Special Rept:Fire Protection Sys Impaired for Greater than 7 Days.On 890118,rust Holes Noted on Fire Door 67-2.On 890121,repair Required for Thermolog Insulation.Caused by Time Deterioration.Fire Patrols Established
ML20235M997
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 02/23/1989
From: Conway W
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
L-89-58, NUDOCS 8902280528
Download: ML20235M997 (2)


Text

_ _ _ . _ _ _ _____

.;f: .: : ,

1

)

, &(

,' l

.t P.O. Box 14000, Juno Beach,FL 33406-0420 s ;c ,;

FPL l l

1 FEBRUARY 2 3 1989 L-89-58 l

U. S. . Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555 Gentlemen:

Re: Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Special Report - Breached Fire Barriers and Other Fire Protection System Impairments In accordance with Technical Specification 6.9.3.c,.the attached Special Report is provided for your information.

Should there be any questions on this information, please contact us.

Very truly yours, h[ F Conway y/ W. Seni Vice President - Nuclear WFC/RHF/gp' Attachment cc: Malcolm L. Ernst, Acting Regional Administrator, Region II, l i

USNRC Senior Resident Inspector, USNRC, Turkey Point Plant 890228052089g350 i pnR ADOCK O pg y if 8 .

hyiepyp.,-,u.m,~

an FPL Group company

_ _ _ _ _ . . _ . _ _ _ _ _ _ _ _ _ _ _ _ . _ _ ___________________i

m.

1 I

I J

SPECIAL REPORT FEBRUARY. 23, 1989 FIRE PROTECTION SYSTEM IMPAIRMENTS REQUIRING NRC NOTIFICATION I l

l PURPOSE:

Technical Specification (TS) 3.14.5.b requires the submission of a report to the NRC if a non-functional fire barrier penetration.is not returned to functional status within 7 days. TS 3.14 also states that.certain other i conditions require NRC notification. In accordance with the above requirements, this special report is being generated in order to notify the NRC.  !

l EVENT:

Fire Protection Impairment (FPI) Number 2254 was issued, on January 18, 1989, for -

rust holes through fire door 67-2. FPI 2257 was issued, on January 21, 1989, to repair thermolag insulation. 'I CAUSE AND CORRECTIVE ACTIONS:

The above impairments were caused by deterioration taking place over a period of time. Detector operability was verified and fire patrols were established, in accordance with Technical Specifications.

STATUS UPDATE i t

r FPI 2195, which identifies an impairment to flammastic, and FPI 2227, which identifies an impairment to barrier 75F, were previously reported as open.

FPI 2195 was closed on January 14, 1989, and FPI 2227 was closed on January 16, l 1989.

i: >

l I

t .. _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ __ _)