g 1

One First Nanonal Plaza. ChcaOo, lHinois

\\' V" / Address Reply to: Post Othce Box 767 Chca00. luinois 60000 0767 May 28, 1987 Mr. Thomas E. Murley, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Comunission Washington, DC 20555 Subiect: Quad Cities Station Units 1 and 2 "Drywell Pressure Instrumentation Regulatory Guide 1.97 Commitment" i

NRC Docket Nos. 50-254 and 50-265 4

1

Reference:

Letter from J.R. Wojnarowski to H.R.

Denton dated October 6, 1986.

(

Dear Mr. Marley:

The purpose of this letter is to provide you and your staff with a current status of Reg. Guide 1.97 item A.3, Drywell Pressure Instrumentation.

The work to be performed as part of this commitment involves the replacement of scales, recalibration of corresponding instruments and EQ qualification of transmitters by_ similarity. There are no hardware changes involved. Our most recent status of Reg. Guide 1.97 commitments was provided in the above referenced letter.

The new recorder scale has been received at the Station which should permit the recalibration of necessary instruments by June 15, 1987.

However, since this is a post-accident monitoring system as specified by the Technical Specifications, the final change cannot be made until a Technical Specification change is prepared and approved. The change requires a revision to Table 3.2-4 of.DPR-30.

The Technical Specification presently specifies a range of 0-75 psig for this instrument. The proposed change necessary to implement the recalibration is -5 to 70 psig.

l t

p DO P

go $

r b

~

r.

T.E. Murley May 28, 1987 1

The proposed Tech Spec change is currently being prepared by Quad Cities Station and should be ready for submittal to you-c staff for their review by July 1, 1987. We will be prepared to implement this Tech Spec change following your staff's approval and issuance of it.

please direct any questions you may have regarding this matter to this office.

Very truly yours, m

I. M. J n on Nuclear Licensi Administrator 1m cc:

A. Bert Davis - RIII Resident Inspector - Quad Cities 3132K

-