Monthly Operating Repts for Feb 1989 for Zion Units 1 & 2
ML20236C340
Person / Time
Site: Zion  File:ZionSolutions icon.png
Issue date: 02/28/1989
From: Austin G
COMMONWEALTH EDISON CO.
To:
Shared Package
ML20236C200 List:
References
NUDOCS 8903220091
Download: ML20236C340 (11)


Text

{{#Wiki_filter:_ OPERATING DATA REPORT 50-295 DOCKET NO. DATE 03 07 89 COMPLETED BY G- ^"" i n TELEPHONE 317-746-2084 QPERATINQ STATUS

1. Unit Nanee:

ZION UNIT 1 Nota

2. Wing Period. 0000 890201 to 2400 890228 3250
3. Lisensed Thennal Power (MWt):
4. Nameplate Rating (Gross MWe):

1085

5. Design Electrial Rating (Net MWe):

1040

6. u==i=um Dependable Capacity (Grom MWe):

1085

7. Maxhaum Dependable Capacity (Net MWe):

1040

8. If Changes Occur la Capacity Ratings (Itans Number 3 T1uough 7) Since Last Report, Give Reasons:

N/A

9. Power Level To Which Restricted,if Any (Net MWe).

N/A

10. Reerans For Restrictions,If Any:

A This Month Yr. to-Dete Cumulative

11. Hours la Reporting Period 672.0 1416.0 132,936.0
12. Nanaber Of Hours Reactor Wm Critical 140 7 848.8 93.681.9
13. Reactor Reserve Shutdown Hours 0.0 0.0 2,621.8
14. Hours Generator On.Line 140.7 832.0 90,981.4 IS. Unit Reestve Sbatdown Hours 0.0 0.0 0.0
16. Geem Therusal Energy Genereled (MWH) 383,/05 2,481,951 260,322,541
17. Gre a Electrical Enugy Generstad (MWH) 127,942 832,/43 64,690,699
18. !W E actrical Emergy Generated (MWH) 115.398 788,300 83,899,389
19. Unit Service Feeto, 20.9 58.7 68.T
20. Unit Availability Factor 20.9 58.7 68.4
21. Unit Capacity Factor (Using MDC Net) 16.5 53.5 60.7
22. Unit Capacity Factor (Uning DER Net) 16.5 53.5 60.7
23. Unit Forced Outage Rate 79.0 40.5 12.5
24. Shadowns Scheduled Over Next 6 Months (Type. Dete,and Duration cf Each):
25. If Shut Down At End Of Report Perso:1. Estknoted Date of Startup:
26. Units in Test Status (Prior to commerelal Operation):

Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION nr2nstunge fg R

AYERAGE DAILY UNIT POWER LEVEL 1 DOCKET NO. 50-295 UNIT Zion Unit 1 03-07-89 DATE COMPLETED BY G. Austin TELEPHONE 312-746-2084~ ) MONTH FEBRUARY l l DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MW& Net) (WWe Net) 1 458 g7 -11 l 912 -11 2 gg 1027 -11 3 1031 -15 4 20 1038 -20 5 21 609 -14 6 n 7 -10 23 -11 -12 -12 8 24 -12 -12 25 10 -11 -12 26 11 -11 27 -12 -11 12 3 -12 -11 13 3 -11 14 30 15 -11 33 -11 16 INSTRUCTIONS On this format, list the average daily unit power level in MWe. Net for each day in the reporting month. Compute to l the nearest whole megawatt, l 1 (9/77) I-1 L-

s4 E RN 7 u7 CE E a mt 0A - AROG o 2 LUT a efL 3 1 PT M 0G3 w e EPNA o c his i n RUWE n tc e ROT o EYE r e or O DS TBN rr t t u - a t D on c TKT A r Gah D Co e NUC E iR NAHIS pS mP T &t e ct WTS Y r E eAn I s e O &A r u v DND W o W a e EfEE TILBN t C P r 0 UAO1A 0 HRC M 4 SD N OOY 1RT R E SA TTTKM IANAI NEEER UHWLP hfd[ YRA ll U a d vuo I R n B h a E v n

  • a F

EEE M s2 4 H 3 TN0 e 8A e e t w nr T o

wp e

R c Ee i O L R FER 1~g5 g6 Igi d ) 1 n ]j a i lpx E g{E (t / e ru if l F 3 a E=$ 1 n t c !zM 3 e 5 m pt

nin o u s qm

-{F aE F eRAB 2 6 0 2 e t 0 aD 9 d 8 e l du ed ce rh o c i. FS i N 2 FS 1

OPERATING DATA RRPORT DOCKET NO. 50-304 -l' DATE 03 07 89 COMPLETED BY G. Austin TELEPHONE 317-746-2084 OPERATING STATUS Nota

1. Unit Neans:

ZION UNIT 2 0000 890201 to 2400 890228

2. Reporting Peded:

3250-

3. Liesmand Thannel Power (MWt):
4. Namspinte Rating (Gross MWe):

1085 1040

5. Design Electrieel Rating (Net MWe):

. 6. Maximum Dependable Capacity (Grom MWe): 1085 1040

7. Maxhauen Dependable Capac;ry (Net MWe):
8. If Changes occur in Capacity Ratings (Items Nuseber 3 nrough 7) Since Last Report, Give Reasons:

N/A-

9. Power Level To Which Restricted,1f Any (Not MWe):

N/A

10. Rassens For Restrictions.If Any:

This Month Yr. to Dete Cumaletive i1. Heers la Reporting Peded 672.0 1416.0 126,649-12.- Number Of Hours Reactor Was Critical 637.8 989.9 927.662

13. Reactor Reserve Shutdown Hours 0.0 0.0

-2z6.1

14. Hours Generator On.Line 617.7 967.3 90178.6 i

!$. Unit Reserve Shutdown Heere 0.0 0.0 0.0

16. Grom Thenmal Energy Generated (MWH) 1.814.355 2.540,431 263,014,575
17. Gross Electrical Energy Generetad (MWH) 614,052 854,631 81,929,528
18. Net Electrieel Energy Genessted (MWH) 5R7.R19 804.765 80.567.653 l
19. Unit Servies Festor 91.9 68.3-71.2
20. Unit Aveliability Factor 91.9 68.3 71.2
21. Unit Capacity Factor (Using MDC Net) 81.3
22. Unit Capacity Factor (Using DER Net) 83.3 54.6 61.2 54.6 61.2 23.~ Unit Forced Outage Rate 7.9 31.5 13.6
24. Shutdowns Scheduled Over Next 6 Months (Type.Dete.end Duration of Each):
25. If Shut Down At End Of Report Period. Estimated Date of Startup:
26. Units la Test Santes (Prior to Commercial Opsession):

Forecast Achieved INITIAL CRITICALITY INITIAL ELEC11LICITY COMMERCIAL GPERATION (4/77)

v-AVERAGE DAILY UNIT POWER LEVEL 50-304 DOCKET NO. UNIT Zion Unit 2 DATE Q3 07 89 COMPLETED BY G. Austin 312-746-2084 11LEPHONE MONTH FEBRUARY l DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net) (MWe-Net) - l 1 217 37 1058 394 1059 2 gg 3 463 39. 1059 987 297 4 20 5 1049 21 -20 l l 1044 205 ) 6 22 7 1027 23 RRR l l 1031 g 24 1030 1041 25 1030 1047 988 10 26 1054 1034 33 27 1057 12 28 1021 1057 13 14 1056 30 1051' 15 3, 16 1055 t INSTRUCTIONS On this format, list the average daily unit power levelin MWe Net for each day in the reporting month. Compute to I l the nearest whole messwatt. l l (9/77)

7 u7 ZA s o nt n0A - I K n 2 RA iD t i3 1 UE c u e e SL 70G3 v c tr n S sn i tc e EG ao EY eo r l i w RN 1B r t r AD D onc PI G Co e K E iR t OC ie T &tct br E eAn TA ipr L s e P h u v x y E Ef a e UE g C P r g DV o L 4 NA WV ODY TA UR HP SS M Y RA d R UR h' N B u E F luA " s D H 3 N T A N0 e N 0 et 9 s a r t n T ew op R kE e O 'L R PER T g )Q IN ggi U 1 }g l I A g55 l F 3 I$ ] 4 5 n o s aE EN F eRA 2 0 2 e 2 taD 0 d 9 ~ l 8 du ed c rh oFS .o 2 N FS I

i 1 i F_ERRUARY MAJOR SAFETY RELATED MAINTENANCE J Equipment Name Work Performed !j l l Steam Generator Replaced gaskets on all steam i Primary Manways generator primary manways. Letdown pressure control Replaced valve. valve bypass valve IVC 8409 { l l l l l l 1 1 l l l 4 i I 1397t 0934A i

f I v 49 8 t ' FEBRUARY

SUMMARY

OF OPERATING EXPERIENCE UNIT 1 The Unit entered the reporting period at.a power level Of? 495 MWe (48% l . ' reactor ' powe r)..On February 6th at-2042 hours, the: Unit was shutdownJtoL repair heater drain tank rupture disc. Went.to cold shutdown to. repair leaks on 18 and 1C: Steam Generator primary manways. The Unit'remainedLin. .i . cold shutdown. the remainder of report ' period. Availability' factor 20.9%. 1 a UNIT 2 The. Unit entered:the report pe'riod' critical. On _ February 1st. at. 0855 . hours, the Unit was1 synchronized to the ' grid. On February' 20th at 1146: hours the Unit was; shittdown due to pressurizer spray. valve; packing leakage, and on February 21st at 2158 hours; the Unit.was-made. critical. On February 22nd at 0907 hours., the unit was synchronized to. the grid. The.Unil remained on line the remainder of the report period 'ending at a 4 L power level of 1086 MWe (99% reactor power) and.having.an availability. ] f actor of 91.9%. j . l - i ~.j ?. ~ l 1 L 'i 1 1 i (. I 1 l-1 l 1 l L i

)

lj J l 4 1 1397t l .0934A

J 'i REFUELING INFORMATION REQUEST Questions: l. Naiae of f acility. 1 -1 2. Scheduled date for next refueling shutdown. I 3. Scheduled date for restart following. refueling. l 4. Will refueling or resumption of operation thereafter require a technical specification change or other license amendment? i If answer is yes, what,. in general,,will these be? If answer is no, has the reload fuel design and. core configuration been reviewed by your Plant Safety Review Committee to determine I whether'any unreviewed safety questions are. associated with the core q reload (Ref. 10 CFR Section 50.59)? j If no such review has taken place, when is it scheduled? 5. Scheduled date (s) for submitting proposed licensing action and supporting information. 6. Important licensing considerations associated with refueling, e.g., new or dif ferent fuel design or supplier, unreviewed. design or 1, performance analysis methods, significant changes-in ' fuel design, new operating procedures. 7. The number of fuel assemblies (a) in the core and (b),in the' spent fuel storage pool. l 8. The present licensed spent fuel pool storage capacity and'the size of any increase in' licensed storage capacity that has been requested or l is planned, in number of fuel assemblies. J l 9. The projected date of the last refueling that can be discharged to L the spent fuel pool assuming the present licensed capacity.- 1 1. d l L l l l I i Page 1 of 3 1397t . j' 0934A u

y i Unit 1 - Answers 1 1. Zion Unit 1 2. Next refueling outage is currently scheduled to begin on September 7, 1989. 3. Cycle 12 is scheduled to start on November 16, 1989. 4. One Technical Specification change was made for the next cycle (Amendment No. 114) and two others are being considered. The completed change involves line and valve assignment changes associated with the recently ) approved Tec'n Spec change for the Boron Injection Tank (BIT) removal. No j additional FSAR Chapter 14 analyses will be required. Of the two Technical Specification change requests being considered for l next cycle, the first will result from a new LOCA analysis being pursued that will allow steam generator tube plugging levels of greater than 10%. l The second would allow for new methods of steam generator repair (tube sleeving). l l i The reload safety review is planned for May 24, 1989. The On-site Review 1 will be held after that review. l u 5. None { l 6. The revised General Operating Procedures should be implemented during l Cycle II operation. f 7. The number of fuel assemblies l l a) in the core is 193, and j l b) in the spent fuel storage pool from Zion Unit 1 is 632. Four of the last discharge of 80 assemblies were originally Zion Unit 2 assemblies. 8. The present licensed spent fuel pool storage capacity (shared with Zion Unit 2) is 2112 fuel assemblies. 4 9. Zion Station will lose full core discharge capability in 1993, based on l the latest Nuclear Stations Refueling Schedule. i i Page 2 of 3 13971 0934A

v l i. t

Unit 2 - Answers El.

Zion' Unit 2 y

2.. Cycle 11 will shut down for refueling approximately March 6, 1990.
3. ~ Cycle 12 should start up approximately May 12, 1990.

j 4. .The reload safety evaluation meeting.for Cycle 12 is scheduled for' j December 6,,1989. The on-site review will be held after this meeting. l S. None _l l 6. The revised General-Operating Procedures should be implemented during. ,l . Cycle 11 operation, j

7. 'The number of fuel assemblies l"

.a) in.the core is 193,'and b) . in'the spent fuel storage pool f rom. Zion Unit 2.is 664. 8. The present licensed spent fuel pool storage capacity-(shared with Zion Unit 1)fis' 2112 fuel assemblies. 9. Zion Station will lose full core discharge capability in 1993, based on 1 the latest Nuclear Stations Refueling-Schedule. -) I l l I I l I Page 3 of.3 1397t 0934A~ s}}