.A C. K. McCcy Southern Nuclear Vice President Op*; rating Coenp=y,lic.
Vogtte Project 40 Inverness Center Parkway R0. Box 1295 Birmingharn Alabarna 35201 Tel 205.992.7122 i
Fax 205 992.0403 l
k SOUTHERN h COMPANY Energy ro Serve YourWorld*
April 16, 1998 LCV-1102-B Docket Nos.
50-424 50-425 TAC-MA0194 MA0195 U. S. Nuclear Regulatory Commission ATTN: Docurnent Control Desk Washington, D. C. 20555 Ladies and Gentlemen:
VOGTLE ELECTRIC GENERATING PLANT REQUEST TO REVISE TECHNICAL SPECIFICATIONS REACTOR TRIP SYSTEM AND ENGINEERED SAFET'.' FEATURE ACTUATION SYSTEM INSTRUMENTATION TRIP SETPOINTS By letter dated November 20,1997, (LCV-Il02) Southern Nuclear Operating Company (SNC) proposed to revise the Vogtle Electric Generating Plant (VEGP) Unit I and Unit 2 Technical Specifications (TS) Limiting Condition for Operation (LCO) 3.3.1, Reactor Trip System (RTS) Instrumentation, and LCO 3.3.2, Engineered Safety Feature Actuation System (ESFAS) Instrumentation. The proposed changes were to facilitate treatment of the trip setpoints as nominal values and correct certain typographical errors.
On January 28,1998, SNC met with the NRC staff to discuss the proposed amendment. As a result of that meeting, SNC has revised the proposed amendment to address concerns expressed by the NRC staff. The changes are as follows:
LCV-1102 proposed new footnotes "n" and "i" for Tables 3.3.1-1 and 3.3.2-1, respectively. The footnotes as proposed by LCV-1102 read as follows:
"The Trip Setpoints may be set more conservative than the Nominal value as necessary in res onse to plant conditions."