ML20214G806

From kanterella
Jump to navigation Jump to search
Submits Evaluation of Util Alternate Position B1 to ANSI N-101.4-1972 Re QA for Protective Coatings.Class 1 Svc Level Applies Only to Sys & Components Inside Primary Containment Essential to Prevent or Mitigate Consequences of Accidents
ML20214G806
Person / Time
Site: Columbia 
Issue date: 08/11/1977
From: Chipman G
Office of Nuclear Reactor Regulation
To: Gilray J
Office of Nuclear Reactor Regulation
References
CON-WNP-0186, CON-WNP-186 NUDOCS 8605220527
Download: ML20214G806 (1)


Text

.

q

, hCkCLL blLC-7; c y p[ "

'~'

g o.@

g fo-39 7 AUG 111877 M940PANDLN FOR: John W. Gilray, Quality Assurance Branch, DPM FRCM:

Gordon L. Chipman, Jr., Section Leader, Section A, Accident Analysis Branch, DSE

SUBJECT:

WPFSS'S ALTERNATES TO ANSI N-101.4-1972 As you requested, we have evaluated the WPPSS's alternate positions to ANSI N-101.4-1972, Quality Assurance for Protective Coatings Applied to Nuclear Facilities.

With regards to WPPSS's alternate position B1 which states that not all quality Class I equiprent will be coated according to this standard, the AAB position is that, Class I service level applies only to those systens and components inside the primary containment of a nuclear facility, which are essential (1) to prevent postulated accidents which cculd affect public health and safety, or (2) to mitigate the conse-quences of these accidents.

The other alternate positions are concerned with quality assurance, and thus fall outside of AAB's review responsibilities.

This evaluation was performed by J. Wing Section A Accident Analysis Branch.

fS\\

Gordon L. Chipman, Jr., Section Leader Section A Accident Analysis Branch Division of Site Safety and Environmental Analysis cc:

D. Bunch Distribution:

l G. Chipnan Central Files l

J. Wing NRR Rdg. File i

DSE Rdg. File i

AAB Rdg. File l

AAB Files 9603220527 770e11

?g d PDR ADCCK 0s000397 I

A PDR i

DSE $NfAAB.DSE:SAtAAB y

l x27917 J.Wiiig:dr

&.Chipm P' _., _.

~

w

...@.i.L-77 kJ/-77

..n>

l NEC ICRM 318 (S741 NT04 0240 W u. s. eove,messur em= vine orreces sete ow '

' ^ -