Text
cu fi==-IA i
~.
'Af M
2NRC-7-116 (412)393 7546 Beawr Va No. 2 Unit Project Organiption Telecopy (412) 393-7889 iiay 12, 1987 P.O. Box 328 shippingport. PA 15o77 United States Nuclear Regulatory Commission Region I 631 Park Avenue King of Prussia, PA 19406 ATTENTION: Mr. William T. Russell Administrator
SUBJECT:
Beaver Valley Power Station - Unit No. 2 Docket No. 50-412 No Control Room Indicating Lights Provided for HVAC Test Switches Potential Significant Deficiency Report 87-12 Gentlemen:
This Potentially Reportable Significant Deficiency Report is being submitted pursuant to the requirements of 10CFR50.55(e).
It is anticipated that no additional reports will be required.
DUQUESNE LIGHT COMPANY By
-/
p.fJ Karey
(/ 3 SeniorV(it'ePresident LMR/ijr NRC/LMR/SDR/8712 Attachment AR/NAR cc: Mr. P. Tam, Project Manager (w/a)
Mr. J. M. Taylor, Director (3) (w/a)
Mr. J. Beall, Sr. Resident Inspector (w/a)
Mr. L. Prividy, hRC Resident Inspector (w/a)
INP0 Records Center (w/a)
NRC Document Control Desk (w/a) 8705270321 870512 PDR ADOCK 05000412 q
S PDR.;
9 f\\
=
e ATTACHMENT-m.
i 1.
Summary Test switches are provided in Unit 2 HVAC circuits that could render safe-ty. signals inoperative.
No indication is provided in the Control Room 1
(CR) to warn operators of' inoperative. status.
l 2.
Immediate Action Taken Advance Change Notice ACN 0-0068 was written to remove test switch contacts from the affected circuits.
Mr. L. M. Rabenau, Lead Compliance Engineer, Beaver Valley Power Station Unit No. 2, notified Mr. D.
Limroth, NRC Region I, of this concern on April 14, 1987.
3.
Descrpition of Deficiency 2
The test switches in question could render circuits HVCAP, HVCBP, CESAM,.
and CESBM inoperative, which in turn could cause the following equipment to be inoperative:
a.
Unit 1
- 1) CR Emergency Bottled Air System SOVs VS103A1, A2, B1, B2, C1, C2, D1, 02, El and E2.
- 2) CR Fan Intake Dampers VS-D-40-1A & IB
- 3) CR Fan Exhaust Dampers VS-D-40-1C & 1D b.
Unit 2
- 1) CR Air Supply Fans 2HVC*FN241-1A & 18
- 2) CR Air Intake Dampers 2HVC*M00201A & B
- 3) CR Air Exhaust Dampers 2HVC*M00201C & D -
4.
Analysis of Safety Implication Since no indication is provided in the CR of the inoperable status, fail-ure of various safety functions could go unnoticed.
This constitutes a deficiency in plant design which, were it to have remained uncorrected, could have adversely affected _ the safe operation of the plant.
5.
Corrective Action to Resolve the-Deficiency
)
The test switches fer circuits HVCAP, HVCBP, CESAM,. and CESBM have been removed to preclude the possibilty of inadvertant operationiof these switches.
6.
Additional Report No additional reports are expected.
-