ML20215N795

From kanterella
Jump to navigation Jump to search
Informs of Completion of Seismic Qualification of Westinghouse 7300 Process Protection Sys Circuit Cards.Mods Made to Ntd Circuit Cards Used in NSSS & balance-of-plant Applications
ML20215N795
Person / Time
Site: Byron 
Issue date: 10/24/1986
From: Ainger K
COMMONWEALTH EDISON CO.
To: Harold Denton
Office of Nuclear Reactor Regulation
References
2316K, NUDOCS 8611070281
Download: ML20215N795 (1)


Text

..

m N Commonwealth Edison l.

72 West Adams Street, Chicago, Illinois

\\

Kidress Reply to: Post Office Box 76T l

Y Chicago, lilinois 60690 0767 October 24, 1986 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, DC 20555

Subject:

Byron Station Unit 2 Seismic Qualification NRC Docket No. 50-455

Dear Mr. Denton:

This is to inform you of the completion of seismic qualification of Westinghouse '7300 Process Protection System circuit cards for Byron Unit 2.

-Modificationn have been made to the NTC circuit cards used in NSSS and BOP applications and the NTD circuit cards used in BOP applications.

Calibration adjustments have been made to resolve anamolies observed during seismic testing of the NPC, NCH and-NSC cards used in NSSS application 3.

The NCH card used in BOP applications did not require any adjustments and is seismically qualified. Installation of seismically qualified Westinghou.~e

~1300 Process Protection System circuit cards in Byron Unit 2 is complete.

Please direct'any questions regarding this matter to this office.

One signed original and fifteen copies of this letter are provided for NRC review.

Very truly yours, l,

K. A. Ainger Nuclear Licensing Administrator Im

)

cc: Byron Resident Inspector go7 g0 p

A

.