ML20236L040

From kanterella
Jump to navigation Jump to search
PNO-77-023:on 770204,while Changing 4 by 4 Foot Panel on Glovebox in Fab 1 Area of Plutonium Facility,Spread of Airborne Plutonium Contamination from Glovebox Into Room Occurred
ML20236L040
Person / Time
Issue date: 02/07/1977
From: Dreher F, Roy G, Thompson D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
To:
References
PNO-77-023, PNO-77-23, NUDOCS 9807100190
Download: ML20236L040 (1)


Text

l

[]- f > v! j n,

j L

l PRELIMINARY ' NOTIFICATION N

N

'~

February 7, 1977 p

PRELIMINARY NOTIFICATION OF EVENT OR UNUSUAL OCCURRENCE-PNO-77-23 This preliminary notification constitutes EARLY notice of an event of POSSIBLE safety or public interest significance. The information presented is as initially received without verification or evaluation and is basically all that is known by IE staff on this date.

l Facility:

Babcock and Wilcox Company Plutonium Facility Leechburg, Pennsylvania

Subject:

, RELEASE OF PLUTONIUM CONTAMINATION TO RESTRICTED AREA -

7:45 P. M., FEBRUARY 4, 1977 While changing a 4 by 4 foot panel on a glovebox in the Fab 1 area

.of the Plutonium Facility, a spread of airborne, plutonium contamination from the glovebox into the room occurred. The contamination escaned hath tents used for contamination control. An air sample in the room indicated airborne plutonium concentration of approximately 1200 MFC-hrs when averaged over 24 hrs - an individual is allowed to be exposed to 520 MPC-hrs of an airborne contaminant during a calendar quarter. All personnel in the room l

or in the tents were protected by either supplied air or full. face mask respirators. Based on available air sampling, after protection factors E3 for masks were used, five people were exposed from 61-122 MPC-hrs; these

, concentrations are less than 25% of'the limits allowed by the Regulations.

There was no release of radioactivity to the unrestricted area or other parts of the facility.

Media interest is not expected but is possible. The Commonwealth of Pennsylvania has been informed. A press release is not planned.

NRC, Region I, (Philadelphia) received notification of this occurrence by telephone from Mr. J. S. Dziewisz on February 5, 1977.

h

Contact:

FADreher, IE x27261 GWRoy, IE x27261 DThompson, IE x27541 Distribution:

Chairman Rowden Commissioner Kennedy S. J. Chilk, SECY Commissioner Gilinsky C. C. Kammerer, CA G. F. Murphy, JCAE L. V. Gossick, EDO K. R. Chapman, NMSS R. G. Ryan, OSP S. H. Hanauer, EDO E. Volgenau, OIE J. A. Harris, PA B. C. Rus'che, NRR H. K. Shapar, ELD T. J. McTiernan5 OIA Transmitted: PBldg[ N H St/jLf #;L;;._MNBB/.*/I[;'_. Luge

.._..s__.

PRELD11 NARY NOTIFICATION s

\\

l

\\

~~

9807100190 770207 PDR I&E l

PNO-77-023 PDR l

1