7fw\\ Commonwealth Edison
- j One Rr t Natior/J Plaza, Chicago, Illinois -
l I
,-(
/ Address Reply to: Post Office Box 767
~
[
' N/ Chicago, Illinois 60690 0767 February 23, 1989 t
Mr.. Daniel Muller, Directorate III-2 Office of Nuclear Reactor Regulation U.S. Nuclear-Regulatory Commission Washington, DC 20555 Attn: Document Control Desk-
Subject:
Byron Units 1 and 2 Braidwood Units 1 and 2 Application for Amendment to Facility Operating Licenses NPF-37, NPF-66, NPF-72, and NPF-77 NRC Docket Nos. 50-454/455 and 50-466/457
Reference:
May 31, 1988, letter from K.A. Ainger to'T.E. Murley
Dear Mr. Muller:
The referenced letter provided the application for amendment to Facility Operating Licenses NPF-37, NPF.-66, NPF-72, and NPF-77 to revise Technical Specification Surveillance 4.8.1.1.2.f.2 and involving the diesel generator's capability to reject the largest single load. Byron and Braidwood have implemented a method to reject several loads that combined constitute a load greater than or equal to 1034 KW.
This method simulates the largest anticipated emergency load of the essential service water (SK) pump.
Since it l er not feasible to align the SX system to duplicate it's maximum rated load during the diese1' generator 18 month surveillance, several loads are combined to simulate the largest single load.
Therefore, Commonwealth Edison requests the referenced application for amendment be withdrawn at this time.
Please direct any questions you may have concerning this matter to this office.
Very truly yours, h
4t%U
/
6 R. A. Ch/zanowski Nuclear Licensing Administrator
/sc1:0047V:1 cc Resident Inspector-Byron Resident Inspector-Braidwood f
S. Sands, Project Manger-NRR L
L. 01chen, Project Manager-NRR I
Regional Administrator-RIII l h M.C. Parker-IDNS 890314041s 890223 PDR ADOCK 0500