Text
..
o nro UNITED STATES
[4 NUCLEAR REGULATORY COMMISSION 5
l WASHINGTON, D. C. 20555
\\...../
CONSUMERS P0k'ER COMPANY PALISADES PLANT DOCKET NO. 50-255 AMENDMENT TO PROVISIONAL OPERATING LICENSE Amendment No. 98 License No. DPR-20 1.
The Nuclear Regulatory Comission (the Comission) has found that:
A.
The application for amendment by Consumers Power Ccmpany (the licensee)datedJune 20, 1986, complies with the standsrds and requirements ~of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public; and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.
The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
I 1
l l
8610300044 861015 DR ADOCK 05000255 PDR
O.
2.
Accordingly, Provisional Operating License No. DPR-20 is amended by changing the Technical Specifications as indicated in the attachment to this license amendment and by revising Paragraphs 2.C. and 3.B.
to read as follows:
[2]C.
Pursuant to the Act and 10 CFR Part 30, " Rules of General Applicability of Licensing of Byproduct Material", to receive, possess and use in connection with operation of the facility 1500 curies of Polonium-210 as two sealed sources not to exceed 750 curies each, 1000 curies of Cesium-137 as multiple sealed calibration sources and up to 500 millicuries per nuclide of any byproduct material with Atomic Numbers 3 to 83, inclusive, without restriction to chemical and physical form to a total of 10 curies; and
[3]B. Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 98, are hereby incorporated in the license.
The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of the date of its issuance.
FOR THE NUCLEAR REGULATORY COMMISSION fl/ W '
Ashok. Thadani, Director PWR P.. ject Directorate #8 Division of PWR Licensing-B
Attachment:
Changes to the Technical Specifications Date of Issuance: October 15, 1986
ATTACHMENT TO LICENSE AMENDMENT N0. 98 PROVISIONAL OPERATING LICENSE NO. DPR-20 DOCKET N0. 50-255 Revise Appendix A Technical Specifications by removing the pages identified below and inserting the enclosed pages. The revised pages are identified by amendment number ar.d contain marginal lines indicating the area of change.
REMOVE INSERT 3-81b 3-81b 6-37 h
l l
l i
l l
.. T ~~^^
Table 3.17.4(Cont'd)
(g) Calculate the Quadrant Power Tilt using the excore readings at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> when the excore detectors deviation alams are inoperable.
l (h) With two flow rate indicators inoperable for a given control valve, the control valve shall be considered inoperable and the requirements of 3.5.2(e) apply.
i l
l 3-81b Amendinent No. 96,98
l ADMINISTRATIVE CONTROLS 6.21 SEALED SOURCE CONTAMINATION 6.21.1 Each sealed source containing radioactive material either in excess of 100 microcuries of beta and/or gamma emitting material or 5 microcuries of alpha emitting material shall be free of greater than or equal to 0.005 microcuries of remo/able contamination.
6.21.2 With a sealed source having removable contamination in excess of 0.005 microcuries, immediately withdraw the sealed source from use and either:
1.
Decontaminate and repair the sealed source, or 2.
Dispose of the sealed source in accordance with applicable regulations.
6.21.3 Each category of sealed sources as described in 6.21.1 with a half-life greater than 30 days (excluding Hydrogen-3), and in any other form than gas, shall be tested for leakage and/or contamina-tion at intervals not to exceed 6 months.
6.21.4 The test shall be perfomed by the licensee or by other persons specifically authorized by the Comission or an Agreemer.t State.
The test method shall have a detection sensitivity of at least 0.005 microcuries per test sample.
6.21.5 The test sample shall be taken from the sealed source or, in the case of pemanently mounted sources, from the surfaces of the mounting device on which contamination would be expected to accumulate.
6.21.6 The periodic leak test does not apply to sealed sources that are stored and not being used. These sources shall be tested prior to use or transfer to another licensee, unless tested within the previous 6 months. Sealed sources which are continuously enclosed within a shielded mechanism (i.e., sealed sources within radiation monitoring or boron measuring devices) are considered to be stored and need not be tested unless they are removed from the shielded mechanism.
6.21.7 Sealed sources transferred without a certificate indicating the last test date shall be tested prior to being placed in use.
6.21.8 A report shall be prepared and submitted to the Comission on an annual basis if sealed source leakage tests reveal the presence of greater than or equal to 0.005 microcuries of removable contamination.
6-37 Amendment No. 98
,