March 20, 1998 X

Mr. J. E. Cross President-Generation Group Duquesne Light Company Post Office Box 4 Shippingport, PA 15077

SUBJECT:

REQUEST FOR ADDITIONAL INFORMATION RELATED TO THE RESPONSE TO GENERIC LETTER (GL) 96-06, BEAVER VALLEY POWER STATION, UNIT NOS.1 AND 2 (BVPS-1 AND BVPS-2) (TAC NOS. M96777 AND M96778)

Dear Mr. Cross:

By letter dated January 28,1997, Duquesne Light Company (DLC) resl: ended to GL 96-06,

" Assurance of Equipment Operability and Containment integrity During Design-Basis Accident Conditions," dated September 30,1996. GL 96-06 included a request for licensees to evaluate cooling water systems that serve containment air coolers to assure that these systems are not vulnerable to waterhammer and two phase flow conditions. DLC provided its assessment for BVPS-1 and BVPS -2 in its January 28,1997, letter. The NRC staff is reviewing DLC's assessment. However, we have determined that additional information is required for us to complete our review.

DLC's response indicated that BVPS-1 and BVPS-2 containment air recirculation coolers (CARCs) are not required for accident mitigation and are not called upon by the Emergency Operating Procedures (EOPs). However, during accident conditions, plant operators may elect to take actions that are not specifically called for in the EOPs if the situation calls for it.

Therefore, in order to complete our review of DLC's resolution of the waterhammer 'and two-phase flow issues, we request that DLC describe any measures that exist or that have been taken to assure that the CARCs will not be used as an option to mitigate accident conditions.

Please provide this information by June 30,1998, to enable us to complete our review of GL 96-06 in a timely manner.

Please contact me at (301) 415-1409 if you have any questions regarding this issue.

Sincerely,

/S/

Donald S. Brinkman, Senior Project Manager Project Directorate 1-2 Division of Reactor Projects - t/II Office of Nuclear Reactor Regulation cc: See next page DISTRIBUTION y'6I[

Docket File MO'Brien GHubbard ~

l}I PUBLIC OGC PEselgroth, RGN-l PDl-2 Reading ACRS JZwolinski-JTatum JStolz LMarsh

' ".O -

DBrinkman swetzel

< 22 OFFICE PDI-2/PM //A Phh 9Ql-2/D NAME DBrinkman:rb kd'Bri$b Jh DATE 3 //fl98-M/98 b/M/98

)

OFFICIAL RECORD COPY

' '/

l l

DOCUMENT NAME: BV96777.RAI g

rT; p n rm o t7I I

9003240276 900320 l

PDR ADOCK 05000334 P

PDR l

March 20, 1998 Y

~/

Mr. J. E. Cross b

President-Generation Group Duquesne Light Company Post Office Box 4 Shippingport, PA 15077

SUBJECT:

REQUEST FOR ADDITIONAL INFORMATION RELATED TO THE RESPONSE TO GENERIC LETTER (GL) 96-06, BEAVER VALLEY POWER STATION, UNIT NOS.1 AND 2 (BVPS-1 AND BVPS-2) (TAC NOS. M96777 AND M96778)

Dear Mr. Cross:

By letter dated January 28,1997, Duquesne Ught Company (DLC) responded to GL 96-06,

" Assurance of Equipment Operability and Containment Integrity During Design-Basis Accident Conditions," dated September 30,1996. GL 96-06 included a request for licensees to evaluate cooling water systems that serve containment air coolers to assure that these systems are not vulnerable to waterhammer and two-phase flow conditions. DLC provided its assessment for BVPS-1 and BVPS -2 in its January 28,1997, letter. The NRC staff is reviewing DLC's assessment. However, we have determined that additional information is required for us to complete our review.

DLC's response indicated that BVPS-1 and BVPS-2 containment air recirculation coolers (CARCs) are not required for accident mitigation and are not called upon by the Emergency Operating Procedures (EOPs). However, during accident conditions, plant operators may elect to take actions that are not specifically called for in the EOPs if the situation calls for it.

Therefore, in order to complete our review of DLC's resolution'of the waterhammer and two-phase flow issues, we request that DLC describe any measures that exist or that have been taken to assure that the CARCs will not be used as an option to mitigate accident conditions.

Please provide this information by June 30,1998, to enable us to complete our review of GL 96-06 in a timely manner.

Please contact me at (301) 4151409 if you have any questions regarding this issue.

Sincerely,

/S/

Donald S. Brinkman, Senior Project Manager Project Directorate 1-2 Division of Reactor Projects - t/II Office of Nuclear Reactor Regulation Docket Nos. 50-334/50-412 cc: See next page DISTRIBUTION Docket File MO'Brien GHubbard PUBLIC OGC PEselgroth, RGN-1 PDI-2 Reading ACRS JZwolinski JTatum JStolz LMarsh

- DBrinkman BWetzel OFFICE PDI-2/PM [ld "Pdh PQl-2/D l

_NAME DBrinkman:r$

kdBri;F JW I

DATE 3 //f/98 kh[/98

  • > /M/98 l

OFFICIAL RECORD COPY

" '/

DOCUMENT NAME: BV96777.RAI t

l j

g3 1{

J. E. Cross Beaver Valley Power Station, Units 1 & 2 Duquesne Light Company cc:

Jay E. Silberg, Esquire Bureau of Radiation Protection

' Shaw, Pittman, Potts & Trowbridge Pennsylvania Depadment of 2300 N Street, NW.

Environmental Resources Washington, DC 20037 ATTN: Michael P. Murphy Post Office Box 2063 Director-Safety and Licensing Harrisburg, PA 17120 Department (BV-A)

Duquesne Light Company Mayor of the Borrough of Beaver Valley Power Station Shippingport PO Box 4 Post Office Box 3 Shippingport, PA 15077 Shippingport, PA 15077 Commissioner Roy M. Smith Regional Administrator, Region l West Virginia Department of Labor U.S. Nuclear Regulatory Commission Building 3, Room 31g 475 Allendale Road Capitol Complex King of Prussia, PA 19406 Charleston, WVA 25305 Resident inspector Director, Utilities Department U.S. Nuclear Regulatory Commission Public Utilities Commission Post Office Box 298 180 East Broad Street -

Shippingport, PA 15077 i

Columbus, OH 43266-0573 I

Director, Pennsylvanie Emergency Duquesne Light Company Management Agency Beaver Valley Power Station Post Office Box 3321 PO Box 4 Harrisburg, PA 17105-1321 Shippingport, PA 15077 ATTN: S. C. Jain, Vice President Ohio EPA-DERR Nuclear Services (BV-A)

ATTN: Zack A. Clayton Post Office Box 104g Columbus, OH 43266-014g Dr. Jud'th Johnsrud National Energy Committee Sierra Club 433 Orlando Avenue State College, PA 16803 Duquesne Light Company Beaver Valley Power Station PO Box 4 Shippingport, PA 15077 ATTN: R. L. Grand, Division Vice President, Nuclear Operations Group and Plant Manager (BV-SOSB-7)