APPENDIX A NOTICE OF VIOLATION Philadelphia Electric Company Docket No. 50-353 Limerick Unit 2 License No. CPPR-107 A

As a result of the inspection conducted on March 30, 1987 to May 10, 1987, and in accordance with 10 CFR 2, Appendix C (Enforcement Policy 1987), the following violation was identified.

10 CFR 50, Appendix B Criterion XIII and the Limerick Preliminary Safety Analysis Report Appendix D.4.9.1 require that measures be established to prevent degradation of the quality of equipment below that required by the applicable equipment specifications.

Further, it is required that written instructions be prepared to govern the preservation of equipment prior to and after installation.

Contrary to the above, on March 30, 1987, no written procedure existed to provide requirements for relief valve protection. The lack of adequate protection resulted in a broken lockwire on the blowdown adjustment ring access plugs on relief valve PSV-51-2F055A.

This is a Severity Level V Violation (Supplement II).

Pursuant to the provision of 10 CFR 2.201, Philadelphia Electric Company is hereby required to submit to this office within 30 days of the date of the letter transmitting this Notice, a written statement of explanation in reply to the violations to include:

(1) the corrective steps which have been taken and the results achieved; (2) the corrective steps which will be taken to avoid further violations; and (3) the date when full compliance will be achieved. Where good cause is shown, consideration will be given to extending time.

4 1

8706040183 870524 PDR ADOCK 05000353 G

PDR

.