7. Maxi num Dependable Capacity (Net MWe):
824.1
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report, Give Reasons:,
N/A
- 9. Power Level T6 Which Restricted, If Any (Net MWe):
N/A
- 10. Reasons For Restrictions, If Any:
N/A 1
'Ihis Month Yr-to-Date Cumulative
- 11. Hours In Reporting Period 744 5,831 53,376
- 12. Number Of Hours Reactor Was Critical 744.0 5,473.6 51,829.8
- 13. Reactor Reserve Shutdown Hours 0.0 0.0 138.0
- 14. Hours Generator On-Line 744.0 5,456.7 -
46,307.5
- 15. Unit Reserve Shutdown Hours 0.0 0.0 0.0 l
- 16. Gross Thermal Energy Generated (NH) 1,782,9.71 T3,755,743 117,073,733 l
- 17. Gross Electrical Energy Generated (NH) 566,926 4,470,550 38,479,820 1
- 18. Net Electrical Energy Generated (MWH) 536,562 4,241,546 36,490,658
- 19. Unit Service Factor 100.0 93.T 86.8
- 20. Unit Availability Factor 100.0 93.6 86.8 i
- 21. Unit Capacity Factor (Using MDC Net) 87.5 88.3 83.9
- 22. Unit Capacity Factor (Using DER Net) 87.0 87.7 82.5 l
- 23. Unit Forced Outage Rate 0.0 6.4 4.6 l
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
l Refueling / Maintenance outage,10/2/87, approximately eight weeks
- 25. If Shut Down At End Of Report Period, Estimated Date of Startup:
N/A
- 26. Units In Test Status (Prior to Commercial Operation):
Forecast Achieved INITIAL CRITICALITY 05/06/81 05/08/81 INITIAL ELECTRICITY 05/24/81 05/25/81 COMMERCIAL OPERATION 08/01/81
_ 07/30/81 Form 2/30
]
50-364'
. DOCKIT No.
UNIT
~2 DA71 Sentombnr 1,'3937 COhfPLEIIp sy.' J. D.- Woodard l
TELEPHONE; (205) 899-5156
]
Au8un 410tml DAY AVERACE DAILY POWER LEVEL DAY AVERACE DAILY POWER LEVEL
- OfWe Net)-
(MWe-Net )
807.
238 g
37 2
808 gg 239
-)
~
~~~ ' 809
-........... g 9 _.
550 3
4' 809 gg 812 I
808 811 g
21 6
807 22 812 807 813-7 23 g
808
- 4 809
[
9 806 gg-807 10 m
26 809 i
l Ig 805 gy, 810 810 12 806 43 l
13 809 29 807 J
636 30 811 14 IS 260 33 812 16 240
'l INSTRUCEONS i
On this form:r. list the sver:ge daily unit power icvelin MWe-Net for each d:y in the reporting month. Compute to -
, the nemic:t whole me;swatt.
1 1
1 (9(77)
'l C
.l I
i 1
1
=
L D 5 t o R R O -
n A E O 9 e r F B W 9 mi 4
M S
n a 3
. E.
)
i p.
3 M T D 5 a e s P
0 t r n 0
. E '. 2 n
o 9 J S J
(
od i E
E c n t G
V C
a c E
I N
w e
R T
E o n n U
O E E T E C
R l o n e N N M T B N E O R l i o e
(
A A O
R T U a t c a s T N D D H R
C c
s t n e e
E E P O N E o e e n a e l c
K T T E C O R t p v o D c i r
C I E L I
s l i
i F u
O N L E E T T d n a t f L o
D U P T C N e i v c o
)
S M
E A E c
u r R O
S V
u e d r n o E e
C U
E d h e t o
- f. L m
A R
e t t s i
(
a C
P r
a at s t S
r r I a t r s o e r e o a f p G a e p I
w o
p h e s -
t e S R t
r s r i r i
e e o b P yt
')
b w c t i
r n 1 i
o c o h r t e 6 h
P a m x o n v 1 x
lll llllIIl III 1IIIIiII1iI1 E f E E 0 E
T S
N N
E O
N I
O 5
T P E L
C M D B
U O O C
D C C E
R T
lll IllliI i IlIl l IIIl II iIIi S
R U
M E
G E
W U
T E O
A S D m )'
P Y O K
a n S C B
~. r i D
H N
T m c a A
N lll IllliI iIl IIiIIi iIIll1i a S l O
r p
c c x S
M E
4 S i E N
E t
(
W T
S T
l l a D
R N T R C
O E N O A
d: a a m r u u o e T
P C E P
/
o n n t h U
E I V E N
h a a u t H
R L E R t M M A O S
e - - - -
T lll Il llIIIIIIIiIIliII iI1i I
M 1 2 3 4 NU R
O T
F C
O G A n
N E 4
D I R o
O T i
t H T N a
T U W E H O n
i M S D ma l ll I lllIIIIII IIII1iI IIi 1I x
E N
)
e O
n s
S i
n A
a e
E B
l c
R p
ni x
o L l ll I l llI I III IIII I1lIIl llI E
i
(
t t a s
c N
e e i g O
)
r T r n I S u
t i T R l r s n e A U 0
i o e i v E i R O a
R a i U H D
(
0 F e r t l l c
yT a e p lll IlllIIIl1IiIIIiiII1lII t n g r r
~
n a n o r t o E e nit o s i m e l a t it
- p t e l a n E
ni n u u r i r e P
o uif g e m e h T
F s q a e e p d pt T
a E M R R oA O e - - -. - -
lll IlllIIII11lII II iIIIIi1 R A B C D E F G 4
1 E
8 T
0 d
A 7
e D
8 l
d u lll 1lllII III1I III IIlIIII 1 ed c e r h o c 6
F S 0
ll l l ll]11iII1II1i1ilIIII1 Y
O 0
N F 3 A
E' i
f6 Alabama Power Company v
o 600 North 18th Street Post Othce Box 2641 Birmingham, Alabama 35291-0400 Telephone 205 250-1835 O
f ~qy[,{ d' g
L Ln"Oce"l,'l,ioen, Alabama Power o
Y rne sournom electre system e
/
\\
September 11, 1987 Docket No. 50-364 Director, Office of Resource Management U. S. Nuclear Regulatory Commission Washington, D. C.
20555 Dear Sir; RE: Joseph M. Farley Nuclear Plant Unit 2 Monthly Operating Data Report Attached are two (2) copies of the August 1987 Monthly Operating Report for Joseph M. Farley Nuclear Plant Unit 2, required by Section 6.9.1.10 of the Technical Specifications.
If you have any questions, please advise.
Yours ve - truly ggy
/
\\.
R. P. Mcdonald RPM /JGS:mab Enclosures xc: Director, IE (10 copies)
[
/p /
]
Director, RII (1 copy)
/C 4,
J v
./
/I$/
/ 4 t