Docket flos.
50-424 and 50-425 9 DEC 1986 APPLICANT:
Georgia Power Ccapany FACILITY:
Vogtle, Units 1 and 2
SUBJECT:
SUMMARY
OF MEETIllG HELD TO REVIEW CABLE DOCUMENTATI0ll Cn December 3,1986, the staff met with the applicant to review cable dccu-trentation to ensure that no chlorinated polyethylene (CPE) is included in cable at Vogtle.
Participants are listed in the enclosure.
The applicant showed the staff three cable purchase specifications used at Vogtle: X3AJ01, X3AJ02, ard X3AJ04.
For the first two, the specification required a hypalon jacket. However, for X3AJ04 the acolicant gave the vendors (Rockbestos and Eaton) the option to provide jacketing of hypalon or CPE. The applicant then showed the staff the material data sheets which indicate what was received from the vendors fnr purchases under specification X3AJ04.
In each case, cable jacketing was of hypalon.
The staff requested the applicant to submit the three specifications ard the r:aterial data sheets for each. The applicant indicated that this inforrcation would be submitted by Decerrher 10, 1986.
The staff and applicant also briefly discussed the mechanical equipment qualification SCEW sheets.
The applicant indicated that updated SCEW sheets would be submitted by December 8, 1986.
Melanie A. ?! iller, Project Manager PWR Project Directorate #4 Division of PUR Licensino-A
Enclosure:
As stated DISTRIBUTILN:
Docket File Local PDR NRC PDR PWR#4 Reading BJYoungblood Reading MDuncan l'.fiille r ACRS(10)
EJordan JPartlow CGrimes JPartlow 4
WR-A PWR.7 M'R-A Pk 7 WR-A
/ rad N[u m
BJYountJblood
/86
/
6 12/y/06 i
86121 g h h 24 PDR PDR A
- Fr. R. E. Conway Georgia Power Corcpany Vogtle Electric Generating Plart Cc:
Mr. L. T. Gucwa Resident Inspector Chief Nuclear Engineer Nuclear Regulatory Commission Georgia Power Company P. O. Box 572 P.O. Box 4545 Waynesbore, Gecrgia 30830 Atlanta, Georgia 30302 Mr. Ruble A. Thor.ias Deppish Kirkland, III, Counsel Vice President - Licensing Office of the Consumers' btility Vogtle Project Council Georgia Power Company /
Suite 225 Southern Company Services, Inc.
32 Peachtree Street, N.U.
P.O. Box 2625 Atlanta, Georoia 30303 Birmingham, Alabama 35202 Jarres E. Joiner Mr. Donald C. Foster Trcutman, Sanders, Lockerman, Vice President & Project General Manager
& Ashmore Georgia Power Company Candler Building Post Office Box 299A, Route 2 127 Feachtree Street, N.E.
kaynesboro, Georgia 30830 Atlanta, Georgia 30303 Danny Feig Mr. J. A. Peiley 1130 Alta Avenue Project Licensing Manager Atlanta, Georgia 30307 Southern Company Services, Inc.
P.O. Box 2625 Carol Stangler Birmingham, Alabama 35202 Georgians Acainst f.'ucicar Energy 425 Euclid Terrace Ernest L. Blake, Jr.
Atlanta, Gecrgia 30307
-Bruce W. Churchill, Esq.
Shaw, Pittman, Potts and Trewbridge 2300 N Street, N.W.
Washington, D. C.
20037 Mr. G. Bockhold, Jr.
Vogtle Plant Manager Georgia Power Company Route ?, Fox 299-A Waynesboro, Georgia 30030 Pegional Administrator, Region 11 l'.S. Nuclear Regulatory Corv:ission 101 Marietta Street, N.W., Suite 2900 Atlanta, Georgia 30323 2
Enclosure i
Particioants NRC Diller H. Walker Georgia Power Ccn cany T. Penland Southern Comoany Services J. Wheless
.,4 4
MEETING
SUMMARY
DISTRIBUTION
- / Docket File.
~ NRC Participants 2
NRC PDR.
M. Mi11er.
L PDR H. l!alker NSIC PRC System PWR(4 Reading File-M. Cuncan OGC-J. Partlow E. Jordan B. Grirres ACRS (10)
OTHERS bcc: Licensee & Service List 5
i l