- TABLE l A - REG GUIDE 1.21 CALVERT CLIFFS NUCLEAR POWER PLANT EFFLUENT AND WASTE DISPOSAL SEMI-ANNUAL REPORT SECOND HALF - 1985 GASEOUS EFFLUENTS - SUMMATION OF ALL RELEASES 3rd 4th Est. Total A.
Fission and activation gases Units Quarter Quarter Error, %
1.
Total Release Ci 7.53E+02 2.09E+03 2.15E+0 !
2.
Average release rate for period uCi/sec 9.57E+ 01 2.66E+02 3.
Percent of tech. spec. limit (1) 1.65E-02 3.82E-02 4.
Percent of tech. spec. limit (2) 6.47E-03 1.51E-02 5.
Percent of tech. spec. limit (3) 2.36E-01 5.53E-01 6.
Percent ot tech. spec. limit (4) 4.72E-01 1.12E-00 7.
Percent of tech. spec. limit (5) 3.01E-01 7.95E-01 8.
Percent of tech. spec. limit (6) 6.01E-01 1.59E+00 B.
Iodines 1.
Total iodine - 131 Ci 4.53E-03 1.41E-02 1.84E+01 2.
Average release rate for period uCi/sec 5.83E-04 1.79E-03 3.
Percent of tech. spec. limit (7) 1.42E-03 4.37E-03 4.
Percent of tech. spec. limit (8) 1.47E-01 4.54E-01 3.
Percent of tech spec. limit (9) 7.37E-02 2.27E-01 C.
Particulates 1.
Particulates with half lives greater than 8 days Ci 9.82E-06 3.34E-05 1.84E+01 2.
Average release rate for period uCi/sec 1.23E-06 4.20E-06 3.
Percent of tech. spec. limit (7) 3.05E-06 1.04E-05 4.
Percent of tech. spec. limit (8) 3.16E-04 1.08E-03 5.
Percent of tech. spec. limit (9) 1.59E-04 5.40E-04 6.
Gross alpha radioactivity Ci 6.30E-07 1.19E-06 8612100270 860430 PDR ADOCK 03000317 R
PDR L_.
~--.
TABLE IC REG GUIDE I.21 (CONT'D) 4 CALVERT CLIFFS NUCLEAR POWER PLANT t
SECOND HALF - 1985 4
GASEOUS EFFLUENTS - GROUND LEVEL RELEASES Continuous Mode Batch Mode 3rd 4th 3rd 4th L.
Particulates Units Quarter
. Quarter Quarter Quarter 3
f' chromium
- 51 C1 7.24E-06 cobalt
- 58 Ci 4.46E-06 (1)
'I.37E-12
- 90 Cl 1.09E-06 (1)
(1) tin
- 113
'Ci
.(1) 2.96E-13 ceEum
- 134 Ci
-(l)
.I.llE-12 cesium
- 137 Ci 1.71E-06 1.51E-06
.(1)
(1)
= lanthium
- 140 C1 1.23E-05 (1) ~
(1) barium
- 140 C1 1.23E-05
~(1)
(1) i cerium
- 144-C1 2.56E-06 (1)
(1)
- Total For Period Cl 9.82E-06 3.34E-05 2.78E-12
. (1) ' Particulates in batch releases are accounted for with the main vent continuous particulate samplers when the release is made through the plant main vent.
E
.l
~
I l
t' 4
1
, TABLE 2A - REG GUIDE 1.21 CALVERT CLIFFS NUCLEAR POWER PLANT EFFLUENT AND WASTE DISPOSAL SEMI-ANNUAL REPORT SECOND HALF - 1985 LIQUID EFFLUENTS -SUMMATION OF ALL RELEASES 3rd 4th Est. Total A.
Fission and activation products Units Quarter Quarter Error, %
1.
Total Release (not including tritium, gases, alpha)
Ci 2.03E-01 1.23E+00 2.16E+01 2.
Average diluted concentration during period uCi/mi 3.60E-10 2.07E-09 3.
Percent of tech. spec. limit (1) 3.60E-01 2.07E+00 4.
Percent of tech. spec. limit (2) 9.12E-01 6.24E+00 5.
Percent of tech. spec. limit (3) 8.23E-02 3.60E-01 6.
Percent of tech. spec. limit (4) 4.56E-01 3.12E+00 7.
Percent of tech. spec. limit (5) 4.1IE-02 1.80E-01 1
B.
Tritium 1.
Total Release Ci 9.58E+01 9.12E+01 1.81E+01 2.
Average diluted concentration during period uCi/ml I,62E-07 1.53E-07 3.
Percent of applicable limit 5.40E-03 5.10E-03 C.
Dissolved and entrained gases 1.
Total Release Ci 4.41E-02 1.36E-01 2.00E+01 2.
Average diluted concentration during period uCi/ml 7.47E-l l 2.29E-10
e TABLE 2B REG GUIDE 1.21 CALVERT CLIFFS NUCLEAR POWER PLANT EFFLUENT AND WASTE DISPOSAL SEMI-ANNUAL REPORT SECOND HALF - 1985 LIQUID EFFLUENTS Continuous Mode (1)
Batch Mode 3rd 4th 3rd 4th Nuclides Released Units Quarter Quarter Quarter Quarter 1.21E-03 sodium
- 24 Cl 0
0 chromium
- 51 Ci 0
0 6.47E-03 1.25E-01 manganese
- 54 Ci 0
0 5.31E-03 1.29E-02 cobalt
- 58 Cl 0
0 4.50E-02 3.30E-01 cobalt
- 60 Cl 0
0 1.87E-02 5.81E-02 strontium
- 89
.Ci 0
0 8.67E-03 2.45E-03 strontium
- 90 Cl 0
0 3.00E-04 7.27E-04 niobium
- 95 Cl 0
0 1.42E-02 5.05E-02 zirconium
- 95 Ci 0
0 6.45E-03 1.49E-02 niobium
- 97 Ci 0
0 2.61E-04 2.15E-03 1.20E-03 ruthenium
- 103 Ci 0
0 silver
- 110m Cl 0
0 2.34E-03 1.46E-01 2.46E-03 tin
- 113 Ci 0
0 antimony
- 122 Ci 0
0 2.08E-04 1.09E-03 1.07E-02 cntimony
- 124 Ci 0
0 antimony
- 125 Ci 0
0 1.88E-02 1.06E-01 indine
- 131 Ci 0
0 2.19E-02 9.69E-02 1.26E-03 tsilurium
- 132 Ci 0
0 iodine
- 133 Ci 0
0 5.62E-03 4.84E-02 l
t
r
? TABLE 2B REG GUIDE 1.21 (CONT'D)
CALVERT CLIFFS NUCLEAR POWER PLANT EFFLUENT AND WASTE DISPOSAL SEMI-ANNUAL REPORT SECOND HALF - 1985 LIQUID EFFLUENTS Continuous Mode (1)
Batch Mode 3rd 4th 3rd 4th Nuclides Released Units Quarter Quarter Quarter Quarter iodine
- 132 Ci 0
0 8.25E-04 t chnicium
- 99m Cl 0
0 6.87E-04 lodine
- 124 Ci 0
0 1.31 E-03 casium
- 134 Ci 0
0 1.65E-02 7.40E-02 iodine
- 135 Ci 0
0 3.42E-03 casium
- 136 Ci 0
0 9.60E-04 c sium
- 137 Ci 0
0 3.20E-02 1.36E-01 barium
- 140 Ci 0
0 4.38E-03 lanthanum -
- 140 Ci 0
0 4.43E-03 cerium
- 144 Ci 0
0 5.00E-04 Total For Period Ci 0
0 2.12E-01 1.23E+00
=-,--.e
, TABLE 2B REG GUIDE 1.21 (CONT'D)
CALVERT CLIFFS NUCLEAR POWER PLANT EFFLUENT AND WASTE DISPOSAL SEMI-ANNUAL REPORT SECOND HALF - 1985 LIQUID EFFLUENTS Continuous Mode (1)
Batch Mode 3rd 4th 3rd 4th Nuclides Released Units Quarter Quarter Quarter Quarter Xenon
- 133 Ci 0
0 4.28E-02 1.22E-01 Xenon
- 135 Ci 0
0 1.29E-03 7.54E-03 Xenon
- 135m Cl 0
0 5.59E-03 Xenon 133 m Ci 0
0 9.19E Total For Period Ci 0
0 4.41 E-02 1.36E-01
.(1)
There were no continuous liquid releases during the 3rd and 4th quarters.
4