Rev 4,Change 1 to Sp 779.1, Gas Turbine Fire Protection Sys Surveillance
ML20216D220
Person / Time
Site: Millstone  
Issue date: 08/29/1997
From: Mcnerney T
NORTHEAST NUCLEAR ENERGY CO.
To:
References
SP-779.1, NUDOCS 9709090252
Download: ML20216D220 (4)


Text

4 Procedure and Form Change Request A

(Sheet I of t) 0' Section 1: Change Initiation Information Document No.: SP 779.1 4

Change No.. 1 Revision No.

Title:

gas Turbine Fire Protection System Surveillance Initiated Ily: T. McNerney Change T pe: Intentb Non intent 3

tn d acceptance criteria to indicate that the surveillance is not 2

i run rc n n

unsatisfactory if the cylinder or flexible discharge loop hydrostatic

. Expiration Date or Condition:

test expiration date will elapse within the next six months. Added s

instruction to initiate a TR to hydrostatically test cylinder or flexible

- Removed Date:

discharge loop before expiration date.

Section 2: Instructions for Entering Change Replace pages 6 and 7.

Section 3: Non-Intent Change Interim Approval Section 3a. Approved by SORc or PORC Member or First Line Supervisor Signature:

IG /A, Date:

interim Approval Section 3b. Approved by Shift Manager or SRO Licensed on Unit Signature:

K. /\\k Date:

Section 4: Reviews QA Reviewer Signature:(irrequired)

Date:

Independent Reviewer Signature:

[M [mg 7 f[py/07 Date:

. _ _ _ _ _ _.- - _ _. __ _ - _,_'from DC 3 not refi /f Gr= Attachment 10 t

No comments

~

4 Safety Es aluation Required?

YES NO Ifeither question is ansu cred ")ES "

+ Ens ironmental Reg iew Required?

YES NO Section 5: Review and Approval runtordont YES (

NOR ltes iew Required?

LI Department llead or Responsible Individual Signature:

,Y,, g,~)

Date:

p'/py/f'7 (Common Department Procedures require Date:

cach affected Department llead's signatures)

Date:

Ee tion 6: APPROVAL M eetm.g N. umber: \\ cn _ t%

PORCirSORC f] -

. trperson Signature: \\'

i Approval Date: g,- Q A - M Effective Date:

DC1. Att. 6, Rev. 5 (06-03-97) 8" M -O Staten Admin Procedures Group OSCAR Report O

9709090252 970829 PDR ADOCK 05000245 l

P PDR

i 4.2 CO CylinderInspection 2

l 4.2.1 CALCULATE cylinder CO weights as follows:

2 EXAMINE cylinder and RECORD the following data on a.

Maint. Form 779.1-1:

Cylinder serial number Last cylinder hydrostatic test date l

Cylinder stamped empty weight b.

Using CO bottle weight rig, lifting bracket, and 2

dynamometer, WEIGH each cylinder.

1

~

c.

RECORD cylinder actual weights on Maint. Form 779.1-L NOTE To calculate the CO weight, the stamped empty weight of the cylinder 2

must be subtracted from the actual weight of the cylinder.

C d.

Refer To date stamped on cylinder, and SUBTRACT stamped empty weight from actual weight and RECORD CO weight on Maint. Form 779.1-1.

3 2

I' 4.2.2 E any CO cylinder contains 67.5 lbs or less CO, PERFORM 2

2 L

the following:

a.

REPLACE CO cylinder.

2 b.

Refer To step 4.2.1, and CALCULATE replacement cylinder CO weight, 2

c.

NOTIFY Control Room and FLS that a CO cylinder was 2

replaced because it contained 67.5 lbs or less CO.

2 4.2.3-Refer To date stamped on cylinder, and E any CO cylinder has a 2

hydrostatic test date that is greater than 12 years old $1 : "1 gic v d7 : !: 3:; t c' ! hef : $c ne:.t h.nenSs, f

hydrostatically TEST. REPLtCE that cylinder, r

D

.A,

[

SP 779.1 Level of Use

, - -STOP'

'THINK'

.-ACF..

BEVIEW Rev. 4 General 6 of 11 u

. - - - - ~.-

J i

1

+..,

4.2.4 Refer 1b metal tag on flexible discharge loops, and RECORD last.

. flexible discharge loop hydrostatic test date on Maint. Form -

'779.1-1.

e i

4.2.5 Eany flexible discharge loop has a hydrostatic test date that is greater than 5 years old Dil : !he 5:. ':: "". E yer :?d ?:fece j

the :: ext i :ne"ths, hydrostatically TEST REPL \\CE that flexible f discharge loop.

4,2.6 SECURE CO cylinders in position, but do not connect discharge 2

heads, i"

4.2.7 E any CO cylinder or flexible discharge loop has a hydrostatic 2

test date that will expire within ew+ 12 rnonths, NOTIFY FLS, and INITIATE a TR to hydrostatically test applicable component i.

L before expiration date.

4.2.8 Visually INSPECT all 0-rings for wear, defects, and damage, i

{

4.2.9.

E necessary, REPLACE O-rings.

p a

4.3 System Inspection -

p 4.3.1 Visually INSPECT fire protection system equipment for 4 V disassembled, disconnected, or missing components.

4.3.2 RECORD inspection results onto Maint. Form 779.1-1.

i 4

E 4

4 i

l ' hi SP 779.1 Level of Use

-, REVIEW Rev.4 STOP"

. THINK' ACT General-70f11

,---n

._.4.e.

  • NDS Document Transmittal #04266 8/29/97 To: