Intervenor Exhibit I-OHIO-G,consisting of Undated Facility Certificate Application Re Excavation & Backfill & Summary of Static & Dynamic Soil Properties
ML20236P586
Person / Time
Site: Davis Besse 
Issue date: 08/06/1986
From:
TOLEDO EDISON CO.
To:
References
ML-I-OHIO-G, NUDOCS 8708120429
Download: ML20236P586 (2)


Text

- _ _ _ _ _ _ _ _ _ _ _ _ _

The Toledo Idisen Oc=pany

~ N/d -' b Davis-Besse Certificate Application DOL KE fil backfill.

These include the borated water storage tank, electric uwkC h

manholes, diesel oil storage tank, and the service water piping manholes.

In all cases, the factor-of-safety of ultimate bearing capacity E MAY 18 P6 :39

~

maximum contact stress was greater than five.

These data are included Off!n -

Ac in Table 1302-B-3 00CKETite 4

L W!U iiHANCH Based on the gradation of the backfill material (crushed granular

=aterial er glacial till) and placement criteria, Catego:7 : backfill i

vill not underge differential consolidation or liquefaction under l

the effects of the vibratory motions of the safe shutdevn earthquake.

Consequently, there i-no potential for these earthquake-induced phenomena to cause instability of the Category : backfill beneath the foundations of the station.

Excavation and Backfill Plan and profiles of structural backfill are presented in Figure 1302-E-19 Structural backfill in the station area vill consist of granular material obtt.ined frem off-site quarries and/or recompacted glacial till from borrow excavations.

Ctructural backfill is to be placed in loose lift thicknesses ranging frem 12 in. in large work areas to 6 in. in small verk areas.

Structural backfill is to be compacted to 98% of the maximum dry density determined in accordance with ASTM Specification ::c. Ef98 Method D, latest revisien, or to 807, relative density determined in accordance with ASW Specification : o. 000!.9 Sumnary of Static and Dynamic Soil Properties Major soil deposits at the site consist of a glaciciacustrine and a till deposit.

The glaciolecustrine deposit censists of a stiff, N1JCLEAR RECllLATORY COMMIS$10N Docket No. N -3Vb M b Official Esh. No, la the matter of Staff IDENTIFIID V

Applicant.

RECEIVED Intervenot REJEC~lD Cent'g Off'r Actrac OATE

[

Other Witness

  1. 4' t

N,.,,,,

1302-B-17 8708120429 060006 PDR ADOCK 05000346

/

0 PDR g

The Toledo Edisen Cc pany Davis-Besse Certificate Application fissured, gray and brown silty clay.

Representative values for selected static properties for the glaciolacustrine deposit are listed as follows:

Representative Property Value*

Range of thickness in statier, area, ft

-6 to 10 Water content, %.

2h e

Liquid limit, %

51 Plastic limit, %

23 Tetal unit weight, lb/cu ft 125 Unconfined compression strength,' tons /sq ft 35 Standard penetration resistance, blovs/ft 12.

~

Permeability, em/see less than 10 Ccepression index, C 0.15 c

0.h

("/

Recon:pression index, C r

s.

~

Coefficient of consolidation, C, sq cm/sec 0 5 x 10 y

Range of maximum past effective consolidation h to 12 pressure, tons /sq ft

No dynamic parameterc vere determined for glaciclacustrine deposit because no major structures are to be founded en the deposit.

The till deposit consists of a hard, fissured, grey to brewn silty sandy clay with generally less th9.n 10% gravel.

Representative values for selected static and dynamic properties for till deposit are listed as follows:

Representative Property Value Range.of thickness in station area, ft 6 to 10 Water content, %

15 i

O 1302-B-16