Georgia Power Company Fbst Offc0 Box.282 Waynesboro, Georgis 00830 Telephone 404 554 9961 404 724 4114 Southern Company Services, Inc.

Fbst Office Box 2625 Birmingham, Alabama 35202 Telephone 205 8704011 Vogtle Project December 5, 1986 1

Director of Nuclear Reactor Regulation File: X3BL01 Attention:

Mr. B. J. Youngblood Log:

GN-1212 PWR Project Directorate #4 Division of PWR Licensing A U. S. Nuclear Regulatory Commission Washington, D.C.

20555 NRC DOCKET NUMBERS 50-424 AND 50-425 CONSTRUCTION PERMIT NUMBERS CPPR-108 AND CPPR-109 V0GTLE ELECTRIC GENERATING PIANT - UNITS 1 AND 2 SER OPEN ITEM 1: EQUIPMENT QUALIFICATION

Dear Mr. Denton:

i Attached are revised mechanical equipment qualification (MEQ) SCEW sheets for your review of the Vogtle MEQ Program. The MEQ SCEW sheets have been revised to provide clarifications and address NRC staff concerns.

If your staff requires any additional information, please do not hesitate to contact me.

Sincerely, J. A. Bailey Project Licensing Manager JAB /sm Attachment xc:

R. E. Conway NRC Regional Administrator R. A. Thomas NRC Resident Inspector J. E. Joiner, Esquire D. Feig B. W. Churchill, Esquire R. A. McManus M. A. Miller (2)

L. T. Gucwa B. Jones, Esquire Vogtle Project File G. Bockhold, Jr.

0908V h[I 8612160317 861205 PDR ADOCK 05000424 4'

K, PDR gl

O BOP Mechanical Equipment Qualification (MEQ)

~

System Component Evaluation Work Sheet i

VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROMENT

DOCtBENTATION :

QUAL.

l REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL.
SYSTEM: AUXILIARY BUILDING OUTSIDE AIR :

OPERATING 1'(EAR 1 YEAR 2

3 TEST &

SUPPLY, NOINAL HVAC & EXHAUST TIME l ANALYSIS SYSTEMS l

COMPONENT: TORNADO DAMPERS TEMPERATURE 123 140 1

3 (oF)

MANUFACTURER: TECHNO CORPORATION PRESSURE ATMOSPHERIC : A1NOSPHERIC :

1 3

(psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 60 100 1

3 EPDM HINIDITY (*) :

DACRON CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.0E6 1.32E6 1

3 (rads)

LOCATION: OUTSIDE CONTAll#4ENT l

QUALIFIED 40 YEARS 40 YEARS 2

3 LIF1s DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 2.

SPECIFICATION X4AJ32 4

3.

TEST REPORT 1083A & 1083D I

m c

j.

y Ns 9Q

_4 A

dM 1

/

'?

q 's '

^

s 2 }v

.)

t ;

.y t

s^

}

\\J

'N s

^

BOP Mechanical Equipment Qualification (MEQ)[,",.'-', i 7

~

~

System Component Evaluation Work Shedt 3

s j

q w

s _

y

/

VOGTLE ELECTRIC GENERATING PLANT - UNIT 1

'9

~

+

r 1

s EQUIH4ENT DESChIPTIOli '

ENVIR0fMENT

DOCUE NTATION :

CUAL.

REFERENCES MTHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: AUXILIARY COMPONENT COOLING OPERATING 1 YEAR 1 YEAR 2

3 TEST &

WATER TIME

ANALYSIS
COMPONENT: CONTROL VALVE TEMPERATURE 352 365 1

3 (oF)

MANUFACTURER: FISHER PRESSURE 50 158 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 EPDM HINIDITY (*)

ETHYLENE-PROPYLENE GRAFOIL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE RADIATION 1.8E8 l

2.0E8 1

3 (rads)

LOCATION: INSIDE & OUTSIDE CONTAI! MENT :

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 2.

SPECIFICATION X5AC03 3.

TEST REPORT FOP-llAB-4

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIRO! MENT

DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL.
SYSTEM: AUXILIARY COMPONENT COOLING OPERATING 1 YEAR 1 YEAR 2

3 TEST &

WATER TIME ANALYSIS

COMPONENT: CONTROL VALVE TEMPERATURE 352 740 1

3 (o F)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HtNIDITY (%)

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.0E9 1.0 Ell 1

3 (rads) l l

l l

l l

l i

IDCATION: INSIDE CONTAIINENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE l

l l

l l

DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.I1.B.1-1 l

2.

SPECIFICATION X4AR01 3.

TEST REPORT 46877-01

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPhENT

  • DOCINENTATION :

QUAL.

REFERENCES PETHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: AUXILIARY COMPONENT COOLING OPERATING 1 YEAR 1 YEAR 2

l 3

TEST &

WATER TIME ANALYSIS

COMPONENT: CHECK VALVE TEMPERATURE 352 740 1

3 (aF)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HINIDITY (%) :

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.0E9 1.0 Ell 1

3 (rads)

LOCATION: INSIDE CONTAINMENT l

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DoctNENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.I1.B.1-1 2.

SPECIFICATION X4AR01 3.

TEST REPORT 46877-01 i

l l

l

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 l

l EQUIPMENT DESCRIPTION ENVIRO!NENT

DOCINENTATION :

QUAL.

l l

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: AUXILIARY COMPONENT COOLING l

OPERATING 1 YEAR 1 YEAR 2

3

ANALYSIS i

WATER TIME

COMPONENT: CHECK VALVE TEMPERATURE 352 740 1

3 l

(oF) l l

l l

l l

l MANUFACTURER: ROCKWELL PRESSURE l

50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HUMIDITY (*) :

ASBESTOS (NOTE 1)

CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.8E8 1.0 Ell 1

3 (rads) l l

l l LOCATION: INSIDE CONTAINMENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X4AR34A REPORT 46877-01.

3.

TEST REPORT (BECHTEL LOG) X4AR34A-75

BOP Mechanical Equipment Qualification (MEQ) y, System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROINENT

DOCtNENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL.
SYSTEM: AUXILIARY FEEDWATER OPERATING 1 YEAR 1 YEAR 2

3

ANALYSIS TIME
COMPONENT: CONTROL VALVE TEMPERATURE 352 740 1

3 (oF)

MANUFACTURER: FISHER PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HLNIDITY (*) :

GRAPHITE (NOTE 1)

CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.8E8 1.0E11 1

3 (rads)

LOCATION: OUTSIDE CONTAIPMENT (NOTE 2)

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE i

DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X5AC01 REPORT 46877-01.

3.

TEST REPORT FQP-llAG-1 & 2 2.

WORST-CASE ENVIROM4 ENTAL PARAMETERS CONSIDERED TO ALLOW FOR VALVE USE IN ANY PLANT LOCATION.

l

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION l

ENVIROPMENT

DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL.

l l

l l

SYSTEM: AUXILIARY FEEDWATER OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME ANALYSIS

COMPONENT: CONTROL VALVE TEMPERATURE 352 l

740 1

3 (oF)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 l

1000 1

l 3

(psig) l l

l l

l l

l l

l l

l l

l l AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HLMIDITY (*) :

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE RADIATION 1.0E9 1.0 Ell 1

3 (rads) l l

LOCATION: OUTSIDE CONTAIfMENT (NOTE 1)

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE l

l l

l l

l l

l l

l DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

WORST-CASE ENVIROINENTAL PARAMETERS CONSIDERED 2.

SPECIFICATION X4AR01 TO ALLOW FOR VALVE USE IN ANY PLANT LOCATION.

3.

TEST REPORT 46877-01 l

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIRO) MENT

DOCINENTATION :

QUAL.

REFERENCES MITHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. !
SYSTEM: AUXILIARY FEEDWATER OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME ANALYSIS

COMPONENT: CHECK VALVE TEMPERATURE 352 740 1

3 (aF)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig) l l

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL

HINIDITY (*) :

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.0E9 1.0 Ell 1

3 (rads) i

LOCATION: INSIDE & OUTSIDE CONTAIPNENT :

QUALIFIED 40 YEARS 40 YEARS 2

3 l

l l

LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3. TABLE 3.ll.B.1-1 l

2.

SPECIFICATION X4AR01 3.

TEST REPORT 46877-01

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROINENT

DOCtNENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: AUXILIARY FEEDWATER OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME

ANALYSIS l

l

COMPONENT: S'IT)P CHECK VALVE TEMPERATURE 352 740 1

3

(*F)

MANUFACTURER
ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HtNIDITY (*) :

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT l

NOT l

1 3

SPRAY APPLICABLE :

APPLICABLE RADIATION 1.0E9 1.0 Ell 1

3 (rads)

LOCATION: INSIDE & OUTSIDE CONTAIPMENT l QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 2.

SPECIFICATION X4AR01 3.

TEST REPORT 46877-01

I BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT

DOCINENTATION :

. QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: AUXILIARY FEEDWATER OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME ANALYSIS

COMPONENT: STOP CONTROL VALVE TEMPERATURE :

352 740 1

3 (oF)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HINIDITY (*) :

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE RADIATION 1.0E9 1.0311 1

3 (rads)

LOCATION: OUTSIDE CONTAllNENT (NOTE 1)

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

WORST-CASE ENVIRO) MENTAL PARAMETERS CONSIDERED 2.

SPECIFICATION X4AR01 TO ALLOW FOR VALVE USE IN ANY PLANT feCATION.

3.

TEST REPORT 46877-01

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT l DOCUMENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: AUXILIARY FEEDWATER OPERATING 1 YEAR 1 YEAR 2

3

ANALYSIS TIME
COMPONENT: CHECK VALVE TEMPERATURE 352 740 1

3 (aF)

MANUFACTURER: DRESSER PRESSURE 50 1000 1

3 (psig) i

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HINIDITY (*) :

GRAPHITE (NOTE 1)

ASBESTOS (NOTE 1)

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.8E8 1.0 Ell 1

3 (rads)

LOCATION: INSIDE & OUTSIDE CONTAl!@ LENT :

QUALIFIED 40 YEARS 40 YEARS 2

l 3

LIFE DOCtNENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X4AR06 REPORT 46877-01.

3.

TEST REPORT (BECHTEL LOG) X4AR06-163

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING FLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROMfENT DOCIMENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: CHEMICAL & VOLINE CONTROL OPERATING 1 YEAR 1 YEAR 2

3

ANALYSIS TIME
COMPONENT: CONTROL VALVE TEMPERATURE 352 740 1

3 (oF)

MANUFACTURER: FISHER PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HUMIDITY (%) :

ASBESTOS (NOTE 1)

FLUOROELASTOMER (NOTE 2)

NITRILE RUBBER (NOTE 2)

CHEMICAL NOT l

NOT 1

3 ASBESTOS / NITRILE RUBBER (NOTE 2)

SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.8E8 1.0 Ell 1

3 (rads)

LOCATION: INSIDE CONTAINMENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X5AC01 REPORT 46877-01.

3.

TEST REPORT FQP-llAG-ll 2.

COMPONENT NOT CRITICAL TO THE VALVE'S SAFETY FUNCTION.

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROl@ LENT DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. !
SYSTEM: CHEMICAL & VOLINE CONTROL OPERATING 1 YEAR 1 YEAR 2

l 3

ANALYSIS-l l

l TIME

COMPONENT: CHECK VALVE
TEMPERATURE 352 740 1

3 (aF)

MANUFACTURER: DRESSER PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HlNIDITY (*) :

GRAPHITE (NOTE 1)

ASBESTOS (NOTE 1)

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.8E8 1.0E11 1

3 (rads)

LOCATION: INSIDE & OUTSIDE CONTAINMENT l QUALIFIED 40 YEARS 40 YEARS 2

l 3

LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X4AR06 REPORT 46877-01, 3.

TEST REPORT (BECHTEL LOG) X4AR06-163

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIRO!NENT

DOCLNENTATION :

QUAL.

REFERENCES METEOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :

SYSTEM: CHEMICAL & VOLINE CONTROL OPERATING 1 YEAR 1 YEAR 2

3

ANALYSIS TIME
COMPONENT: CHECK VALVE
TEMPERATURE 352 740 1

3 (aF)

MANUFACTURER: ROCKWELL PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HINIDITY (*) :

ASBESTOS (NOTE 1)

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE RADIATION 1.8E8 1.0E11 1

3 (rads)

LOCATION: INSIDE & OUTSIDE CONTAI!NENT l QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.I-l 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X4AR34A REPORT 46877-01.

i, 3.

TEST REPORT (BECHTEL LOG) X4AR34A-75

BOP hechanical Equipment Qualification (MEQ)

Sy.*em Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPE NT DESCRIPTION ENVIRoletENT

DOCLNENTATION :

QUAL.

REFERENCES MTHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: CONDENSATE & FEEDWATER OPERATING 1 YEAR 1 YEAR 2

l 3

TEST TIME

COMPONENT: CONTROL VALVE
TEWERATURE :

320 335 1

3 (a F)

MANUFACTURER: ANCHOR DARLING PRESSURE 15 16.5 1

3 (psig)

J

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 ETHYLENE-PROPYLENE HtMIDITY (*)

NYIDN TEFIDN VITON CHEMICAL NOT NOT 1

3 LEATHER SPRAY APPLICABLE :

APPLICABLE :

VELLINOID (KRAFT PAPER)

NEOPRENE RADIATION 5.0E6 5.5E7 1

3 l

(rads)

LOCATION: OUTSIDE CONTAll#ENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCIDENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 2.

SPECIFICATION X4AR19 3.

TEST REPORT 46657-03

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIf9ENT DESCRIPTION ENVIROISENT

DOCIDENTATION :

QUAL.

REFERENCES MTHOD PARAETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL.
SYSTEM: CONDENSATE & FEEDWATER OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIE

ANALYSIS
COMPONENT: CHECK VALVE
TEWERATURE :

352 740 1

3

(* F)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL

HUMIDITY (*) :

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE RADIATION 1.0E9 1.0 Ell 1

3 (rads)

LOCATION: OUTSIDE CONTAI)#ENT (NOTE 1)

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE I

DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

WORST-CASE ENVIROMENTAL PARANTERS CONSIDERED 2.

SPECIFICATION X4AR01 TO ALLOW FOR VALVE USE IN ANY PLANT IDCATION.

3.

TEST REPORT 46877-01 l

J

O BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPENT DESCRIPTION ENVIROfMENT

DOCIDENTATION :

QUAL.

REFERENCES MTHOD PARAN TER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: CONDENSATE CHEMICAL INJECTION OPERATING 1 YEAR 1 YEAR 2

3 ANALYSIS TIE

COMPONENT: CONTROL VALVE
TEMPERATURE :

352 740 1

3

(*F)

MANUFACTURER: FISHER PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HUMIDITY (%) :

ASBESTOS (NOTE 1)

FLUOROELASTOER (NOTE 2)

NITRILE RUBBER (NOTE 2)

CHEMICAL NOT NOT 1

3 ASBESTOS / NITRILE RUBEER (NOTE 2)

SPRAY APPLICABLE :

APPLICABLE RADIATION 1.8E8 1.0 Ell 1

3 (rada)

LOCATION: OUTSIDE CONTAIPMENT (NOTE 3)

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 1.

FSAR CHAPTER 3 TABLE 3.I1.B.1-1 REPORT 46877-01.

2.

SPECIFICATION X5AC01 2.

COWONENT NOT CRITICAL 10 THE VALVE'S 3.

TEST REPORT FQP-llAG-5 SAFETY FUNCTION.

3.

WORST-CASE ENVIROINENTAL PARAMETERS CONSIDERED TO ALLOW FOR VALVE USE IN ANY PLANT LOCATION.

BCP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUII9ENT DESCRIPTION ENVIPOMENT

DOCtDENTATION :

QUAL.

REFERENCES MTHOD PARAE TER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: CONDENSATE CHEMICAL INJECTION OPERATING 1 YEAR 1 YEAR 2

3

ANALYSIS TIME
COMPONENT: CHECK VALVE
TEMPERATURE 352 740 1

3 (oF)

MANUFACTURER: DRESSER PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HtNIDITY (*) :

GRAPHITE (NOTE 1)

ASBESTOS (NOTE 1)

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE RADIATION 1.8E8 1.0 Ell 1

3 (rads)

IX) CATION: INSIDE CONTAI! MENT l

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X4AR06 REPORT 46877-01.

3.

TEST REPORT (BECHTEL IDG) X4AR06-163

O BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROM4ENT l DOCINENTATION :

QUAL.

REFERENCES MTHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: CONTAIPMENT & AUXILIARY OPERATING 1 YEAR 1 YEAR 2

3 TEST &

BUILDING DRAINS TIME ANALYSIS

COWONENT: CONTROL VALVE TEMPERATURE 352 740 1

3 (aF)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HUMIDITY (*) :

GRAPHITE ASBESTOS / STAINLESS STEEL 1

3 CHEMICAL NOT l

NOT SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.0E9 1.0 Ell 1

3 (rads)

LOCATION: INSIDE & OUTSIDE CONTAIPMENT :

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 2.

SPECIFICATION X4AR01 3.

TEST REPORT 46877-01

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT

DOCIMENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: CONTAINMENT CRDM, OPERATING 1 YEAR 1 YEAR 2

3 ANALYSIS CAVITY & REACTOR SUPPORT TIME COOLING

COMPONENT: PRESSURE RELIEF TEMPERATURE 352 352 1

3 (aF)

MANUFACTURER: TECHNO CORPOR*.TIvN PRESSURE 50 50 1

3 (psig)

AGE-SENSITIVE MATERIALS

RELATIVE 100 100 1

3 NO AGE-SENSITIVE COMPONENTS (NOTE 1)

HINIDITY (*) :

CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.8E8 1.8E8 1

3 (rads)

LOCATION: INSIDE CONTAIPMENT QUALIFIED 40 YEARS 40 YEARS 2

l 3

LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

CONSTRUCTED FROM ALL-M8TALLIC COMPONENTS WHICH 2.

SPECIFICATION X4AJ32 ARE INSENSITIVE TO DEGRADATION OVER THE 3.

TEST REPORT 883B & 1283A SPECIFIED RANGE OF ENVIROPMENTAL CONDITIONS.

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 l

EQUIPMENT DESCRIPTION ENVIRODNENT

DOCINENTATION :

QUAL.

REFERENCES DETHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: CONTAIPMENT CRDM, OPERATING 1 YEAR 1 YEAR 2

l 3

TEST &

i CAVITY & REACTOR SUPPORT TIME ANALYSIS

{

COOLING

COMPONENT: FAN TEMPERATURE 352 346 1

3 (aF)

NOTE 1 l

l i

l l MANUFACTURER: JOY MANUFACTURING PRESSURE 50 l

78 1

3 COMPANY (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 NO AGE-SENSITIVE COMPONENTS.

HINIDITY (*) :

CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.8E8 2.04E8 1

3 (rads)

LOCATION: INSIDE CONTAIPMENT l

QUALIFIED 40 YEARS 40 YEARS 2

3 l

LIFE 1

DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.I1.B.1-1 1.

REQUIRED FOR LOCA ONLY (2910F). QUALIFICATION 2.

SPECIFICATION X4AJ34 TEMPERATURE ACCEPTABLE BASED ON CALCULATION 3.

TEST REPORT X-604 & X-1028 X6CHG.18.

BOP Mechanical Equipment Qualification (MEQ)

I System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT DOCtNENTATION :

QUAL.

REFERENCES letTHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: CONTAllNENT HEAT REMOVAL OPERATING 1 YEAR 1 YEAR 2

3 TEST TIME

COMPONENT: CONTAIPMENT COOLING UNIT TEMPERATURE 352 415 1

3 (oF)

MANUFACTURER: CVI l

PRESSURE 50 l

200 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 VITON

HINIDITY (*)

ETHYLENE-PROPYLENE NEOPRENE CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE :

APPLICABLE RADIATION 1.8E8 2.2E8 1

3 (rads)

LOCATION: INSIDE CONTAI!NENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCtNENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 2.

SPECIFICATION X4AJ16 3.

TEST REPORT 17350

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROletENT

DOC M NTATION :

QUAL.

REFERENCES MTHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: CONTAIMENT HEAT REMOVAL OPERATING 1 YEAR 1 YEAR 2

l 3

ANALYSIS i

TIME

COMPONENT: CONTAl!# GENT BACKDRAFT
TEMPERATURE 352 367 1

3 DAWER l

(*F)

MANUFACTURER: QUALITY AIR DESIGN PRESSURE 50 50 1

3 (psig)

I

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 SILICONE RUBBER

HINIDITY (*) :

POLYISOBUTYLENE-BUTYL RUBBER r

SILICONE RTV CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.8E8 2.0E8 1

3 (rads) i

LOCATION: INSIDE CONTAI) DENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE 1

1 DOCIPENTATION

REFERENCES:

NOTES:

1 1.

FSAR CHAPTER 3. TABLE 3.I1.B.1-1 2.

SPECIFICATION X4AJ20 l

3.

TEST REPORT 83-387 i

O BOP Mechanical Equipment Qualification (MEQ)

I System Component Evaluation Work Sheet VOCTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPENT DESCRIPTION ENVIRO M NT

DOCIDENTATION :

QUAL.

REFERENCES MTHOD PARAMTER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: CONTROL BUILDING ELECTRICAL OPERATING 1 YEAR 1 YEAR 2

3 TEST &

PENETRATION ROOM FILTRATION TIME

ANALYSIS EXHAUST l
C0pf0NENT: TORNADO DAW ERS
TEWERATURE :

120 140 1

3 (aF)

MANUFACTURER: TECHNO CORPORATION PRESSURE
ATMOSPHERIC : ATMOSPHERIC :

1 3

(psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 90 100 1

3 EPDM

HIMIDITY (*) :

DACRON CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 5.0E5 1.32E6 1

3 (rada)

IOCATION: OUTSIDE CONTAI M NT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOC 17ENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3. TABLE 3.ll.B.1-1 2.

SPECIFICATION X4AJ32 3.

TEST REPORT 1083A & 1083D

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet V0GTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPENT DESCRIPTION ENVIROISENT

DOCIMENTATION :

QUAL.

REFERENCES ETHOD PARAETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: ELECTRICAL TUNNEL VENTILATION OPERATING 1 YEAR 1 YEAR 2

3 ANALYSIS TIME

COMPONENT: FAN
TEWERATURE 123 123 1

3

(* F)

MANUFACTURER: BUFFAID FORGE PRESSURE
A1MOSPHERIC : A1MOSPHERIC :

1 3

(psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 90 90 1

3 THE FANS DO NOT CONTAIN ANY

HIMIDITY (*) :

AGE-SENSITIVE NOMETALLIC COMPONENTS (NOTE 1)

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 5.0E5 5.0E5 1

3 (rads)

IDCATION: OUTSIDE CONTAIPMENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCIMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

CONSTRUCTED FROM ALL-METALLIC COWONENTS WHICH 2.

SPECIFICATION X4AJ02 ARE INSENSITIVE TO DEGRADATION OVER THE 3.

TEST REPORT DO-146F SPECIFIED RANGE OF ENVIROl# ENTAL CONDITIONS.

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPM NT DESCRIPTION ENVIROlGENT

DOCINENTATION :

QUAL.

REFERENCES MTHOD PARAM TER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: ESF ROOM COOLERS OPERATING 1 YEAR 1 YEAR 2

l 3

TEST &

TIME

ANALYSIS
CapFONENT: ROOM COOLERS
TEWERATURE :

104 123 1

3

(*F)

MANUFACTURER: AMRICAN AIR FILTER PRESSURE
ATMOSPHERIC : ATNOSPHERIC :

1 3

(psig)

AGE-SENSITIVE MATERIALS: NEOPRENE RELATIVE 60 100 1

3

HINIDITY (*) :

CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.0E7 1.SE7 1

3 (rada)

IDCATION: OUTSIDE CONTAllelENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOClNENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3 TABLE 3.ll.B.1-1 2.

SPECIFICATION X4AJ06 3.

TEST REPORT NESE-738

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIM4ENT DESCRIPTION ENVIRO) MENT

DOCINENTATION :

QUAL.

REFERENCES PECTHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: FIRE PROTECTION OPERATING 1 YEAR 1 YEAR 2

l 3

TEST &

TIME ANALYSIS

COMPONENT: CONTROL VALVE TEMPERATURE 352 740 1

3 (aF)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HINIDITY (*) :

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.0E9 1.0E11 1

3 (rads)

IDCATION: OUTSIDE CONTAIPMENT (NOTE 1)

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

WORST-CASE ENVIROPMENTAL PARAMETERS CONSIDERED 2.

SPECIFICATION X4AR01 TO ALLOW FOR VALVE USE IN ANY PLANT LOCATION.

3.

TEST REPORT 46877-01

O BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1

{

t EQUIPMENT DESCRIPTION ENVIROl#EENT

DOCLNENTATION :

QUAL.

REFERENCES MTHOD PARAMTER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: FIRE PROTECTION OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME ANALYSIS :

l l

COMPONENT: CHECK VALVE
TEWERATURE 352 740 1

3 (aF)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig) l

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL

HLMIDITY (*) :

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.0E9 1.0E11 1

3 i

(rada)

IDCATION: INSIDE CONTAIINENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE l

l 1,

DOCtMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABIS 3.ll.B.1-1 2.

SPECIFICATION X4AR01 3.

TEST REPORT 46877-01 i

a

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIRO!NENT

DOCINENTATION :

QUAL.

l l

REFERENCES MTHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL.
SYSTEM: FUEL HANDLING BUILDING HVAC OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME ANALYSIS

COMPONENT
'IURNADO DAMPER
TEMPERATURE 120 140 1

3 (oF)

MANUFACTURER: TECHNO CORPORATION PRESSURE
A1NOSPHERIC : A'INOSPHERIC :

1 3

(psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 90 100 1

3 EPDM

HINIDITY (*) :

i DACRON 1

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

i RADIATION 5.0E5 1.32E6 1

3 (rads)

IDCATION: OUTSIDE CONTAIPNENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 2.

SPECIFICATION X4AJ32 3.

TEST REPORT 1083A & 1083D

.w 8

p

,~

w :..

3_

O, :,.

' : 1<

~'

a.

s s,

~

J.,

=

s

\\

s

-g

,g x.

'Y:)s BOP Mechanical Equipment Qualification

(*- EQ )

t

'~

System Component Evaluati,on Work Sheet s_.s

\\

VOGTLE EIICTRIC GENERATI?iG PLANT - UNIT !.

i i-f w

EQUIPDENT DESCRIP? ION i

ENVIROl0ENT

DOCLMENTATION :

CUAL.

-s REFERENCES NETHOD

  • SPECIr'ICATION : QUALIFICATION : SPFC. : QUAf,. :

PARAMETER

SYSTEM: FUEL HANDLING BUILDING HVAC OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME ANALYSIS 1

COMPONENT: DABFER (CLASS A)
TEMPERATURE :

116 371 1

3 (a F)

MANUFACTURER: JOHNSON CONTROLS /

PRESSURE A'INOSPHERIC :

150 1

3 l

JADESBURY (psig) l

ACE-SENSITIVE MATERIALS:

RELATIVE 60 100 1

3 TEFZEL HtNIDITY (*) :

NOMEX CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 5.0E5 1.2E8 1

3 (rada)

IDCATION: OUTSIDE CONTAI)#ENT QUALIFIED 40 YEARS 40 YEARS 2

l 3

LIFE DOctBENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3. TABLE 3.ll.B.1-1 i

2.

SPECIFICATION X4AJ20 3.

TEST REPORT W/S 61

o BOP Mechanical Equipment Qualification (MEQ)

~

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT

DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :

l l

l l

SYSTEM: FUEL HANDLING BUILDING HVAC OPERATING 1 YEAR 1 YEAR 2

3 ANALYSIS TIME

COMPONENT: DAMPER, BUBBLE TIGHT TEMPERATURE :

118 200 1

3 (CLASS B)

(oF)

MANUFACTURER: JOHNSON CONTROLS /

PRESSURE A'INOSPHERIC A'IMOSPHERIC :

1 3

QUALITY AIR DESIGN (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 EPDM/ NYLON HINIDITY (*) :

POLYISOBUTYLENE-BUTYL RUBBER SYNFLEX 3700 (NYLON ll/POLYURETHANE/ l l

l l

l l

l l

POLYESTER FIBER /HYTREL)

CHEMICAL NOT l

NOT 1

3 SFRAY APPLICABLE :

APPLICABLE :

I RADIATION 1.0E6 1.0E7 l

1 3

l l

(rads) l

LOCATION: OUTSIDE CONTAINMENT QUALIFIED 40 YEARS 40 YEARS 2

l 3

LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 2.

SPECIFICATION X4AJ20 3.

TEST REPORT 84-145

1 BOP Mechanical Equipment Qualification (MEQ)

System Comiponent Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIFNENT DESCRIPTION ENVIROINENT

DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: FUEL HANDLING BUILDING HVAC OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME

ANALYSIS COMPONENT: POST-ACCIDENT FIL mn
TEMPERATURE 120 l

212 1

3 EXHAUST UNIT (aF)

MANUFACTURER: AMERICAN AIR FILTER PRESSURE
A'IMOSPHERIC ATMOSPHERIC :

1 3

(psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 90

>90 1

3 MINERAL WOOL HINIDITY (*) :

GLASS CLOTH SILICONE RTV HYPAIDN CHEMICAL NOT NOT 1

3 NEOPRENE SPRAY APPLICABLE :

APPLICABLE :

TEFLON ASBESTOS CARBON RADIATION 2.0E5 5.0E5 1

3 (rads)

LOCATION: OUTSIDE CONTAIfNENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 2.

SPECIFICATION X4AJ07 3.

TEST REPORT NESE-329, NESE-832, & A-601-83-01

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT

DOCLMENTATION :

QUAL.

REFERENCES PETHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. !
SYSTEM: INSTRlNENT & SERVICE AIR OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME

ANALYSIS
COMPONENT: CONTROL VALVE TEMPERATURE :

352 740 1

3 (aF)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HINIDITY (*) :

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.0E9 1.0 Ell 1

3 (rads)

LOCATION: OUTSIDE CONTAIPMENT (NOTE 1)

QUALIFIED 40 YEARS 40 YEARS 2

l 3

LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 1.

WORST-CASE ENVIROPMENTAL PARAMETERS CONSIDERED 2.

SPECIFICATION X4AR01 TO ALIDW FOR VALVE USE IN ANY PLANT LOCATION.

3.

TEST REPORT 46877-01 1

O BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT

DOCLNENTATION :

QUAL.

REFERENCES DEtTHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL.
SYSTEM: INSTRINENT 8 SERVICE AIR OPERATING 1 YEAR 1 YEAR 2

3 ANALYSIS TIME

COMPONENT: CONTROL VALVE TEMPERATURE 352 740 1

3 (oF)

I

)

MANUFACTURER: FISHER PRESSURE 50 1000 1

3 1

(psig) i

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HlNIDITY (%) :

ASBESTOS (NOTE 1)

FLUOROELASTOMER (NOTE 2)

NITRILE RUBBER (NOTE 2)

CHEMICAL NOT l

NOT 1

3 ASBESTOS / NITRILE RUBBER (NOTE 2)

SPRAY APPLICABLE :

APPLICABLE RADIATION 1.8E8 1.0 Ell 1

3 (rada)

LOCATION: OUTSIDE CONTAINMENT (NOTE 3)

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 REPORT 46877-01.

2.

SPECIFICATION X5AC01 2.

COMPONENT NOT CRITICAL TO THE VALVE'S 3.

TEST REPORT FQP-llAG-6 SAFETY FUNCTION.

i 3.

WORST-CASE ENVIROPMENTAL PARAMETERS CONSIDERED TO ALLOW FOR VALVE USE IN ANY PLANT LOCATION.

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT

DOCINENTATION :

QUAL.

REFERENCES :

MTHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. !

SYSTEM: INSTRIMENT & SERVICE AIR OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME

ANALYSIS COMPONENT: CHECK VALVE TEMPERATURE 352 740 1

3 (oF)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL

HINIDITY (*) :

GRAPHITE ASBES10S/ STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.0E9 1.0El]

1 3

(rads)

LOCATION: INSIDE CONTAI!NENT l

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 2.

SPECIFICATION X4AR01 3.

TEST REPORT 46877-01

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIRONMENT

DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: INSTRUMENT & SERVICE AIR OPERATING 1 YEAR 1 YEAR 2

3 ANALYSIS TIME

COMPONENT: CHECK VALVE TEMPERATURE :

352 740 1

3 (oF)

MANUFACTURER: ROCKWELL PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HINIDITY (%) :

ASBESTOS (NOTE 1)

CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.8E8 1.0 Ell 1

3 (rads)

LOCATION: INSIDE CONTAINMENT QUALIFIED 40 YEARS 40 YEARS 2

3 l

l LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYIE 2.

SPECIFICATION X4AR34A REPORT 46877-01.

3.

TEST REPORT (BECHTEL LOG) X4AR34A-75

O BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 I

EQUIPMENT DESCRIPTION ENVIROM4ENT

DOCLNENTATION :

QUAL.

REFERENCES METHOD 1

PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL.

4

SYSTEM: INSTRUMENT & SERVICE AIR OPERATING 1 YEAR 1 YEAR 2

3

ANALYSIS TIME j

l l

COMPONENT: CHECK VALVE TEMPERATURE 352 740 1

3 (oF)

MANUFACTURER: DRESSER PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HUMIDITY (*) :

GRAPHITE (NOTE 1)

ASBESTOS (NOTE 1)

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE RADIATION 1.8E8 1.0 Ell 1

3 (rads) l l

l

LOCATION
INSIDE CONTAIM4ENT l

QUALIFIED 40 YEARS 40 YEARS 2

3 i

LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X4AR06 REPORT 46877-01.

3.

TEST REPORT (BECHTEL LOG) X4AR06-163

O BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 l

l l

l EQUIPMENT DESCRIPTION ENVIROPNENT

DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :

l l SYSTEM: MAIN STEAM l

OPERATING 1 YEAR 1 YEAR 2

3 ANALYSIS TIME l

l l

l l

l l

COMPONENT: A1NOSPHERIC STEAM DINP l

TEMPERATURE 320 l

740 1

3 VALVE l

(o F) l l

l l

l l

MANUFACTURER: CCI PRESSURE 15 1000 1

3 (psig) l l

l l

l l

l l

l l AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HUMIDITY (*) :

l l

l l

ASBESTOS / STAINLESS STEEL (NOTE 1)

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE :

l l

l l

l l

l l

l l

l l

RADIATION 5.0E6 1.0 Ell 1

3 (rads) l l

l l

l

LOCATION: OUTSIDE CONTAINMENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE l

l l

l l

l l

l l

l l

DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X5AC13 REPORT 46877-01.

3.

TEST REPORT (VENDOR DRAWING NO.) 23469-1, -2

O BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet V0GTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIRO!NENT

DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL.

l l

l l

l l

l l

l l SYSTEM: MAIN STEAM OPERATING 1 YEAR 1 YEAR 2

3 TEST TIME l

l l

l l

l l

l l COMPONENT: MAIN STEAM ISOLATION TEMPERATURE 320 358 1

3 VALVE l

(oF) l l

l l

MANUFACTURER: ROCKWELL PRESSURE 15 45 1

3 (psig) l l

l l

l l

l l

l l

l l

l l

l l

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 NYLON HUMIDITY (%) l l

l l

l l

VITON i

ETHYLENE-PROPYLENE i

GRAFOIL CHEMICAL NOT l

NOT 1

3 SPRAY l

APPLICABLE APPLICABLE :

l l

l l

l l

l l

l l

l l

l l

l l

l RADIATION 5.0E6 2.13E7 1

3 (rads) l l

l l

l

LOCATION: OUTSIDE CONTAINMENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE l

l l

l DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 2.

SPECIFICATION X4AR17 3.

TEST REPORT RAL-7088, RAL-7089 & 44309-1

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROfMENT

DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER l SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :

l l

l l

l l

SYSTEM: MAIN STEAM OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME ANALYSIS l

l 1

COMPONENT: CONTROL VALVE
TEMPERATURE 352 740 1

3 (oF)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig) l l

l l

l l

l l

l l

l AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL

HINIDITY (*) ;

(

GRAPHITE l

ASBESTOS / STAINLESS STEEL l

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.0E9 1.0E11 l

1 3

I (rads) l l

l l

l l

l l

l LOCATION: OUTSIDE CONTADNENT (NOTE 1)

QUALIFIED 40 YEARS 40 YEARS 2

3 l

LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

WORST-CASE ENVIROMENTAL PARAMETERS CONSIDERED 2.

SPECIFICATION X4AR01 TV ALLOW FOR VALVE USE IN ANY PLANT LOCATION.

3.

TEST REPORT 46877-01

o BOP Mechanical Equipment Qualification (MEQ)

~

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROMENT

DOCUMENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC.

l-QUAL. :

SYSTEM: MAIN STEAM OPERATING 1 YEAR 1 YEAR 2

l 3

ANALYSIS TIME
COMPONENT: CONTROL VALVE TEMPERATURE 352 740 1

3 (aF)

MANUFACTURER: FISHER PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 l

100 1

3 1

GRAFOIL (NOTE 1)

HlNIDITY (*) :

ASBESTOS (NOTE 1)

FLUOROELASTOMER (NOTE 2)

NITRILE RUBBER (NOTE 2)

CHEMICAL NOT NOT l

1 3

i ASBESTOS / NITRILE RUBBER (NOTE 2)

SPRAY APPLICABLE :

APPLICABLE RADIATION 1.8E8 1.0 Ell 1

3 i

(rads) i

LOCATION: INSIDE & OUTSIDE CONTAIMENT :

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X5AC01 REPORT 46877-01.

3.

TEST REPORT FQP-llAG-10 & FQP-llAG-12 2.

COMPONENT NOT CRITICAL TO THE VALVE'S SAFETY FUNCTION.

O BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROINENT l DOCtNENTATION :

QUAL.

REFERENCES MTHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: MAIN STEAM OPERATING 1 YEAR 1 YEAR 2

3 ANALYSIS TIME

COMPONENT
RELIEF VALVE TEMPERATURE 352 740 1

3 l

(* F)

MANUFACTURER
CROSBY PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HINIDITY (*) :

ASBESTOS (NOTE 1)

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 1.8E8 l

1.0 Ell 1

3 (rads)

LOCATION
OUTSIDE CONTAllNENT (NOTE 2)

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X5AC05 REPORT 46877-01.

3.

TEST REPORT (VENDOR DRAWING NO.) DS-C-62569 2.

WORST-CASE ENVIROINENTAL PARAMETERS CONSIDERED TO ALLOW MR VALVE USE IN ANY PLANT LOCATION.

o BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet V0GTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIRO!NENT

DOCUMENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: MAIN STEAM OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME

ANALYSIS COMPONENT: CHECK VALVE TEMPERATURE 352 740 1

3

($ F)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HINIDITY (*)

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE APPLICABLE RADIATION 1.0E9 1.0E11 1

3 (rads)

LOCATION: OUTSIDE CONTAllefENT (NOTE 1)

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

WORST-CASE ENVIROMfENTAL PARAMETERS CONSIDERED 2.

SPECIFICATION X4AR01 TO ALLOW FOR VALVE USE IN ANY PLANT IDCATION.

3.

TEST REPORT 46877-01

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 I

EQUIPMENT DESCRIPTION ENVIROINENT

DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: NUCLEAR SAMPLING - LIQUID OPERATING 1 YEAR 1 YEAR 2

3

ANALYSIS TIME
COMPONENT: CONTROL VALVE TEMPERATURE 352 740 1

3 (oF)

MANUFACTURER: FISHER PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HINIDITY (*) :

ASBESTOS (NOTE 1)

FLUOROELASTOMER (NOTE 2)

NITRILE RUBBER (NOTE 2)

CHEMICAL NOT NOT 1

3 ASBESTOS / NITRILE (NOTE 2)

SPRAY APPLICABLE :

APPLICABLE :

l l

l RADIATION 1.8E8 1.0 Ell 1

3 (rads)

LOCATION: INSIDE & OUTSIDE CONTAIPMENT :

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X5AC01 REPORT 46877-01.

3.

TEST REPORT FQP-llAG-4, FQP-llAG-5 & FQP-llAG-13 2.

COMPONENT NOT CRITICAL TO THE VALVE'S SAFETY FUNCTION.

O BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROISBNT l DOCINENTATION :

QUAL.

REFERENCES :

PETHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: NUCLEAR SERVICE COOLING WATER OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME ANALYSIS

COMPONENT: BUTTERFLY VALVE TEMPERATURE 250 365 1

3 (a F)

MANUFACTURER: FISHER PRESSURE 11.7 150 1

3 (psig)

(psia)

AGE-SENSITIVE MATERIALS:

RELATIVE 90 100 1

3 EPDM HINIDITY (*) :

ETHYLENE-PROPYLENE GRAFOIL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 2.0E6 1.0E7 1

3 (rada)

LOCATION: OUTSIDE CONTAI1 MENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.I1.B.1-1 2.

SPECIFICATION X5AC03 3.

TEST REPORT FQP-llAB-2

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIRO!#fENT

DOCINENTATION :

QUAL.

REFERENCES PETHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: NUCLEAR SERVICE COOLING WATER OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME ANALYSIS

COMPONENT: CHECK VALVE TEMPERATURE 352 740 1

3 (o F)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HtNIDITY (*) ;

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.0E9 1.0 Ell 1

3 (rads)

LOCATION: INSIDE & OUTSIDE CONTAIM1ENT l QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3. TABLE 3.I1.B.1-1 2.

SPECIFICATION X4AR01 3.

TEST REPORT 46877-01

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROINENT l DOCUMENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: P1 PING PENETRATION AREA OPERATING 1 YEAR 1 YEAR 2

3 TEST &

FILTRATION & EXHAUST TIME ANALYSIS

COMPONENT: TORNADO DAMPERS TEMPERATURE 123 140 1

l 3

(oF)

MANUFACTURER: TECHNO CORPORATION PRESSURE ATMOSPHERIC A1MOSPHERIC :

1 3

(psig) l l

l l

l l

AGE-SENSITIVE MATERIALS:

RELATIVE 60 l

100 1

3 EPDM HINIDITY (*) :

DACRON l

l l

l l

l l

CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE :

APPLICABLE l

l l

l l

l l

l l

l l

RADIATION 1.0E6 1.32E6 1

3 (rads) l l

l l

l

LOCATION: OUTSIDE CONTAINMENT l

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 2.

SPECIFICATION X4AJ32 3.

TEST REPORT 1083A & 1083D

o BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT

DOCLNENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: PIPING PENETRATION AREA OPERATING 1 YEAR 1 YEAR 2

3

ANALYSIS FILTRATION & EXHAUST TIME
COMPONENT: DAMPER TEMPERATURE 120 l

212 1

3 (oF)

NOTE 1

MANUFACTURER: QUALITY AIR DESIGN PRESSURE 13.2 - 17.7 A'INOSPHERIC 1

3 (psig)

(psia)

AGE-SENSITIVE MATERIALS:

RELATIVE 60 100 1

3 SILICONE RUBBER HINIDITY (*) :

POLYISOBUTYLENE-BUTYL RUBBER SILICONE RTV NEOPRENE CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE :

APPLICABLE :

RADIATION 2.0E6 3.8E6 l

1 3

(rads)

LOCATION: OUTSIDE CONTAI!NENT QUALIFIED 40 YEARS 40 YEARS 2

l 3

LIFE DOCINENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3 TABLE 3.ll.B.1-1 1.

NOT REQUIRED TO OPERATE DURING OR AFTER A DBA.

2.

SPECIFICATION X4AJ20 3.

TEST REPORT 83-387

O-BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROINENT l DOClMENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: PIPING PENETRATION AREA OPERATING 1 YEAR 1 YEAR 2

3 TEST &

FILTRATION & EXHAUST TIME ANALYSIS

COMPONENT: FILTER & EXHAUST UNIT TEMPERATURE 120 l

212 1

3 (aF)

MANUFACTURER: AMERICAN AIR FILTER PRESSURE
ATMOSPHERIC A1NOSPHERIC :

1 3

(psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 90

>90 1

3 MINERAL WOOL HINIDITY (*) :

GLASS CLOTH SILICONE RTV HYPALON CHEMICAL NOT l

NOT 1

3 NEOPRENE SPRAY APPLICABLE :

APPLICABLE TEFLON ASBESTOS CARBON RADIATION 2.0E5 5.0E5 1

3 (rads)

LOCATION: OUTSIDE CONTAI!NENT l

QUALIFIED 40 YEARS 40 YEARS 2

l 3

LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 2.

SPECIFICATION X4AJ07 3.

TEST REPORT NESE-329, NESE-832, & A-601-83-01

D BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT

DOCLNENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
  • SYSTEM: PLANT DEMINERALIZED WATER OPERATING 1 YEAR 1 YEAR 2

l 3

ANALYSIS TIME l

l l

l

COMPONENT: CHECK VALVE
TEMPERATURE 352 740 1

3 (oF)

MANUFACTURER: ROCKWELL PRESSURE 50 l

1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 l

GRAFOIL (NOTE 1)

HINIDITY (*) l l

ASBESTOS (NOTE 1)

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.8E8 1.0E11 1

3 l

l l

l (rads) l l

l l

l l

l l

l l

l l

l l

l l LOCATION: INSIDE CONTAINMENT l

QUALIFIED 40 YEARS 40 YEARS l

2 3

LIFE NOTES:

DOCINENTATION

REFERENCES:

l 1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE REPORT 46877-01.

i 2.

SPECIFICATION X4AR34A 3.

TEST REPORT (BECHTEL IDG) X4AR34A-75 l

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIRO!#fENT l DOCINENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: REACTOR COOLANT OPERATING 1 YEAR 1 YEAR 2

3 ANALYSIS TIME

COMPONENT: OTCK VALVE TEMPERATURE 352 740 1

3 (or)

MANUFACTURER: ROCKWELL PRESSURE 50 1000 1

3 (psig) i

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HINIDITY (*)

ASBESTOS (NOTE 1)

CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE RADIATION 1.8E8 1.0E11 1

3 (rads) l LOCATION: INSIDE CONTAIletENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE i

DOCUMENTATION

REFERENCES:

NOTES:

l 1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X4AR34A REPORT 46877-01.

3.

TEST REPORT (BECHTEL LOG) X4AR34A-75

)

BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1

~

EQUIPMENT DESCRIPTION ENVIROPMENT

DOCLMENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :
SYSTEM: SAFETY INJECTION OPERATING 1 YEAR 1 YEAR 2

3

ANALYSIS TIME
COMPONENT: CHECK VALVE TEMPERATURE 352 740 1

3 (o F)

MANUFACTURER: ROCKWELL PRESSURE 50 1000 1

3 l

l (psig) j

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HINIDITY (%) :

ASBESTOS (NOTE 1) i CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE :

APPLICABLE I

RADIATION 1.8E8 1.0E11 1

3 (rads) j

LOCATION: INSIDE CONTAIPMENT QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCLNENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X4AR34A REPORT 46877-01.

3.

TEST REPORT (BECHTEL LOG) X4AR34A-75

e BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIRONMENT

DOCUMENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL.
SYSTEM: SAFETY INJECTION OPERATING 1 YEAR 1 YEAR 2

3 ANALYSIS TIME

COMPONENT: CHECK VALVE
TEMPERATURE 352 740 1

3 (oF)

MANUFACTURER: DRESSER PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL (NOTE 1)

HUMIDITY (*)

GRAPHITE (NOTE 1)

ASBESTOS (NOTE 1)

CHEMICAL NOT l

NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.8E8 1.0 Ell 1

3 (rads)

LOCATION: INSIDE & OUTSIDE CONTAINMENT l QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.ll.B.1-1 1.

MATERIAL QUALIFICATION ESTABLISHED IN WYLE 2.

SPECIFICATION X4AR06 REPORT 46877-01.

3.

TEST REPORT (BECHTEL LOG) X4AR06-163

e BOP Mechanical Equipment Qualification (MEQ)

System Component Evaluation Work Sheet VOGTLE ELECTRIC GENERATING PLANT - UNIT 1 EQUIPMENT DESCRIPTION ENVIROPMENT l DOCLNENTATION :

QUAL.

REFERENCES METHOD PARAMETER

SPECIFICATION : QUALIFICATION : SPEC. : QUAL. :

SYSTEM: WASTE EVAPORATOR STEAM SUPPLY OPERATING 1 YEAR 1 YEAR 2

3 TEST &

TIME ANALYSIS

COMPONENT: CONTROL VALVE TEMPERATURE 352 740 1

3 l

(o r)

MANUFACTURER: ANCHOR DARLING PRESSURE 50 1000 1

3 (psig)

AGE-SENSITIVE MATERIALS:

RELATIVE 100 100 1

3 GRAFOIL HUMIDITY (*) :

GRAPHITE ASBESTOS / STAINLESS STEEL CHEMICAL NOT NOT 1

3 SPRAY APPLICABLE APPLICABLE :

RADIATION 1.0E9 1.0 Ell 1

3 (rads)

LOCATION: OUTSIDE CONTAIfMENT (NOTE 1)

QUALIFIED 40 YEARS 40 YEARS 2

3 LIFE DOCUMENTATION

REFERENCES:

NOTES:

1.

FSAR CHAPTER 3, TABLE 3.11.B.1-1 1.

WORST-CASE ENVIRO!NENTAL PARAMETERS CONSIDERED 2.

SPECIFICATION X4AR01 TO ALLOW FOR VALVE USE IN ANY PLANT LOCATION.

3.

TEST REPORT 46877-01