fppck)J:sG PRELIMINARY N0TIFICATION - NOT FOR PUBLIC DISCLOSURE October 14, 1975 f'5#:

- P PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE

--PN-75-107 1

This preliminary notification constitutes EARLY notice of events of POSSIB'E safety or public interest significance. The information preseq;ed is as initially received without verification or evaluation and is basically all that is known by OIE staff as of 4:00 p.m. on the date of this notification. IT SHOULD BE SPECIFICALLY NOTED THAT THIS NOTIFICATION MAY CONTAIN INFORMATION THAT LATER MAY BE DETERMINED TO BE INACCURATE OR INCONSISTENT. AN OFFICE OF INSPECTION AND ENFORCEMENT NOTIFICATION 0F AN INCIDENT OR OCCURRENCE (BLUE SHEET) SUBSEQUENTLY

~

~

~

WILL BE ISSUED IF WARRANTED.

Facility:

Commonwealth Edison C' ompany (Quad-Citt es Unit 2)

Subject:

INDICATIONS IN 4" RECIRCULATION PIPIN'J The licensee informed Region III that ultrasonic testing (UT) of the 4" type 304 stainless steel bypass lines around the primary recirculation pump discharge valves revealed an indication of a crack approximately 1" long. The indication was found on the unist.". ole portion of the j

B loop on the pipe side of the pipe to weldolet wid in the hest affected zone. The bypass pipe was replaced in February 1975. 'There were no reportable indications identified during the two previous UT examinations N

of the new piping.

The licensee,is currently reviewing corrective action.

ge s

(

The plant was shutdown on October 3 for a fuel maintenance outage and was originally scheduled to resume operation on October 28.

Some delay in startup is expected.

j Region III received notification of this occurrence by telephone from N. Kalivianakis, Plant Superintendent, at 12:00 noon on October 13, 1975.

Contact:

RFWarnick, IE x7261 HDThornburg, IE x7353 JGDavis, IE x7541 Distribution:

Chairman Anders Commissioner Mason S. J. Chilk, SECY Commissioner Gilinsky Commissioner Rowden G. F. Murphy, JCAE Commissioner Kennedy C. C. Kammerer, CA L. V. Gossick, EDO D. F. Knuth, IE J. A. Harris, PA B. C. Rusche, NRR J. La Fleur, ISP T. J. McTiernan, AIA K. R. Chapman, NMSS H. K. Shapar, ELD

\\

E St Er k ; MNBB b ; Luge a u Transmitted: P Bldg V B ;