gg/
f -f
' [/ g y f'CAZENT O LUNDY
[
f6 ENCINEEQO L-2790
- * * ^ *
- And. 48, 11-04-85 Making all external electrical connections (including ground conneQSf c.
tion).
~
d.
Making of any internal connections on equipment that were omitg9 fg 3) gg :40 d
purposes of shipment and the installation of necessary jumpers and local interconnections.
OFFly 0F :w: J Mounting and connecting of minor items shipped separately, ang0g,ggEWICL e.
and replacing details for convenient handling.
~
f.
Cleaning and checking of electrical equipment and connections.
g.
Testing assistance as defined in, Article,402.25.
h.
Assisting manufacturer's servicemen or Purchaser's Engineers in placing equipment in satisfactory operating condition including internal align-ing and adjustment of oil circuit breakers, metal enclosed switchgear, and other similar electrical mechanisms.
l i.
Touching up damaged surfaces.
l 401.17 Contractor shall review the equipment manufacturer's instruction books And.1 prior to equipment installation for any special procedures, recommenda-tions and/or conflicts with this Specification or the installation drawings. Purchseer or Consulting Engineers shall be notified of all special procedures, reconnendations or conflicts, and permission ob-tained before proceeding with equipment installation.
l, 401.18 Fleid Welding Requirements And.42 401.18.1 Welding shall be in accordance with the requirements of AWS D1.1.
At the option of the Contractor, where base metals thinner than 1/8 inch l
are to be welded, the requirements of AWS D1.3 may be applied in lieu oJ AWS D1.1.
Welders may be qualified to either ASME B & FV Code Sec-tion IX, AWS D1.1 or AWS D1.3 (for meterial less than 1/8" thick) requirements.
401.18.2 The fo11oving ASTM materials shall require one welding procedure quell-fication for each group of materialt stainless steel - A240, Type 304 and A312, Type 304i sluminus - B-241, Type 6061 and B-241, Type 6063.
401.18.3 The procedure qualification to demonstrate weldsbility specified by paragraphs 8.2.3 and 10.2.3 of AWS D1.1 is not required for the fol-And.45 towing base materials: ASTM A446, Credes A, B, El ASTM A526.
And.42 401.19 Fleid Welding Inspection Requirement.41 401.19.1 Walde including full and partial penetration groove welds, shall be subject And.4 to visual inspection as specified in BY/3R/VWAC.
In addition, full And.48 penetration groove welds shall be subject to NDE Inspectiort as specified in Form 1701 for structural steel.
RECElVED '!
401.19.2 (Deleted).
401.19.3 (Deleted).
glgg 401.19.4 (Deleted).