ML20235V207

From kanterella
Jump to navigation Jump to search
Special Rept:On 870928,train a Upper Range Static Reactor Vessel Level Indication Declared Inoperable Based on Input Failures from Transmitter & Hydraulic Isolator.Transmitter Under Investigation
ML20235V207
Person / Time
Site: Beaver Valley
Issue date: 10/09/1987
From: Lacey W
DUQUESNE LIGHT CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
ND3SPM:0054, ND3SPM:54, NUDOCS 8710150038
Download: ML20235V207 (2)


Text

_ _ - _ _ _ _ _ _ _ _ - -

.e AL< "

.s!

s!Ife.-

'Ap M

rei pnon em3936000 Y$Yo'((*' "

October 9, 1987 l

Shippingport. PA 15077*

ND3SPM:0054 Beaver Valley Power Station, Unit No. 2 Docket No. 50-412, License No. NPF-73 Special Report United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

In accordance with Beaver Valley Technical specification 3.3.3.8,

" Accident Monitoring Instrumentation",

the following Special Report is. being submitted.

This report is required when the conditions specified in Technical Specification 3.3.3.8.C are not satisfied.

On September 28, 1987, during inspection and testing of the Plant Safety Monitoring

System, the Train A

Upper Range Static Reactor Vessel -Level Indication was declared inoperable based on input failures from the transmitter and it's hydraulic isolator.

Maintenance Work Requests were initiated for both.

Preliminary investigation has determined the problem with the hydraulic isolator does not affect the channels operability.

The transmitter is still under investigation.

The only procedure that calls solely for the use of the Upper Range Static indication is Emergency Operating Procedure, FR-I.3 Step 8,

Detection of Void Size during Natural circulation.

Provisions are made in the procedure for an inoperable Reactor Vessel Level l

' Indication System.

The Train B Upper Range Static channel, both Full i

Range Static

channels, and both Dynamic channels are operational.

There has been no compromise in the plant safety as the redundant train and full range channels provide sufficient information to j

analyze postulated events.

j

\\

Very truly yours,

/

y, m. 'S. Lace [

Plant Manager

(

tlu l

Attachment 8710150038 871009 PDR ADDCK 05000412 l

S PDR Y

l.

L

fig j @gg)5 a

fu e

m

[fpK tbber 9,x19'87 "f

ND3SPM:0054 jgC Page'two.

,g

[c icc:;Mr. WilliamLT. Russell 6 Regional Administrator' 1 United. States Nuclear' Regulatory Commission Region 1 L

. King of Prussia, PA 19406 I

C..-.A.;Roteck, Ohio Edison Mr. Peter Tam,- BVPS Licensing Project Manager.

United States. Nuclear RegulatoryLCommission Washington, DC 20555 F. I. Young, Nuclear Regulatory Commission, BVPS. Site Inspector-J. Beall, Nuclear Regulatory Commission,

.BVPS Senior Resident Inspector L..Prividy,; Nuclear Regulatory Commission, BVPS Resident Inspector Mr. Alex Timme, CAPCO Nuclear Projects Coordinator Toledo' Edison INFO Records' Center suite 1500 1100 Circle 75 Parkway

. Atlanta, GA 30339 G. E. Muckle, Factory. Mutual Engineering, Pittsburgh

.Mr. J. N. Steinmetz, Operating Plant Projects Manager Mid Atlantic-Area Westinghouse Electric Corporation Energy Systems Service Division Box 355 j

Pittsburgh, PA 15230 American Nuclear Insurers

.c/o Dottie Sherman, ANI Library The Exchange Suite 245 270 Farmington Avenue i

Farmington, CT 06032

.-. - - - _ _ _ _ - _ _