Discusses 820723 Submittal Re Protection of Diesel Generator Exhausts from Tornado Missiles.Applicant Must Select Either Alternative 1,control of Bluff or Alternative 2,providing Missile Barrier,Contained in O Parr 820611 Memo
ML20213E229
Person / Time
Site: Columbia 
Issue date: 08/06/1982
From: Parr O
Office of Nuclear Reactor Regulation
To: Schwencer A
Office of Nuclear Reactor Regulation
References
CON-WNP-0538 NUDOCS 8208190090
Download: ML20213E229 (1)


Text

Dittribution M06g IMcket File ASB Rdg. File

~

ASB Members 0Parr DIcket No. 50-397 LRubenstein MEMORANDUM FOR: Albert Schwencer, Chief, Licensing Branch No. 2, Division of Licensing, NRR THRU:

L. S. Rubenstein, Assistant Director for Core and Plant Systems, Division of Systems Integration, NRR FROM:

Olan D. Parr, Chief, Auxiliary Systems Branch, Division of Systems Integration, NRR

SUBJECT:

DIESEL GENERATOR EXHAUST TORNADO MISSILE PROTECTION FOR WASHINGTON NUCLEAR PROJECT NO. 2 We have reviewed the applicant's submittal dated July 23,1982,(Letter No.

G02-82-620) concerning the protection of the diesel generator exhausts from tornado missiles.

In a memorandum frcm O. Parr to A. Schwencer dated June 11, 1982, we proposed three alternative methods of providing tornado missile pro-tection, namely,1) have control of the bluff area and commit to having no loose materials including utility poles stored there during the life of the facility, 2) verify that the. plugging of one of the two diesel exhausts will not result in the diesel's failure to start and produce sufficient power to safely shutdown the reactor (this assumes a single failure in the redundant diesel generator system) or 3) provide a missile bariter.

The applicant elected none of these options. The applicant did state that the plugging of one of the two exhausts of the diesel generator would disable that diesel generator. Alternative 2 listed above is therefore not viable for UNP-2.

After considering the arguments put forth by the applicant, it is our position that the applicant must select either Alternative 1, control of the bluff or Alternative 3, providing missile protection to the diesel generator exhausts.

/C

~

M Olan D. Parr, Chief e208190090 820906 Auxiliary Systems Branch

.^ C ADOCK-OSOCO39 T-Division of Systems Integration

-OF-cc:

E. Case R. Auluck R. Mattson J. Ridgely D. Eisenhut T. Novak R, tobel

Contact:

J. Ridgely

(

.i2 ^300 DS

AD

...,,J :,ASB jf._, DS I : AS B j

DSIg omeo suen Ei.d.ge,1,,; a s

,,,R,Lo b,el,,,,, ODPa rr LRul t in

'f 7

om W

. 8.a282.....

...8/.g.g..!...m p 82..l.

8 &.2

?

.p sac rosu ais oa.cmacu m OFFICIAL RECORD COPY usw n.,_m m