ML20214M221

From kanterella
Jump to navigation Jump to search
Forwards Insp Rept 99901020/87-01 on 870120-23 & Notice of Violation.Concern Re Licensees Fire Seal Documentation Not Representing as-installed Configurations Discussed.Response to Notice of Violation Requested within 30 Days
ML20214M221
Person / Time
Issue date: 05/22/1987
From: Merschoff E
Office of Nuclear Reactor Regulation
To: Charles Brown
BRAND INDUSTRIAL SERVICES, INC. (BISCO)
Shared Package
ML20214M225 List:
References
REF-PT21-87, REF-QA-99901020 NUDOCS 8706010238
Download: ML20214M221 (2)


Text

c'~

pueg%

UNITED STATES 8

NUCLEAR REGULATORY COMMISSION y,

wasumorow.o.c. noses

. \\,.,,,,/

May 22, 1987 Locket No. 99901C20/87-01 Brand Industrial Services, Incorporated ATTN: Mr. C. W. Brown, President Construction Group 1420 Renaissance Drive Park Ridge, Illinois 60068 Gentlemen:

This refers to the inspection conducted by J. J. petrosino of this office on January 20-23, 1987, of yeur facility at Park Ridge, Illinois, a follow-up NRC inspection at the V.C. Sununer nuclear generating station on February 25-27, 1987, and to the discussions of our findings with you and members of your staff at the conclusion of the inspection.

The purpose of this inspection was to obtain generic technical and testing infonnation concerning silicone foam fire protecticn applications and to evaluate the implementation of your QA program. Areas examined during the inspection and our findings are discussed in the enclosed report. Within these areas, the inspection consisted of an examination of procedures and representative records, interviews with personnel,.and observations by the inspector. The specific findings and references to the pertinent requirements are identified in the enclosures to this letter.

The most significant issue that was identified concerns the potential for nuclear plant licensees to have fire barrier penetration seal testing documen-tation that is not representative of the particular as-installed penetration seal configurations. Some as-installed penetration seals may not be adequate, because its installed configuration exceeds the documented qualification test data parameters for specific characteristics. _ Consequently, some NRC licensees 2

may not be able to provide reasonable assurance that the effects of a fire are limited to discrete fire areas, and that one division of safe-shutdown related systems remains free of fire damage.

The enclosed Notice of Violation is sent to you pursuant to the provisions of Section 206 of the Energy Reorganization Act of 1974. -You are required to submit to this office within 30 days from the date of this letter a written statement containing:

(1) a description of steps that have been or will be 4

taken to correct these items; (2) a description of steps that have been or will be taken to prevent recurrence; and (3) the dates your corrective actions and. preventive measures were or will be completed.

I f

8706010238 870522 PDR GA999 EECBRAI l

l e

99901020 PDR l

e Brand Industrial Services, Inc. May 22, 198/

The responses requested by this letter are not subject to the clearance procedures of the Office of Managerrent and Budget as required by the Paperwork Reduction Act of 1980, FL 96-511.

In accordance with 10 CFR 2.790 of the Coninission's regulations, a copy of this letter and the enclosed inspection report will be placed in the NRC's Public Document Room.

Should you have any questions concerning this inspection, we will be pleased to discuss them with you.

Sincerely, d

Ellis W. Merschof,f cting Chief Vendor Inspection,5 ranch Division of React'or Inspection and Safeguards Office of Nuclear Reactor Regulation f

Enclosures:

1.

Appendix A-Notice of Violation 2.

Appendix B-Inspection Report No. 99901020/87-01 cc: Mr. J. Carney, Vice President American Nuclear Insurers The Exchange:

Suite 270 270 Farmington Avenue Fannington, Connecticut 06032 Mr. C. A. McNeill, Jr.

Vice President - Nuclear Public Service Electric and Gas Company Post Office Box 236 Hancocks Bridge, New Jersey 08038 South Carolina Electric & Gas Company ATTN: Mr. D. A. Nauman Vice President, Nuclear Operations Post Office Box 764 (Mail Code 167)

Columbia, South Carolina 29218

)

1 l