Rev 0 to Clarification of Impell Cth Design Verification Criteria/Methods for Resolution of Cygna Audit Concerns, Safety Margin Against Buckling Using American Inst of Steel Const Factored Allowables
ML20215B224
Person / Time
Site: Comanche Peak  Luminant icon.png
Issue date: 05/15/1987
From: Ashley G
ABB IMPELL CORP. (FORMERLY IMPELL CORP.)
To:
Shared Package
ML20215B058 List:
References
IM-P-004, IM-P-004-R00, IM-P-4, IM-P-4-R, NUDOCS 8706170262
Download: ML20215B224 (4)


Text

!

l l

J l

u l

l CLARIFICATION OF IMPELL CTH DESIGN VERIFICATION CRITERIA / METHODS FOR RESOLUTION OF CYGNA AUDIT CONCERNS i

I 1

Safety Margin Against Buckling Using AISC Factored Allowables j

-j 1

I Prepared for:

Texas Utilities Electric Company Prepared by:

Impe11 Corporation 0210-040/041 IM-P-004 Revision 0 Prepared by: d./?J.MA 4.w s s'//s-/g 7 Approved by: (( M J-/r-g7

/

8706170262 870699 PDR ADDCK O g5

'IM-P-004-CONCERN:

Increasing _AISC allowables for SSE loading conditions may.not.

provide a safety margin against buckling.

In particular,.a concern was raised for brace ' angles in longitudinal cable tray.

hanger supports.

8ACKGROUND:

For cable tray hanger. design verification, the project l applies a 1.6 increase factor to SSE allowables.

Per the CFSES FSAR, normal stresses are never allowed to. exceed 0.90 Fy. [1]

The ASME Code, Subsection NFl[2] Ifmits normal compressive'-

stress to two-thirds of the' critical buckling stress. _ The CPSES FSAR list of structures to be qualified per the requirements of ASME NF excludes cable tray support. systems.

Other nuclear codes examined.for guidance (e.g., ANSI /AISC N690 [3] allow'a 1.6 increase factor for SSE loading conditions without providing an additional limit as a. function; of the criti_ cal buckling stress.

DISCUSSIONS:

AISC Equations 1.5-1 and 1.5-2 are' used to compute axial

=comprssive allowables.

The ATSC equations providp/r.= Cc when-k' a factor of.

k /r = 0 to 1.92 at safety varying from 1,67 at compared to SSRC test data for steel columns [4].

Examination of SSRC test results shows that rol. led steel sections provide the indicated factors of: safety with a.high-degree at confidence since they have.less residual. stress than welded (built-up) sections.

Shorter columns have a lower inherent factor of safety in the AISC equations.

However, the strength of these columns is limited by yielding rather than buckling.

Regardless of column length, the use of a 1.6 allowable

)

increase factor under no circumstances allows SSE stresses to exceed the critical buckling stress.

This is illustated.in l

Figure 1 4

Angle brace.s act primarily as axial members.

E'nd connection is provided by relatively flexible gusset plates.

Flexural stresses in these members are typically not significant.

q 2/4 i

1

m-P-09e l

For angle braces design verified to date, the axial stress interaction ratio has been very small..The average SSE interaction ratio was shown to be less than 12% of the c

[

allowable, with an extreme value slightly exceeding one-half l

the allowable.

Tha actual factor of safety against buckling is therefore significantly greater than that provided by the allowable limits.

i CONCLUSION:

Project design verification procedures meet FSAR licensing committments.

4 Project design verification' procedures under no circumstances allow stresses to. exceed critical buckling stresses, l

Longitudinal angle braces design verified to date indicate axial stresses fall far below allowables, providing substantial margin against buckling,

(

REFERENCES:

1.

Impe11 Project Instruction PI-03, " Design Verification of Cable Tray Supports", Rev. 4 2.

ASME 1985 Subsection NF 3132.3.

3.

ANSI /AISC N690 1984.

4 Gaylord & Gaylord " Design of Steel Structures", 2nd Edition.

d 3/4