_

lEtucraic Umon 1901 Gratiot Street, St. Louis Donald F. SchneII Vice President June 18, 1987 U.S. Nuclear Regulatory Commission ATTN:

Document Control Desk Washington, D.C.

20555 Gentlemen:

ULNRC-1535 DOCKET NUMBER 50-483 CALLAWAY PLANT APPLICATION FOR EELOAD LICENSE AMENDMENT USING WESTINGHOUSE VANTAGE 5 FUEL ASSEMBLIES

References:

1) ULNRC-1470 dated March 31, 1987
2) ULNRC-1491 dated April 15, 1987 j
3) ULNRC-1525 dated June 5, 1987 i

References 1 through 3 transmitted the license application and additional supporting information for Callaway Cycle 3, in which a transition to Westinghouse VANTAGE 5 fuel will begin.

Transmitted herewith are marked-up copies of Callaway Technical Specification pages 2-7 and 2-9, noting a revision to the definition of AT and page B2-5, noting corresponding revision to the Bases.

An a8ditional quarterly recalibration' check has been added to Table 4.3-1.

The proposed revision requires the use of as-measured loop-specific vessel AT values at 100% rated thermal power.

This will result in the two protection functions representing the actual plant equivalents to the transient analysis assumptions.

The

]

revised wording reflect the generic wording of NUREG-0452, j

Revision 4.

The results of the Safety Evaluation transmitted by l

Reference 1 remain unchanged in that this change would not j

adversely affect or endanger the health of the general public and j

does not involve an unreviewed safety question.

i 1

l

\\

8706250533 87061B h0 0

PDR ADOCK 05000483 P

PDR 1

Maihng Address: P 0. Box 149. St. Louis, MO 63166

i e

  • . The results of the Significant Hazards Evaluation transmitted by Reference 1 remain unchanged as a result of this revision.

If there are any questions with respect to this subject, please contact us.

Very truly yours,

<\\

w

~

k Donald _F Schnell DS/ tar - Marked-up Technical Specification Pages 1

e',.,

.,4..-

. 1:.=,

g-L

STATE OF/ MISSOURI l-)

)

SS

' CITY;OF ST.. LOUIS )

w a

Robert J.

Schukai, of lawful. age, being'first duly. sworn-j upon'oathisays:that'he is General Manager-Engineering'(Nuclear)'for'

. Union! Electric LCompany; that he has ' read the foregoing.. document-and _

1

knows the content thereof; that' he has executed the.same for and on

' behalf of said company with' full power.and authority.to do so;.and..

that the. f acts ' therein -stated are true and correct' to the: best of his,

' knowledge, information and belief.-

j

l. b s.

\\'

.By

)

Rober chukai

-Genera nager-Engineering Nuclear

' SUBSCRIBED and sworn"t'o 'before me this /fd day of 198' G.b hARY C. GUINN NOTARY PUBLIC-STATE OF MISSOURI ST. LOUIS CITY j

MY COMMISSION EXPlRES JUNE 16, 1990' l

l 1

l q

l 1

r

\\

m 00 ) l,

._ p

~

1 l

r i

i b

l cc:

Gerald Charnoff, Esq.

Shaw, Pittman, Potts & Trowbridge i

2300 N.

Street, N.W.

)

Washington, D.C.

20037 i

Dr.

J.

O. Cermak

)

CFA, Inc.

4 Professional Drive (Suite 110)

Gaithersburg, MD 20879 j

R.

F. Warnick Chief, Reactor Project Branch 1

{

U.S.

Nuclear Regulatory Commission j

Region III L

799 Roosevelt Road i

Glen Ellyn, Illinois 60137 J

Bruce Little Callaway Resident Office i

U.S.

Nuclear Regulatory Commission RRil i

Steedman, Missouri 65077 Tom Alexion (2)

Of fice of Nuclear Reactor Regulation l

U.S.

Nuclear Regulatory Commission Mail Stop 316

[

7920 Norfolk Avenue Bethesda, MD 20014 Ron Kucera, Deputy Director Department of Natural Resources P.O.

Box 176 Jefferson City, MO 65102 Manager, Electric Department j

Missouri Public Service Commission P. O.

Box 360 Jefferson City, MO 65102 l

1