pecaopy ye t

UK; FED STATES 3

NUCLEAR REGULATORY COMMl8810N

=

O

%,.....,e#[

WASHINGTON. D.C. 30M64001 NORTHEAST NUCLEAR ENERGLCOMPANY. ET AL.

QQf&ET NO. 50-423 MILLSTONE NUCLEAR POWER STATION. UNIT H0. 3 AMENDMENT TO FACILITY OPERATING LICENSE 1

Amendment No.146 l

License No. NPF-49 1.

The Nuclear Regulatore Commission (the Commission) has found that:

A.

The application for amendment by Northeast Nuclear Energy Company, et al. (tne licensee) dated May 1,1997, complies with the standerds and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the healtn and safety of the public; and E.

The issuance of this amendment is in &ccordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

9708260442 970821 DR ADOCK 05000423 PDR

t 2-2.

Accordingly, the license is amended by changes to the Technic.1 Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.

I amended to read as(2)llows:of Facility Operating License No. NPF-49 is hereby l

fo i

(2)

Technical Snecifications The Technical Specifications contained in Appendix A, as revised throu h Amendr9nt No.146 and the Environmental Protection Plan conta!nedinAppendixB,bothofwhichareattachedheretoare hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications and i

the Environmental Protection Plan.

3.

This license amendment is effective as of the date of its issuance, to be implemented within 60 days of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION Phillip F McKee Deputy Director for Licensing Special Projects Office Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance: August 21, 1997 I

s 4

-etc v

,r-.------s.

e y-

?.

rr

--,v-

.c m--

--e-

++-,-

-~

c.~-

--e

.w>e-m-+

-iw y-_.m

,-.+

+v er

T 811ACHMENT 10 LICENSE AMENDMENT NO. 146 FAClllTY OPERATING LICENSE NO. NPF-49 QQCKET NO. 50-423 Replace'the followin the attached pages. g ) ages of the Appendix A Technical Specifications, with 11e revised pages are identified b conta,in vertical lines indicating tl1e areas of change. y amendment number and i

Rtany1 insert 3/4 8-15 3/4 8-15 3/4 8-18 3/4 8-18 3/4 8-18a

  • overflow page - no changes made I

e E

EttcTRICAL POWER SY1TEMS D'. r, souncts AHUTDOW LIMITlho CONDIT!9N FOR OPERATION I

l 3.8.2.2 As a minimum full ' capacity chargers, one train (A or B) of batteries and their associated shall be OPERABLE:

a.

Train

'A' consisting of:

1)

Battery Bank 301A 1 and a full capacity battery charger, and 2)

Battery Bank 301A 2 and a full capacity battery charger.

i OR l

b.

Train

'B' consisting of:

1)

Battery Bank 3018 1 and a full capacity battery charger, and 2)

Battery Bank 301B.2 and a full capacity battery charger.

APPLICABillTY: MODES 5 and 6.

ACTION:

With the required train incperable, immediately suspend all operations l

j involving CORE ALTERATIONS, positive reactivity changes, movement of irradiated fuell crane operation with loads over the fuel storage pool, or t

operation with a potential for draining the. reactor vessel; initiate corrective action to restore the required train to OPERABLE status as soon as l

possible.

SURVEILLANCE REQUIRENENTS 4.8.2.2 The above required train shall be demonstrated OPERABLE in accordance with Specification 4.8.2.1.

MILL 5 TONE - UNIT 3 3/48-15 AmendmentNo.Jp,pp, 177 146 onoo

rtrefalcAL POWER SYj g g i

DNSITE POWER DISTRIBUH2N sterTDOWN LlMITING COND1110N FOR OPERATION 3.B.3.2 As a minimum, one train (A or 8) of the following electrical busses shall, be OPERABLE:

a.

Train "A" consisting of:

1 One 4160 volt AC Emergency Bus #34C, and 2

Four 480 volt AC Emergency Busses #32R, f325, #32T. f32Y, and i

3 Two 120 volt AC Vital Busses consisting of:

s)

Bus fVIAC 1 energized from Inverter flNV-1 connected to DC Bus #301A 1, and b)

Bus fVIAC 3 energized from Inverter f!NV 3 connected to DC Bus #301A 2, and 4)

Two 125 volt DC Busses consisting of:

a)

Bus #301A 1 energized from Battery Bank f301A-1, and b)

Bus #301A 2 energized from Battery Bank #301A 2.

OR b.

Train

  • B" consisting of 1

One 4160 volt AC Emergency Bus #340, and 2

Four 480 volt AC Emergency Busses f32U, #32V, #32W. #32X, and

(

3 Two 120 volt AC Vital Busses consisting of:

a)

Bus fVIAC 2 energized from Inverter flNV-2 connected to DC Dus #3018 1, and b)

Bus fylAC 4 energized from Inverter flNV-4 connected to DC Bus #3018 2, and 4)

Two 125 volt DC Busses consisting of:

1)

Bus #3018 1 energized from Battery Bank #3018-1, and b)

Bus #3018 2 energized from Battery Bank f3018 2.

APPLICABILITY: MODES 5 and 6.

EllQli:

3 With any of the above required electrical busses not energized in the required manner, immediately suspend all operatiens involving CORE ALTERATIONS, positive reactivity changes, movement of irradiated fuel, crane operation with loads over the fuel storage pool, or operations with a potential for draining in6 reactor vessel, initiate corrective action to energize the required electrical busses in the specified manner as soon as possible.

gl5 TONE-UNIT 3 3/4 8-18 Amendment No. JP, JJ, 175,146

\\

ELECTRICAL POWER SYSTEMS ON51TE POWER DISTR 180T104

$HUTDOWN SURVEILLANCE REQUIRENENTS 4.8.3.2 The specified busses shall be determined energized in the required manner at least once per 7 days by verifying correct breaker alignment and indicated voltage on the busses.

l l

NILL 5 TONE - UNIT 3 3/4 8-18a Amendment No. 146 l