a JUL 2 7 m33 MEMORANDUM FOR:
Cecil 0. Thomas, Chief Standardization and Special Projects Branch Division of Licensing FROM:
Victor Benaroya, Chief Chemical Engineering Branch Division of Engineering
SUBJECT:
REVIEW OF WPPSS NUCLEAR PROJECT NO. 2 TECHNICAL SPECIFICATIONS We have reviewed Sections 3/4.4.4, Chemistry; 3.3.7.9 Fire Detection Instrumentation; 3/4.7.6, Fire Suppression Systems; 3.7.6.2, Spray and Sprinkler Systems; 3.7.6.3, Halon Systems; 3.7.6.4, Fire Hose Stations; 3.7.6.5, Yard Fire Hydrants and Hydrant Hose Houses; 3/4.7.7, Fire-Rated Assemblies; and 3/4.3.7.9, the Basis for Fire Detection Instrumentation; and 6.8.4.c, Procedures and Programs-Post Accident Sampling.
We have only minor comments.
We have discussed and resolved these comments with Don Hoffman, Standard Technical Specifica ions Section.
Victor Benaroya Chief Chemical Engineering Branch Division of Engineering
Contact:
D. J. Kubicki F. J. Witt X27743 X28360 cc:
R. Vollmer W. Johnston D. Eisenhut S. Pawlicki R. Ferguson C. McCracken D. Hoffman A. Schwencer
- SEE NEXT PAGE FOR PREVIOUS CONCURRENCE
- 0. Brinkman T. Sullivan R. Auluck DE/CMEB DE/CMEB DE/CMhh DE/ EB DE/CMEBk)
J. Taylor
- FWitt
- CMcCracken DKubicki RFe' uson VBenaroya 7/ l/83 L
AE00 7/26/83 7/27/83 7/1 7/83 7/3 /83 F. Witt D. Kubicki P. Sternberg, Region V
/
o
~
MEMORANDUM FOR:
Cecil 0. Thomas, Chief Standardization and Special Projects Branch Division of Licensing FROM-Victor Benaroya, Chief Chemical Engineering Branch Division of Engineering
SUBJECT:
' REVIEW 0F WPPSS NUCLEAR PROJECT NO. 2 TECHNICAL SPECIFICATIONS We have reviewed Sections 3/4.4.4, Chemistry; 3/4.7.6, Fire Suppression Systems; 3.7.6.2, Spray and Sprinkler System 3; 3.7.6.3, Halon Systems; 3.7.6.4, Fire Hose Stations; 3.7.6.5, Yard Fire Hydrants and Hydrant Hose Houses; 3/4.7.7, Fire-Rated Assemblies; and 3/4.3.7.9, the Basis for Fire Detection Instrumentation; and 6.8.4.c, Procedures and Programs-Post Accident Sampling.
We have only minor comments.
We have discussed and resolved these comments with Don Hoffman, Standard Technical Specifications Section.
Victor Benaroya, Chief Chemical Engineering Branch Division of Engineering
Contact:
D. J. Kubicki F. J. Witt X27743 X28360 cc:
R. Vollmer W. Johnston D. Eisenhut S. Pawlicki R. Ferguson C. McCracken D. Hoffman A. Schwencer D. Brinkman T. Sullivan R. Auluck J. Taylor P. Sternberg, Region V AE00 I 'A I
F. Witt
/
D. Kubicki DE/CMEB DE7CMEB DE/CMEB DE/CMEB DE/CMEB FWitt CMcCracken DKubicki RFerguson VBenaraya 7/;;/83 7tff/83 7/0J7/83 7/ /83 7/ /83
.