(j M.tl.LSTONE NUCLEAlt l'OWElt STATION ff SURVEILIANCE l'ROCEDURE U-TEK-TOR Fire Detection System Checks SP 786.1 Rev. 9 s ,

.v,h .__ - ,

SToe sixx Act . ~1eview .

, ~

Approval: ) Q g

PORC Mtg. No: \ - 9 7 - \ ?6 Date: cu a-9 7 Effective Date: 9 '( -9 7 9709150034 970903

(.

~

PDR ADOCK 05000245 \'

t g

F PDR [A 'n

%/

Level of Use SME: M. Dunn General l

9 Millstone Unit 1

[sv c SurvelHance Procedure

~ U-TEK-TOR Fire Detection System Checks TABLE OF CONTENTS

1. PURPOSE....................................................2
2. P R E R EQ UI S ITES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3. P R E CAUTI O N S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4. I N ST R UCTI O NS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 4.1 S t a tion Bat t ery Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 4.2 G as 'Ib rbine Building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5. REVIEW AND SIG N - OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6. R E F E R E N C ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7. S U M M A RY O F Cl l ANG ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 p . ATI'ACllMENTS AND FORMS

' t.

v Maint. Form 786.1-1,"U-TEK-TOR Fire Detection System Checks-Station Battery Room" Maint. Form 786.1-2, "U-TEK-TOR Fire Detection System Checks-Gas

'Ihrbine Building" r

o l f^

ig l

SP 7861 Level of Use - . .. . .

[, STOP' THINK .'ACT REVIEW. Rev.9 General l of 12

J

' ~

-s 1. PURPOSE

(" ) '

1.1 Oldeclive This procedure provides instructions for ensuring the OPERAHILITY of the U-TEK-TOR Fire Detection System used in the Station Battery Rooms and in the Gas 1brbine Building.

This procedure satisfies Technical Requirements Manual, OPS Form 273-7.2, Fire Protection 1bchnical Requirements Section 4.1.El .. d 2 for the Station Hattery Rooms. The Gas 1brbine Building U-TEK-TOR fire detection system is not covered by the 1bchnical Requirements Manual or Technical Specifications.

1.2 Discussion The U-TEK-TOR system is a closed circuit detection system. The system consists of normally closed circuits that produce an alarm situation should one of the circuits open. The two normally closed circuits comprise a zone alarm pair. One circuit of the pair is of cutectic wire and causes an open circuit in the event of excessive heat. The other circuit is of ordinary wire and is the supervisory circuit, o Through the use of test switches on the U-TEK-TOR panels, test U signals are input to the alarm logic circuitry to simulate trouble and fire alarm conditions. OPERAlllLITY of the fire detection system is confirmed via alarms and lights on the local panel and annunciation lights on the Control Room panel.

The U-TEK-TOR cabinet for the Station Battery Room is located on the outside wall near the entrance to the Station Battery Rooms. The Gas 1btbine Building U-TEK-TOR cabinet is located on the outside of the west wall of the building near the htdiding entrance. All switches and lamps are on inside panel unless otherwise noted.

1.3 Applicability This procedure applies to the following U-TEK-TOR systems:

  • U-TEK-TOR,"U-TEK-TOR Fire Detection System"
  • FIRE-AIARM-2," Station Hattery Room Fire Nant"
  • FIRE-A1 ARM -4," Gas Tbrbine Building Fire Alarm" m

(

SP 786.1 Levelof Use STOP THINK ACT REVIEW Rev.9 Genera -

2 of 12 L_

ll - - -

'I

~

1.4 Frequency Monthly

2. ERERED1).lS11ES 2.1 General 2.1.1 An AWO has been issued and approved by Unit 1 Operations Department and Performance livaluations (Pli) Department as necessary.

2.1.2 The following appropriate suncillance cover sheet has been signed and surveillance has been approved:

  • Maint. Form 786.1 -1, for Station llattery lloom

. Maint. Form 786.1-2, for Gas Thrbine lluilding 2.1.3 Operations Department has been notified that the U-TliK-TOlt fire detection system test will be performed.

2.2 'Ibols

  • Screwdriver 2.3 ltesponsibilities 2.3.1 Unit 1 Operations Department is responsible for acknowledging Control lloom annunciators.
3. l'BECAUTIONS 3.1 N/A l I) sp 786.1 Levelof Use sToe- Tuing Act neview nev. 9 General ,

3 of 12

- _ . . _ _ - . _ _ _ _ _ . _ _ _ _ _ . _ _ _ _ _ . . _ . . ~ . _ _ _ . _ _ _ _ _ _ . -

. 4. INSTRUCTIONS j 4.1 Station flattery Room 4.1.1 OPEN U-TEK-TOR cabinet located outside the 1813 battery l roorn entrance,

, j

! l NOTE

1. System check may be completed before reporting deficiencies to SM or US.
2. Dual verification is required for steps 4.1.3 through 4.1.17.

4.1.2 REQUEST dual verification for performing steps 4.1.3 through 4.1.17.

NOTE The Station llattery Room U-TEK-TOR cabinet breaker is located on the 34' 6" elevation of the 'Ibrtiine lluilding on the north wall near bus 14C.

O 4.1.3 ENSURE the following breakers are closed:

  • UP-lli circuit number 6 (110-volt " Normal" power supply)
  • UP-lll circuit number 4 (110-volt " Normal / Emergency" power supply) 4.1.4 ENSURE all switches are in " NORMAL" (up) position.

4.1.5 ENSURE the following are indicating correctly on outside panel of U-TEK-TOR box:

  • Green " NORMAL POWER" lamp is lit.
  • All other lamps are not lit.  !
  • All alarms are not actuated.

C Level of Use SP 786.1 ST P THINK ACT ', REVIEW Rev.9 General

- 4 of 12

")

'i

(, WARNING STOP STOP

._/ \

'Ib prevent injury from arcing and s 3arking, power must not be shut off by removing the power fuse in U-TE <-TOR box.

4.1.6 OPEN breaker UP-111, circuit number 6, and DEENERGlZE the unit.

NOTE Power failure alarm is an oscillating beep.

4.1.7 Refer 'Ib Figure - 1, and ENSURE the following occurs on outside pancl:

Figure - 1. Station llattery Room U-TEK-TOR Panel "4

POWER QN f ALLURE DEEPs uNT TROUBLE FIRE SILENCE TROUBLE N*^'

BUZZEn O G

\ /

O BATTERY ROOM 1 0 $" ~'

TROUBLE NNAL O BATTERY ROOM 1 A O cincuiT o

"' TESTS STATION NO 2 FIRE ALARM "

c'a "

O BuzzeROrP ><>1 O

ALARM HELAY

^ ^

EMERGENCY-+ PO Q

NO AL MAIN EMERGENCY POWER POWER Outside Panel O O pggg3 Inside Panel
  • Green " NORM AL POWER" lamp is not lit.
  • Amber " EMERGENCY POWER" lamp is lit.
  • Power failure beep is actuated, g

SP 786.1 Level of Use ST P THINK ACT ,REVIEW Rev.9 General 5 of 12

l i

l 4.1.8 SET " SILENCE POWER FAILURE BEEP" switch to

" SILENT" and ENSURE the following occurs:

  • Power failure beep is silenced
  • Amber " BUZZER OFF" lamp on outside panel is lit.

4.1.9 CLOSE breaker UP-lll, circuit number 6 and RESTORE normal power io unit.

l 4.1.10 SET " SILENCE POWER FAILURE BEEP" switch to  :

" NORMAL" m

4.1.11 SET " TESTS TROUBLE CIRCUlT" switch to " TEST" and ENSURE the following occurs:

  • Amber "TROUllLE BA1TERY ROOM 1" lamp on outside panel is lit.

4

  • Amber " TROUBLE 13A1TERY ROOM 1 A" lamp on outside

. panel is lit.

  • llouble buzzer is actuated.

, 4.1.12 SET "SlLENCE TROUBLE IlUZZER" switch to " SILENCE" and ENSURE the following occurs:

  • ' Rouble buzzer is silenced.
  • Amber " BUZZER OFF" lamp on outside panel is lit.

. 4.1.13 SET " TESTS TROUBLE CIRCUIT" switch to " NORMAL"

- 4.1.14 SET " SILENCE TROUBLE BUZZER" switch to " NORMAL."

4.1.15 NOTIFY Control Room to expect "BA1TERY ROOM FIRE ALARM PNL #2" annunciator actuation on CRP 903 A-3 (8-7) during next portion of test.

O Level of Use SP 786.1 ST Pl THINK ACT ' REVIEW - Rev.9 Genew 6 of 12

_. ._ = _ _

N -W v'-"' ' ' "-" rv

. i 4.1.16 SET " TESTS FIRE ALARM" switch to " TEST" and ENSURE  ;

O -

'" reiie*i"a ecc#< : 1

  • Red " FIRE HA'ITERY ROOM 1" lamp on outside panel is lit.
  • Red " FIRE HA'ITERY ROOM 1 A" lamp on outside panelis lit.
  • Fire bell actuates.
  • Red " ALARM RELAY ACTUATED" lamp on inside panel t

> - is lit.

4.1.17 SET" TESTS FIRE ALARM" switch to " NORMAL."

4.1.18 ENSURE that Control Room "DA'lTERY ROOM FIRE ALARM PNL #2" annunciation was received on CRP 903 A-3 (8-7).

i 4.1.19 IE detector fails to operate as specified, immediately NOTIFY Control Room and CONSULT FLS.

4.1.20 NOTIFY Control Room that testing is completed.

4.1.21 DOCUMENT the following on Maint. Form 786.1-1: l

  • Local panel is OPERABLE as indicated by acceptance criteria set forth in this procedure,

, acceptance criteria set forth in this procedure.

4.1.22 COMPLETE Maint. Form 786.1-1 cover sheet as applicable.

4.2 Gas 'Ihrhine Hullding

. 4.2.1 OPEN U-TEK-TOR cabinet.

t 1

SP 786.1

- Levelof Use ST P THINK ~ ACT ,REV EW Rev.9 General 7 of 12

.,-..,-., 4wm,, m., 7p,,,_ _.-.y ..,,..,,,,,..s_ ,,,,.,,,.,,g., , . _ _ _ , , , _ _ _ _ , . , _ , . _ , . _ . ,

p v

. NOTE

1. System check may be completed before reporting deficiencies to SM or US.
2. Dual verification is required for steps 4.2.3 through 4.2.17.

4.2.2 REQUEST dual verification for performing steps 4.2.3 through 4.2.17.

NOTE i The Gas Wibine lluilding U-TEK-TOR cabinet breaker is located I inside the Gas'Ibrbine llullding on the west wall in panel LP-7 near the i building entrance.

4.2.3 ENSURE the following breakers are closed:

. LP-7 circuit number 2 (110-volt " Normal" power supply

. LP-7 circuit number 12 (110-volt " Normal / Emergency" power supply)

( v 4.2.4 ENSURE all switches are in " NORMAL!' (up) position.

4.2.5 ENSURE the following are indicating correctly on outside panel

  • of U-TEK-TOR cabinet:

I

. Green " POWER NORMAL" lamp is lit, j

. All other lamps are not lit.

  • All alarms are not actuated.

STOP WARN 1NG STOP

% prevent injury from arcina and s 3arking, power must not be shut off by removing the power fuse in 0-TEX-TOR cabinet.

4.2.6 OPEN breaker LP-7, circuit number 2, and DEENERGlZE the unit, b

SP 786.1 Levelof Use Gened ST P '"'ux Ar .

naview Rev.9

- 8 of l2 l

l

)

l 1

OV NOTE Power failure alarm is a buzzer.

1 4.2.7 Refer % Figure - 2, and ENSURE the following occurs on outside pancl:

Figure - 2. Gas %rbine Hullding U-TEK-TOR Panels TROUBLE FIRE POWER Q eug FA! LURE BUZZ mm O exciter O sitenesinouetE~r~~

BUZZER Q O SWITCH GEAR O - - - - m- -

TROUBLE WM4 0 - AUX. EQUIPMENT-O c'acu't O O GENERATOR - O y, rests FIRE ALARM 0, c'acu'1 O -CONTROLCABINET-O O auzzenOrF STAtl0N NO 4 AMR REMY ACTUATED ENCY- O o t ht uA,N EutnoENcy POWER POWER o

O Outside Panel FUSES inside Panel

  • Green " POWER NORM AU' lamp is not lit.
  • Amber " POWER EMERGENCY" lamp is lit.
  • Power failure alarm is actuated.

4.2.8 SET " SILENCE POWER FAILURE HUZZ" switch to

" SILENT" and ENSURE the following occurs:

  • Power failure alarm is silenced.
  • Amber "HUZZER OFF" lamp on outside panel is lit.

4.2.9 CLOSE breaker LP-7 circuit number 2, and RESTORE normal power to unit.

4,2.10 SET" SILENCE POWER FAILURE BUZZ" switch to "NO R M AL."

O O SP 786.1 Level Of Use STOP1 THINK ACT REVIEW Rev.9 General ,

9 of 12 yer , , .-.__,. 7,,-o , _ _ ,- , , . , , - , , , ,,yrep_%mw y..,.. _q.3 .,w___,._w% . _ . ,._,,,%_,_9.,___..%,,,__.,,,,,,_,_,,_,,,,,9 ,._,+,,._,,,,,.p ,,. ,;...r.,g,g,,9,,,,__, ,_

4.2.11 SET " TESTS TROUBLE CIRCUlT" switch to " TEST" and 1 ENSURE the following occurs: l

  • Amber " TROUBLE" lamps for all five zones are lit on i outside panel.  !
  • Double buzzer is actuated.  ;

4.2.12 SET " SILENCE TROUBLE HUZZER" switch to " SILENT" and ENSURE the following occurs:

  • Double buzzer is silenced.
  • Amber "HUZZER OFF" lamp on outside panel is lit.

4.2.13 SET " TESTS TROUBLE CIRCUIT" switch to " NORMAL" 4.2.14 SET " SILENCE TROUBLE BUZZER" switch to " NORMAL" 4.2.15 NOTIFY Control Room to expect " GAS TURH FIRE ALARM

- PANEL NO 4" annunciator actuation on CRP 903 A-3 (7-7) during next portion of test.

p 4.2.16 SET " TESTS FIRE ALARM CIRCUlT" switch to " TEST" and V ENSURE the following occur =:

  • Red " FIRE" lamps for all five zones are lit on outside panel.
  • " FIRE" bell is actuated.
  • Red " ALARM RELAY ACTUATED" lamp is lit on inside panel.

4.2.17 SET" TESTS FIRE ALARM CIRCUlT" switch to " NORMAL" 4.2,18 ENSURE that Control Room "OAS TURH FIRE ALARM PANEL NO 4" annunciation was received on CRP 903 A-3 (7-7).

~

4.2.19 IE detector fails to operate as specified, immediately NOTIFY Control Room and CONSULT FLS.

4.2.20 NO7 U Y Control Room that testing is completed.

C Level of Use- .

SP 786.1 ST P THINK E - ACT - REVIEW Rev.9 GeneM:

10 of 12

-. --, ,-w--w~.,,-,--r---,_,;.-------,.e------yr,r--.---,.-y-.--r- ,, ,- m ,.-.-r,.r, - - , ,y-e.+,me w 4 e -- y. s ryie , c. w,----,-r -

,c s 4.2.21 DOCUMENT the following on Maint. Form 786.1-2: l t

s

) .

  • Local panel is OPERA 13LE as indicated by acceptance criteria set forth in this procedure.
  • Control Room annunciator is OPERABLE as indicated by l acceptance criteria set forth in this procedure.

4.2.22 COMPLETE Maint. Form 786.1 -2 cover sheet as required.

(v )

( )

Q/ '

SP 786.1 Level of Use ST P THINK ACT REVIEW Rev.9 General 11 of 12

5. EEVIEW AND SIGN-OFF 5.1 The review and sign-off of this procedure is satisfied by the review and sign-off of the AWO and applicable Maint. Form (s).
6. REFERENCES 6.1 lbchnical Requirements Manual, OPS Form 273-7.2, Fire Protection 1bchnical Requirements, Section 4.1.F.1 and 2 6.2 25202-448-001 A,"U-TEK-TOR Fire Alarm System" 6.2 25202-31001, Sheet 1131," Annunciator 903-A3" l
7.

SUMMARY

OF CllANGES -

7.1 Added appropriate Control Room annunciators to steps 4.1.15,4.1.18, 4.2.15, and 4.2.18.

7.2 Added Technical Requirements Manual to References Section.

)

7.3 Modified Maint. Forms 786.1-1 and 786.1-2 to climinate need for electrician to independently verify control room annunciations.

b 7.4 Added step reference to sign-off fields of Maintenance Forms.

! 7.5 Deleted requirement that an electrician perform independent verification of annunciators and alarms.

t 4

7.6 Changed SCO references to SM.

7.7 Added steps to perform dual verification of local panel indications.

f 4 .

C Level of Use - - . . .

SP 786.1

_ ggggg . -STOP --THINK ACT- REVIEW Rev.9 1 12 0f 12 yye'y.-g.- 9nm,enw,e-m =--m.- y 4 a, -wwggy w su-ug.,.,y p g-y,-- -

y-ir-,,*% -y -- .gr.--v.., r.q 9g~n+ w -+,ory.-yaqw-,g-..y.- er

_.._ _ _._ .______.____..._._m_____ - .

Form Approv;l I i

, Apppval[ [] Approval Date Ettective Date PoRc Meeting No 42 &A't? 9-4-97 l CO - m3  :

O -

v  :

U-TEK-TOR Fire Detection System Checks-Station Battery Room r f- l

, oenerie Information I i Reference Procedure Applicable Tech, Spec. or Technical Requirements Manual Frequency SP 786.1 Technical Requirements Manual Monthly f OPS Form 273-7.2, Section 4.1.F.1 & .2 This form is being used for the following:

T chnical Requirements Manual O Tech spec survei"ance O system ^iionment @ otner:

Q Maintenance (Retest)

Rostoration Q Non-Tech Surveillance (PM)

Spec Specific Information Scheduled Date Applicable Mode AWo Test Authortred Dy(SM/US) Date Prerequisites Completed Dy (initials /Date) Precautions Noted Dy (initials /Date)

Surveillance Completed By Date O Acceptance Criteria Met? O ves O NO Accepted Dy (Department FLS) Date Approved By (Department Head / Designee) Date Shift Manager Notified of Failed Survoillance Date f

Acceptance Criterla Technical Roquirements Manual acceptanco critoria is considered mot when all of the following conditions occur:

1. Station Battery Room firo detection instrument is demonstrated OPERABLE at the local panol.
2. Control Room annunciation is demonstrated OPERABLE.

Test Equipment Equipment Type .ldentification/OA Nurabat Calibration Due Date None Required O

. Maint Form 786.1-1

  • Rev.7 Page 1 of 2

. _ _ . , _ _ _ . . . _ _ ~ _ _ - . _ . _ _ _ - . _ . . _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _

' U-TEK-TOR Fire Detection System Checks-Siction llattery Room l Data and comments CONTROL ROOM AREA LOCAL PANEL OPERABILITY ANNUNCIATION OPERABILITY PROTECTED ZONE (Step 4.1.21) (Step 4.1.21)

Acceptance Criteria Satisfied Acceptance Criteria Satisfied O YES O NO O YES O NO Station Perfornied Ily Perforrned 13y ,

llattery Rooms 1/2 Date Date (18A and 1811)

Verified Ily Date Conunents O

O Maint Form 786.1-1 Rev.7 Page 2 of 2

._.. -~ _ _- - - - _ _ . - _ _ - _ - . . - _.

Form Approv:1 At . va h v} og aj g.

v. l ) Approval Date Litective Date Foke Meetng No.

m 9 'M~l H-4. M \on- M Q V '

U-TEK-TOR Fire Detection System Checks-Gas 'Ihrbine llullding rr!

Generic Information l -

neforence Procedure Apphcable Tech spec. or Technical Requkements Manual Frequency

. SP 786.1 N/A Monthly 4 ,

. This form la being used for the following: '

O Tech spoo surveitiance O s etem^iionment v O Other:

O Maintenance Rostoration @ Non-Tech Spec (Retest) Surveillance (PM)

Specific Information Scheduled Date Apphcable Mode AWO Test Authortred Dy (SM/US)

) Date Prerequisites Completed Dy (initials /Date) Precautions Noted By (Initials /Date)

Surveillance completed By Date O Acceptance Criteria Met? O ves O NO Accepted Dy (Department FLS) Date Approved Dy (Department Head, Designee) Date Shift Manager Nottf.ed of railed Surveillance Date Acceptance Criteria Acceptance critoria is considered mot when allof the following conditions occur

1. Gas Turbino Building fire dotection instrumont is demonstrated OPERABLE at local panel.
2. Control Room annunciation is demonstrated OPERABLE.

Test Equipment i EQUJpment Typa identification /OA Number Calibration Due Date None Required O

Maint Forit 786.1-2

' Rev.3 Page 1 of 2

~ . .

'U-TEK-TOR Fire Detection System Checks-Gas Thrbine llullding l Data and comments CONTROL ROOM AREA LOCAL PANEL OPERABILITY ANNUNCIATION OPERABILITY PROTECTED ZONE (Step 4.2.21) (Step 4.2.21)

Acceptance Qiteria Satisfied Acceptance Criteria Satisfied O YES O NO D YES O NO Performed By Performed By II I3 Gas 'ilabine Date Date lluilding 4/5 Verified Ily Date Comments 4

O 4

a O

Maint Form 786.1-2 Rev.3 Page 2 of 2.

o . . 3N'(s}.wcf,y t

  • NDS Document Transmittal #05044 9/4/97 Addressee Unque8140 To: Nuclear Regulatory Commission ROUTINE distributen Document Control Desk Washington, D.C. 20555 The following documents have been revised. You are currently on distribution for these documents. Verify that all documents are included in this distribution set.