e STARwP TsST RssuLTS (Coen.)
f 4.9 STI-c91-019 Core Performance (TSN-127, 128 194, 195) 4 i
The purpose of this Test Instruction is to evaluate several of the primary f
reactor core performance parameters with respect to their corresponding
{
limits in the Technical Specifications. This testing is divided into the evaluation of the " global" parameters of core thermal power (CTP) and flow, Section 8.1, and the localized parameters listed below, Section 8.2:
I a.
Maximum Linear Heat Generation Rate (MLEGR);
l f
b.
Minimum Critical Power Ratio (MCPR);
Maximum Average Planer Linear Heat Generation Rate (MAPLaGR).
c.
Acceptance Criteria I
i Level 1 1.
Steady-state reactor power shall be limited to the rated Mwr and values on or below the minimum of either rated thermal power or the bounding licensed load line (8.1).
2.
The Maximum Linear Heat Generation Rate (MLHGR) during steady state conditions shall not exceed the limit specified by the Plant Technical Specifications (8.2).
3.
The steady state Minimum Critical Power Ratio (MCPR) shall exceed the minimum limit specified by the Plant Technical Specifications (8.2).
4.
The Maximum Average Planar Linear Heat Generation Rate (MAPLHGR) shall not exceed the limits specified by the Plant Technical Specifications (8.2).
There are no Level 2 or 3 Acceptance Criteria.