. r 30-y'54/@7-e6 B.--2z-cocxE.TE0 d[d Pd uss.w PROCEDURE TRACKING SHEET 1
g7 efa 31 All:29
- B-\\O c ro;- -
PROCEDURE NO.
C "; ' ~
REVISION k:
- M-90 INTERIM: \\ A -@
CECO INTERIM APPROVAL
- Effective.
FINAL:
S & L/ CECO FINAL APPROVAL - k l-l9 -9
~
1
- Effective e
- IMPLEMENTATION DATE
-IIk-9 SUPERCEDED BY REVISION b APPROVED D SE Inter inal)
- Effective -
- Effective Date - The date Q.C. received approval.
- Implementation Date - The effective date plus fif teen working days.
~
8705200655 860610 ao;hgJAT{].dgqNLY PDR ADUCK 05000456 c
in u
, q, ';;,
SARGENTatuMOV QUALITY CONTROL PROCEDURES REVIEW REPORT hlien.t Commonwealth Edison Comp'any Project Braidwood Contractor L. K. Comstock and -
Project No. 4683-05 Unit 1&2 Company, Inc.
S&L Specification No. L-2790 PROCEDURE TITLE Storage, Issue and Control of Weldino Material Procedure No.
4.3.10 Rev.
E Date 9/27/84 ELXNHEE44 l
l Reviewed & Accepted l
l Revise as noted and resubmit.
Hold fabrication.
Revise as noted and resubmit.
Results do not meet specifi-lX l Contractor can proceed based
' cation requircraents.
on making revisions noted CDMMENTS:
Paragraph 3.3.1.1 in the procedure shall state that portable ovens will be maintained at 2500F minimum.
D Distribution:
Reviewed by E.
V. Andruszkiewicz SN.TM.7C+1%< Le.W1X333X Dat.e, November 8, 1984 l
Y
't *
"''y
~ ' '
i QC Form 1022 R8 l
L b COMSTOCK & COMPANY. INC.
y....
QA SECT 4.3.10 STORAGE, ISSUE AND CONTROL 0F WELOING MATERIAL PAGE REV/0 ATE I
E - 09/27/84 CARGENT & LUNDY E - 09/27/84 4;viJr. r,S %C f f D AND Af 1W3.AIT.
2* STUUli750".[*2[ifyF E - 09/27/84 3
$.*. E7.7.c7d'. "vl. le*0' EElEr!**
E - 09/27/84 4
f*-.0.*-KOSIK
[ff BY OATE E_
5 fo$ M N O ("o.'/hf3J$
J Form #57 E - 09/27/84 Form #63 0 - 08/21/04 Attachment 'A' E - 09/27/84 APPROVALS:
L. K. COMSTCCK'AND COMPANY, INC. d MORC OATUB-C-7 ~
UALITY CONTROL MANAGER
- f o.<a L. K.,COMSTOCK AND COMPANY, INC.
DATE /o -/c -t'f PROJECT MANAGER l
L. K. COMSTOCK AND COMPANY, INC.
A O-1 DATE 0-it-$4/
PROJECTEN@NEER heb OATE/o[/5 89
~'
L. K. COMSTOCK AND COMPANY, INC.
_._ f QA ENGINEER l
REV. E (09/27/84) l EFFECTIVE DATE:
10/19/84 l
00851
\\fD
~
t3 u
iniivh unL1 I
/
l
~..
L K.'CORSTOCK & CORAPANY,INC.
GA SECT 4.3.10
- STORAGE, ISSUE AND CONTROL OF WELOING MATERIAL REV/DATE PA_Q,(,
1 E - 09/27/84 l.,
I~'.'h[,!Y?!LUNO.'R E - 09/27/84 2
- 2. a:: :.. c.,,,. 1 'l u >. 2.,.,w u,,,_
.:, :,,"l_
- a...[ 2' "'l.:l - '"o E - 09/27/84
""mc[..e.;,Z';'g'..e,,,,..,,,
3 C ~ O2U*
"Eh=Q.sn3________ }4
/
E - 09/27/84 5
scre N $. k }04rcjf; Form #57
~
E - 09/27/84 Form #63 0 - 08/21/84,
Attachment 'A' E - 09/27/84 APPROVALS:
L. K. COMSTOCK AND COMPANY, INC.
/19d4 OATE/#-/2-k UALITY CONT OL MANAGER Me f L. K. COMSTOCK AND COMPANY, INC.
DATE /d-/a -ff PROJECT MANAGER 0 ATE 0-it 4*/
1 L. K. COMSTOCK AND COMPANY, INC.
O-PROJEtTEN@NlER DATE/d//5'/89 L. K. COMSTOCK AND COMPANY, INC.
127 exeA QA ENGINEER REV. E (09/27/84) 00851 EFFECTIVE DATE:
10/19/84 ER NFORMATE':ND QASI
L. K.COMSTOCK & COMPANY,INC.
BRAIDWOOD 4.3.10 QA SECT 4.3.10 STORAGE, ISSUE AND CONTROL
~
OF WELDING MATERIAL i
1.0 REFERENCE 1.1 American Welding Society (AWS D1.1-75) 1.2 An Approved AWS Filler Metal Specification 1.3 L. K. Comstock, Procedure 4.9.1 2.0 PURPOSE / SCOPE 2.1 To provide instruction for handling, storing and issuing weld filler metal.
2.2 To prevent use of unauthorized material for construction.
3.0 PROCEDURE 3.1 Classification of all weld filler metal (Electrodes) will be in accordance with the applicable American Welding Society Filler Metal Specifications.
3.2 Electrode Storage 3.2.1 Welding electrodes will be stored by Phillips Getschow Co. in T
hermatically sealed containers.
Oy The L. K. Comstock warehouse foreman will withdraw welding electrodes (in hermetically sealed containers) from Phillips Getschow Co. using the Phillips Getschow Co. Stores Request.
27.
The stores request form will be filled out by Phillips Getschow
='7']
personnel at the time of request for the electrodes and signed Q
by L. K.'Comstock warehouse foreman.
N A cop'/ of the stores request form will be retained by the L. K.
]
Comstock warehouse foreman and given to the LKC QC Inspector w
who shall verify that there is a released MRR # and verify with M}
CECO QA that certs are acceptable. Verification shall also include a check that the heat number is identified.
(C When welding electrodes are received directly by Comstock or a g' ll requisitioned from site contractors other than P.G. Co., a copy of the MRR and/or applicable requisition will be placed in the Q
stores request file.
The MRR and/or requisition must show g
traceability from heat number to MRR number. The information will be entered in a log cross referencing heat number, MRR I
number and description.
No rod will be released to the field M
until the MRR has been released (interim status as a minimum) by CECO QA.
- RE8ARED APPROVED m E v a SE D TITLC ORIG.OATE REVISION PAGE E
PROCEDURE 02/01/78 09/27/84 1 of 5 ECE IFD ATS aas.
=,
]
C K. COMSTOCK ai COMPANY, INC.
BRAIDWOOD 4.3.10 QASECT e
~
3.0 PROCtHRE - continued 3.2.2 Weld.ing electrodes received by L. K. Comstock will be in the following containers:
3.2.2.1 E308/E309, E7018 - Hermetically sealed containers.
3.2.2.2 E6013, E6010 - Clean dry containers.
3.2.3 The electrodes will be transferred to L. K. Comstock warehouse and/or tool crib for storage. When sealed containers are opened, the electrode holder end of the rod will be painted white for identification, 3.2.3.1 E308/E309 and E7018 electrodes will be placed in temperature controlled electrode storage ovens.
3.2.3.2 E6010 and E6013 electrodes will be placed in separate l
clean, dry containers.
3.2.4 Electrodes of dissimilar chemical composition shall not be kept in the same storage oven.
3.2.4.1 All Tool Crib rod ovens and containers will be l
labeled to indicate the classification and heat number of electrodes they contain.
i 3.2.5 The L. K. Comstock warehouse foreman / tool crib attendant shall l
assure that the following electrode storage oven tempert.tures and conditions are utilized by production.
3.2.5.1 TOOL CRIS OVEN E7018/E308/E309 250' to 450*F Q
3.2.5.2 The temperature of the tool crib storage ovens shall AAa be monitored on a daily basis by the LKC warehouse
""M foreman or tool crib attendant for the purpose of setting the oven thermostat. A thermometer shall be i
u.mg placed inside the storage oven in a conspicuous place 83
- and the temperature shall be recorded on LKC QC Form i
Q
,63.
Form 63 shall be located adjacent to the storage i
0 oven in open view. Form 63 shall be forwarded to
.8#
L. K. Con. stock QC at the end of each month for "m'M filing, (excluding Saturdays, Sundays and Holidays).
=*
i 3.2.5.3 E308/E309 and E7018 electrodes may be removed from i
Z the portable ovens during construction activity not i
to exceed a period of four hours.
I O
i 3
3.2.5.3.1 Electrodes that have been removed from ovens more than four (4) hours shall be redried as described below or disposed of.
I
- E*AREO A**RovtO REvtSED Tt f t.E OplG.DATE REVISION PAGE E
PROCEDURE l
ECE IFD ATS 02/01/78 09/27/84 2 of 5 Q A S4
L. K. COMSTOCK O COMPANY, INC.,
BRAIDWOOD 4.3.10 QA SECT 3.0 PROCEDURE - continued 3.2.5.3.2 Redrying shall consist of heating the electrodes for at least two (2) hours at 450*F to 500*F for electrodes conforming to AWS AS.1, or for at least one (1) hour at 700*F to 800*F for electrodes conforming to AWS A5.5.
3.2.5.4 E6010. E6013 electrodes will be maintained at room temperature in separate, clean dry containers.
3.2.5.5 Electrodes that show any ofsthe following conditions will be bent and discarded. '
3.2.5.5.1 Excessive moisture.
3.2.5.5.2 Coating blisters.
3.2.5.5.3 Direct contact with water.
3.2.5.5.4 Cracked coating.
]
3.3 Issuance of Material 3.3.1 The L. K Comstock warehouse foreman or tool crib attendant shall issue electrodes in clean dry containers for transporting to work areas.
I 3.3.1.1 E7018 shall be placed in designated portable rod
~
- ",*")
ovens to maintain heating requirements at a minimum Q'3 range setting of 175'F.
,,5ed 3.3.1.2 E309 shall be placed in desinnated portable ovens to
~
maintain heating requirements of a minimum range mr...
setting of 175'F
' ".]J 3.3.1.3 Portable rod ovens shall be energized to maintain the required heat levels.
,,y
M 3.3.1.4 Electrodes of the same type and size but with
.;;;.n different heat numbers shall be segregated in the rod y;a crib to insure traceability of rod is not lost.
' ),
3.3.2 A Filler Metal Withdrawal Authorization Fom (Form #57) will be m
required for each welder. A new Form 57 will be required for a,i',
each day's welding activity even if the activity is continued Z
from a previous day's work.
O 3.3.3 Upon receipt of a Filler Metal Withdrawal Authorization Form Z
(Form #57), the L. K. Comstock warehouse foreman or electrode attendant will prepare an electrode oven or clean dry
,'s container, as applicable, with the required electrode and store the oven PRE *A AEO AppRO V E D AEvaSED TITLE OmtG.OATE REVi$lON PAGE E
ECE IFD ATS PROCEDURE 02/01/78 09/27/84 3 of 5 0454
LiK. COMSTOCK 8: COMPANY, INC.
BRAIDWOOD 4.3.10 QA SECT 3-3.0 PROCEDURE - continued or container in the crib until it is requested by the welder.
The ovens containing welding electrodes shall be kept heated per the requirements of Paragraph 3.2.5.1.
The Filler Metal Withdrawal Tab shall be completed in accordance with the
~
attached Filler Metal Withdrawal Instructions.
(Attachment A) 3.3.3.1 The tool crib attendant shall not issue any E309 or E7018 electrodes from the storage ovens that have not been maintained as specified per Paragraph 3.2.5.1 of this procedure.
3.3.3.2 Upon the presentation of a valid welder 10 card by the certified welder specified on the Forin 57, the warehouse foreman or electrode crib attendant shall issue the oven or container and electrodes to the welder along with the Form 57.
3.3.3.3 During the days welding activities, the welder shall enter the WIR Number on the Filler Metal Withdrawal Tab for each installation welded.
(Reference Attachment A).
3.3.4 Upon completion of the days welding activities, the welder shall return the electrode ovens, electrode containers and all electrodes along with the Form #57 with the foreman's review and signature to the electrode crib.
3.3.4.1 At the end of each working shift the LKC warehouse foreman or electrode crib attendant shall verify that all electrode ovens have been returned. Any ovens not returned shall be noted and QC shall be notified.
3.3.4.2 The crib attendant shall remove any unused weld rod from the portable oven or containers and return it to the appropriate location.
3.4 Control of Weld Stubs and Spoiled Electrodes 3.4.1 Each welder shall carry a stub pail for spent or spoiled electrodes and shall be near the work in progress.
3.4.2 The welder shall deposit all discarded stubs (unused portion of electrodes and spoiled rod) in the stub pail provided.
3.4.3 The welder shall discard any spoiled electrodes, using the stub _,
pail provided. All electrodes which are soiled, wet, contaminated, oil-impregnated or unidentifiable shall be considered " spoiled". Electrodes which have been " spoiled' shall be bent and discarded.
" Spoiled" electrodes shall not be _
" ' ~ ' ~
FOR NORMAIl0N ONLY eg gea n g D AP*MovtO REVISED TITLE O mtG. O ATE FIEVISION PAGE E
JAH IFD ATS PROCEDURE 02/01/78 09/27/84 4 of 5 QASA
- z L.!
K. COMSTOCK Q COMPANY, INC.
BRAIDWOOD 4.3.10 Q sic 7 3.0 PROCEDURE - continued 3.4.4 Each welder shall empty his pail daily at the end of his shift or a't the completion of the welding activity. All stubs and spoiled electrodes shall be deposited in a locked, uniquely identified barrel. Stub pails shall be used for no other purpose.
3.4.4.1 Each foreman shall walk-down his inmediate work area at the end of each shif t or at the completion of welding activity to verify that no weld electrodes, stubs, or spoiled electrodes have been lef t out in x,
open. All stub pails shall be locked up in gang boxes or deposited in the crib (s) during the off time.
~
3.4.5 Under no' circumstances shall any filler metal be removed from stub pails or the designated receptacle for use in welding.
Such activity shall subject the welder to disciplinary action, as deemed appropriate by the LKC Project Manager.
NOTE:
Each welder must consider the work to be performed when withdrawing electrodes from the portable oven, in order to reduce waste of electrodes and to provide bett' r control of weld stubs and spoiled material.
e i
Use of low-hydrogen electrodes in conjunction with hot storage will minimize problems of hydrogen cracking. Observation of procedures will contribute c
substantially to weld quality by eliminating hydrogen, which may be introduced by water, water vapor or oil. Welders are encouraged to minimize the time between the withdrawal of electrodes from heated ovens and their use in welding.
4.0 TEST E0VIPMENT 4.1 None 5.0 FORMS 5.1 Filler Metal Withdrawal Instructions - Attachment A 5.2 Form 57 - Filler Metal Withdrawal Tab 5.3 Form 63 - Electrode Storage Oven Temperature Log FOR INFORMAiiON ORY 6.0 SPECIAL INSTRUCTIONS 6.1 G. K. Newberg personnel shall be responsible for the painting, marking, securing, placing, and emptying of electrode disposal barrels.
.aceanco annovio acvisto nrte calc.cATc RE ISION PAGE JAll IFD ATS PROCEDURE 02/01/78 09/27/84 5 of 5 0454
, L. lb COMBTOCK & COMPANY,1NC.
BRAIDWOOD 4.3.10 QA SECT WELO FILLER METAL WITH0RAWAL TAB FORM #57 ELECTRODE WELDERS NAME b
SYMBOL NO.
b OVEN NO. b
.....................=..........................................................
M R METAL TYPE QUANTITY ISSUE 0 HEAT NO.
QUANTITY RETURNED b
b
- E6013, 18 Other (61 (ih
~
v v
v RETURNED ELECTRODES b
OATE b RECEIVED BY DATE O O.
ISSUED BY WIR NUMBERS:
a REMARKS:
h h
FOREMAN REVIEW: Signature h
Date I
l Rev. E (09/27/84)
.l l
FOR INFOM1 ail 0h OLY QAS 1
,. _ _. _. _ ~____ _
a L. K. COMSTOCK & COMPANY. INC.
Braidwood 4.3.10 QASECT l
OVEN #
OAILY 1.0G MONTH YEAR i
ELECTRODE STORAGE OVEN TEMPERATURE DATE TEMPERATURE THERMOMETER INITIAL 1
2 3
4 5
7 R
9 10 11 12 13 14 16 16 17 la 19 2G 21 22 23 24
' YRi \\/!C"M 2s 2s N2 dE 27 i
2R
' ' 'i' h' 29 g
i
- r. r.
i
,$, 7 f*7,;:
1 - t * ? t'i !! j Q)?1 \\ /
I't 3 '
I
- l; ; +
'r.3 Q U d U !5 L l 31 PREPA RE D A88mov tD REvlSED flTLE O msg. D ATE REVISION FORM g RAB ITD DWB 05/01/80 D
63 Pnoctouns 08/21/84
L.
CORNTOCK & COMPANY,INC.
BRAIDWOOD 4 3.10 QA SECT ATTACHMENT A 1.
Welder to print name.
l 2.
Welder to enter assigned symbol no.
3.
Welder to enter portable oven no.
4.
Welder to circle filler metal type and size. Filler metal, other than E6013 or E7018 will be noted in the appropriate section.
5.
Welder to list quantity of filler metal to be issued.
6.
Electrode crib attendant to enter heat no. of filler metal issued.
7.
Electrode crib attendant to sign and date.
8.
Welder to enter the WIR Number on the Filler Metal Withdrawal Tab for each Safety Category I Area installation welded during the course of the day. When working on Non-Safety Category II Area installations, the welder shall enter non-safety related in this section.
9.
If no welding is performed, this shall be stated in the Remarks section. All remarks shall be initialed and dated indicating who made the entry.
- 10. The welder's foreman shall sign and date,to verify the completed weld Filler Metal Withdrawal Tab was completed as define'd by these instruations and the information is accurate and legible with all corrections made properly.
- 11. Electrode crib attendant shall indicate amount of electrodes returned and sign and date.
for concurrence and filing.
1 i
Rey. E (09/27/84) l QASI m
w-y y