Ro:On 861028,while Performing Routine Monthly Surveillance Tests,Alarm Condition in Circuit Activated Visual Annunciation at Police Dept Indicator Panel But Failed to Activate Audible Annunciation.Caused by Dirty Contacts
ML20213G933
Person / Time
Site: Kansas State University
Issue date: 10/30/1986
From: Faw R
KANSAS STATE UNIV., MANHATTAN, KS
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
NUDOCS 8611180411
Download: ML20213G933 (1)


Text

Department of Nuclear Engineering m Ward Hall Manhattan, Kansas 66506 m 913-532-5624 October 30, 1986 I y h, ,

U. S. Nuclear Regulatory Commission, Region IV \j "!

Gil Ryan Plaza Drive, Suite 1000 l- g,. [ ^q$ p Arlington, Texas 76011 , 1

__.f. 6, j L

Re: License R-88 Docket 50-188 -~

Dear Sirs:

This is to report temporary degraded performance of the intrusion-alarm system called for by the Reactor Facility Physical Security Plan.

While performing routine monthly surveillance tests on 28 October 1986, we found that an alarm condition in the circuit activated a visual annunciation at the Police Department indicator panel but failed to activate an audible annunciation. The unit was removed from service on 28 October 1986, repaired, tested, and replaced into service on 30 October 19S6. The performance degradation was due to dirty electrical contacts which prevented delivery of adequate power to the audible alarm. While the unit was out of service for repair, all provisions of the Facility Physical Security Plan were met.

Although this experience reinforces the value of periodic surveillance tests, the intrusion-alarm system has functioned well for a number of years and we have elected not to increase surveillance

( frequency. The University is considering the adoption of new standards l

for security systems. The Reactor Facility staff will be working with the Campus Police Department to assure that any new specifications meet the needs of the Reactor Facility.

Sincerely.

l S& -

w[

Richard E. Faw, Director KSU Nuclear Reactor Facility j cc: N. D. Eckhoff, Chairman l Reactor Safeguards Committee 8611180411 861030 gDR ADOCK 05000188 PDR l 9,-in5 @ f k0