Notice of Violation from Insp on 870922-1105.Violation Noted:Precaution Statement in Procedure Which Stated That Opening Racking Screw Shutter on Closed Circuit Breaker Would Trip Breaker Incorrect
ML20236S799
Person / Time
Site: Quad Cities  
Issue date: 11/23/1987
From: Harrison J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
To:
Shared Package
ML20236S776 List:
References
50-254-87-25, 50-265-87-25, NUDOCS 8711300101
Download: ML20236S799 (1)


Text

-

l NOTICE OF VIOLATION l

Commonwealth Edison Company Docket No. 50-354-c<

i Docket No. 50-265 1

l As a result of the inspection conducted on September 22 through November 5, 1987,'and in accordance with 10 CFR Part 2, Appendix C - General Statement of Poli,cy.and Procedure for NRC Enforcement Actions (1985), the following violation was,1dentified:

10 CFR 50, Appendix B, Criterion V, as implemented by the Commonwealth Edison I

Operational QA program, requires that activities affecting quality be l

prescribed by documented instructions procedures, or drawings, of a type l

appropriate to the circumstances, and be accomplished in accordance with these peg. instructions, procedures, or drawings.

p a

s 4

4

  • ' Con: rad to"the above, Proctiure No. 00P 6500-4, which is used in racking-out 4160 volt ranua11y operated air circuit breakers, was inadequate because of the following:

1.

Theprecautionstatementint$eprocedurewhichstatedthatopeningthe racking' screw shutter on a closed circuit breaker would trip the breaker was incorrect.

2.

The procedure did not caution the operhor to verify the position of the open/close indicator prior to proceeding to rack-out the breaker.

3.

The procedure did not caution the operator to actuate the manual trip button prior to rack-out of the breaker.

This is a Severity Level IV violation (supplement I).

l Pursuant to the provisions of 10 CFR 2.201, you are required to submit to this office within thirty days of the date of this httice a written statement or explanation in reply, including for each violation: (1) corrective action taken and the results achieved; (2) corrective action to be taken to avoid I

further violations; aM (3) the date when full compliance will be achieved, f f Consideratigo may be given to extending your response time for good cause shown.

' /'

/

(

s \\ - M -Yl h.

Dated J.,J. Harrison, Chief Enginoch ng Branch Divistor. of Reactor Safety e