ML20213D785

From kanterella
Jump to navigation Jump to search
Rev 0 to S-C-A910-CFD-0328-R0, Maint Requirements for Maintaining Environ Qualification of Exo-Sensors,Inc Hydrogen Analyzer. Related Info Encl
ML20213D785
Person / Time
Site: Salem  
Issue date: 07/29/1985
From: Gross H, Michael Levine, Stanley R
Public Service Enterprise Group
To:
Shared Package
ML20213D757 List:
References
S-C-A910-CFD-03, S-C-A910-CFD-3, NUDOCS 8611120233
Download: ML20213D785 (65)


Text

-

t t

(f S-C-A910-CFD- 0 3 2 8 Page i of 3 1

R0 Date 7/15/85-J Pun >c semce E ec:oc anc Gas :

.e 33E_-

Nuclear Oecartment TITLE: MAINTENANCE REQUIREMENTS FOR MAINTAINING THE ENVIRONMENTAL l

QUALIFICATION OF THE EXO-SENSORS, INC. HYDRUGEN ANALYZER

1.0 PURPOSE

This Field Directive transmits to the Salem Generating Station i

the requirements for maintaining the qualified status of the Exo-Sensors Hydrogen Analyzers.

2.0 SCOPE

This document applies to the required hydrogen analyzers.

Both Units 1 and 2 possess an Exo-Sensors hydrogen analyzer installed in each containment.

3.0 REFERENCES

3.1 Containment Hydrogen Analyzer System - Operation and Maintenance Manual - Exo-Sensors, Inc.

PSBP 174275

4.0 DISCUSSION

The purpose of the hydrogen analyzers is to provide an indication of hydrogen concentration in the containment.

The Hydrogen Analyzer System consist.s of hydrogen sensor calibration assemblies mounted in containment and a microprocessor control assembly located in the Equipment Room.

The Exo-Sensor Hydrogen Analyzer utilizes hydrogen partial l

pressure and containment total pressure to compute the hydrogen concentration in containment.

Information from the temperature transducer is used by the microprocessor for temperature compensation.

Hydrogen Partial Pressure x 100 Volume % Hydrogen =

Total Containment Pressure To maintain their qualified status, specific scheduled maintenance must be performed.

What follows is a summary of 4

the required maintenance activities and the frequency with which they shall be performed:

1)

Every 90 days (or 30 days post-LOCA) the automatic calibration cycle shall be checked by performing the hydrogen sensor 2-point check, and the single point check for the temperature and pressure sensors.

EDD-7 FORM 1 REV 0 10 SEPT 81 hDR D

500 272 G

PDR

S-C-A910-CFD- 0 3 28-R0 Date:

7/15/85 2)

Every 12 months, the signal conditioner status shall be checked by a) measuring the bridge voltages for the transducers and RTD's, b) updating the calibration factor, and c) verifying the system alarm.

3)

Every 24 months the calibration gas supply shall be replenished.

This involves recharging the calibration gas cylinders, checking the regulator settings, and checking the supply manifolds, fittings and valves for leakage.

4)

Every 36 months, the hydrogen sensors shall be replaced; and the RTD's and pressure transducers shall be checked.

This involves performing a 2-point calibration check of each, and updating the calibration factors, as necessary.

5)

Every 10 years, the calibration assemblies shall be refurbished by replacing the following components:

a) calibration pistons and caps b) regulator diaphragms c) bottle valve stem seals d) pressure transducers e)

RTD's f) solenoid coils The procedures to perform these activites are all clearly outlined in Section 5 of the vendor's manual ( Re f. 3.1 ).

Reference 3.1 includes the diagrams, schematics, descriptions of the analyzer and vendors information of all replacements parts necessary to perform the required maintenance with relative ease.

5.0 CONCLUSION

/ RECOMMENDATION:

Section 5 of Ref. 3.1 gives a clear, step-by-step set of procedures to accomplish the necessary maintenance activites.

Adhering to the information and procedures of this reference will ensure the continued qualification of the Exo-Sensors Hydrogen Analyzers in Salem Unit 1 and 2.

6.0 VENDOR MANUAL IMPACT:

l This Field Directive has no impact on the Vendor's Manual.

l l

l

{

l l

l EDD-7 FORM 1 REV 0' 10 SEPT 81 i

Page 3 of 3 Date:

7/ M/85 S-C-A910-CFD 0328_go 7.0 REVIEW AND APPROVAL:

% G.. v. Iv ' + / n / f W m O w Originator Verif C g

7 fff 7feff[

S roup Head

'cpinator's Group Head Manager - Nucaear Systems Engineering BGH: jab FD6/1 1-3 EDD-7 FORM 1 REV 0 10 SEPT 81 I

Arrscumv7 3 Comygianaar //yo.toGw Mani r tea

>7 ste,,

PS E f' C PSfdP # 174 :2 yr SECTION 5 SYSTEM MAINTENANCE 5.1 GENERAL The proce[iures outlined herein are to document functional status of each sub-Actual maintenance proca-system and specify periodic maintenance requirements.

dures are by design, held to a minimum. Table 5-1 summarizes both maintenance and verification activities beginning with the most frequently required function.

TA8LE 5-1 SYSTEM MAINTENANCE AND STATUS CHECK SCHEDULE ACTIVITY FREQUENCY SCOPE AUTOMATIC 90 Days

  • HYDROGEN SENSOR 2 POINT CHECK CALIBRATION (30DaysPost
  • SINGLE POINT CHECK FOR TEMPERATURE AND CYCLE LOCA)

PRESSURE SENSORS SIGNAL 12 MONTHS

  • MEASURE BRIDGE VOLTAGES FOR THE TRANSOUCER CONDITIONER AND RTO
  • UPDATE CALIBRATION FACTORS STATUS
  • CHECK SYSTER ALARMS REPLENISH 24 MONTHS
  • RECHARGE CALIBRATION GAS CYLINDERS
  • CHECK REGULATOR SETTING & LEAK CHECK SUPPLY CALIBRATION MANIFOLD, FITTINGS AND VALVES.

GAS SUPPLY HYDROGEN 36 MONTHS

  • PERFORM 2 POINT CALIBRATION CHECK OF THE RTO SENSOR
  • PERFORM 2 POINT CHECK OF THE PRESSURE REPLACEMENT /

TRANSDUCER RTD AND

  • CONFIRM EXISTING FACTORS OR ENTER NEW PRESSURE CALIBRATION FACTORS TRANSDUCER CHECK REFURBISH 120 MONTHS
  • REPLACE THE FOLLOWING COMPONENTS:

- Calibration Piston and Cap CALIBRATION ASSEMBLY

- Regulator Diaphragm

- Battle Valve Stem Seal

- Pressure Transducer

- RTD

- Solenoid Coil

a...

..,.~:-

3,

,->,-v.

. a,,

1 5-1

fG S Cf. O o Eno Snnsan Que u6i M m~ Trst p/n yp.

_g, g

A7~~mcNMEm 7 4 3.0 AGING The qualification test program, including any engoing programs which follow, will establish the qualified life of Routine the analyzer system and its major ccmponents.

maintenance and replacement procedures will thus be defined 1

to assure the proper operation of equipment throughout the qualified life.

Based upon consideration of environmental conditions, material and performance evaluations and baseline data for components, the age-related failure mechanisms will be estimated for the hydrogen analyzer system.

Those components and subassemblies susceptible to aging (e.g., sensor assembly) will be artificially aged to an end-of-life condition by For the sensor, operation operation at stress conditions.

I at temperatures higher than the normal pre-event levels will be sufficient to provide accelerated aging.

Cataloged data from various sources will be used to establish aging criteria I

for other components as well.

For purposes of establishing ground rules for aging, As a result of a,n environmental profile has been assumed.

l the sharing electronics between PINGP-1 and PINGP-2, it is anticipated that the data systems will be continuously l

" powered up", and that operation for 100 days after accident onset is required.

The hydrogen sensors and associated calibration equipment will see continuous operation at normal containment conditions.

A typical duty cycle for the electronics is assumed to be as follows:

Operation at 72-75*F;i355, days per year Operation at 105'F; 10 days per year As a result of the requirement totoperate continuously, because of the unique nature _of the tims shared configuration, it w'ill not be faisib'le tC perform;a full pri~ aging, there-fore, an ' ongoing ' aging procedure 1will' be implemented.

22

The electronics shall be subjected to brief perieds of operation at 50*C,(2 periods of 100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br /> each) by the manu-Operation of the electronics after this initial facturer.

screening will be for as long a period as practical prior to seismic simulation.

Operation through seismic, and subsequent accident simulation will then be performed with a minimum of 100 days of post accident operation accumulated.

Evaluation of system performance at this time will verify satisfactory performance to th5t date.

Operation of the system will continue:and. additional performance date g

will be accumulated.

Techniques and validity of accelerated aging processes will again be evaluated and utilized if feasible.

Aging may include another seismic simulation at this time.

This approach to demonstrating qualified life is in

~

381-general accord with the options afforded by IEEE Std. 1977.

The post-accident aging by operation is deemed valid for the electronics since the DBE adds no appreciable stress to this equipment which is located in the " Bus Room".

The basis for in-contain m at equipment is that routine f

I replacement of the sensor be accomplished at 18 months, at which time the support equipment may be inspected and/or maintained.

Assuming continuous duty on the reactor for this period, the temperature will remain at 140*F for the

{

entire period.

f 4.0 SEISMIC SIMULATION The seismic qualification of the hydrogen analyzer is intended to demonstrate that it will function.during and after the time when it is-subjected to the-forces-resulting

[from a safe shutdown ea$thquakai-~(NSE)~ai~fter ~it-is shown' -

f 3.

'~~ that it can withstand a[mEbdm]cT~five operatinfbifiY~~

23 G

e

x m c...5...

n

,; y y,,y pgg y,5-E:c3 sENSCES, I1C.

T TPYCOVEP. LETTER N # # M## #

FROM: F/264 P M W 4 F 'c

. LEASE DELIVER TO:

Pua ba denyet f/2 i M COMPANT 84/##

NAy IIO 5ZN50K!, INC.

gg yacx,eg

/Wf g g 1200-5 SIMON CIRCLE ggte yg3g.ej ANAEEIM,CA 92506 (714) 632-6239 eff DATE/ TIME TOTAL NUMBER OF PAGES

  1. 4#

2 G of-.137 '/038.., _,

EICLUDING COVER PAGE TEECOPY OPhLf0R:

~ ]:.: DATE / TIME SENT:

RIMARES:

22.44#uA b47# M4 kPuerbc/E4 4 /#"S ac //vbeccen A m ueen c a se d en is

/

RfA.3G

/11077ftr ALS. A^C21."4 deas7

/mmE.bv4 TN * '//pos/

Ai?st3r/PT e#'

77H3

~?3?nM hs.tsbd EIO INTIRNAL TERCOPY DISTRIBUTION 4

RB21TED fnAmm1T!!D COPY To:

INFO.ONLY/ ACTION REQUIRED R. ALDERSON J. FULLER G. GREEN LIWOE 1.LEFF y,

m.

~~

/

Z F.RUDEK

~~~ C

~

D. mvENs

~

~

T. WHITEHEAD

z 14 6: 5:v:

CCM90NENT: E d~n:*71 / (4 d (A/S$f

'S

//SD ESC A//0,) ?//W)

EXO SENSORS 9/N:

SUPPLIER: [M*C&#f SUPPLIER PIN: OdC 44 N/Af ENVIRCNMENTAL CUALIFICATION r

THERMAL AGINE

~

Mdt/4[#M I

4 /7dN Age Sensitive Camponent:

l

~/./d ~[###'/)

Activation Energy:

268 *#f Aljypt AT3 )

Nax Aging Teeperature:.

Qualified Life:

' 4 4 4 # J "'

1 Normal Operating Tamp:

93 *#

i htADIATION 4// #4AT' [N Total Integrated Dose:

Fac111ty:

A Ab d 77tw.57xicit'sta dt Exo Sensors P.O. f:

8 - 4.3 0 d 4 [ W / F W 4 7Prarld f e e M ao Wtees Date:

A Aafft, 4,/914 Qualification Level:

4t/d 7 #4df (F)

OPERATIONAL ASINE W4 Total No. Cycles Equivalent Age N/A SEISMIC TETT Facility:

ILY

[MddddI4/d

/VT8 [44S Exo Sensors P.O.'9:

AC 033$A

/ 739 i

/NAHf /9/$ Ts Af/dit/57/ff/

Cate:

[N8Y

'/4V/- 9/97 Report No.:

LQCA SIMULATION 258 [#A' dlM3 A7T Facility:

Sample Tamperature:

A//4

  1. 4 7 -/
  • 14 84 7 #3 r N W Sanole Pressure:

^JVA

  1. F /** bedhis FKdd f

9 6

C jtconent Aging Suaanary camaanent l

  • fmi-4 a Matsr'a1

'agtng

' Qualifies *

). lame l J. av l Temo.. wax,

Iffe. yrs.

Hydrogen Sensor

, Ethylene 2msylene 1.1 (2) 220 'F.

7.3

--O y ;;.. ^; ;;r

'W?:x;'n;j?r.

',2 '

215

'3 Pressurs Transducer Esexy 0.78 (1) 275~*F 10 RTD EC 2215 Esazy 0.38 (1)*253 'F.

40

"' :1 L' 'O

"" O'::: * -,

. ;.2

(;.;

2 2 "".

'O Asco Valve Ethylene Propylene 0.34 (2) 258 *F.

40

. ; '!:!x "ri',- ; " ;;; E-:

1.;

?'" **

-Q

.e.

m, Electrical Cable Polyelkene 1.10

('1): 268 *F.

40 ~.

Terminal Blocks Ourez 152

, l'.'D5 **. (1-). :329 *F 40 m __. _ _

,_t r,.

s

.,a Pressure Regulator Viton g,

1.1

('1) 300 *F.

40 Manual Valve carbon / graphite

  • T/A 268 *F 40 T L.,rn _ '~
~. *..
i., \\

e--

s.,.

..,.r..,,,._

Cable Terurinettons Nylon 6/6 1.14

,(3) 300 *F.

40 s..

-m

  • Refer to Appendix 8 for the service temperatures associated with the qualifiM
  • Life of these components. -

NOTI $:

(1) EPRI NP-1558; A Review of Equipment Aging Theory & TecMology. Project 890-1, Sept., 1980.

i (2) ACR-67368 Rev 0; Report on Qualification of ASCO NP 1 Solenoid Valves.

(3) 01-1430-1230. Rev 0; EDS Nuclear Inc., Mild Environment Qualification of Exo Sensors Inadequate Core Coolant Monitor.

(4) The cualfffed Iffe for the motor startar is taken from Me G.E. test documentation re/erenced fn Tante 4-1.

It is based on an 85 *F ammient temperature and a 25% duty cycle.

N* YE.*

/7kT M bru6.0 Cur s&ds sue 7 di+2O M4c.d

'r'o NO &

'/'7 - 3 t'*M H*f bdC6 e~N &'& iWA. 3

-77fpt _

2 t- <.s -u

z n4 6:: s: :

i AGING CALC'JuTIONS The following listing is the kay to the taoles in t.iis section.

Activation Energy in electron volts (ev)

Test temperature is in degrees centigrace Test time is in days Qualified t.ife is in years

...c

.z (1) EPRI NP-1558 A Review'of. Equipment Aging Theory &

Technology. September ~1980. ~-

(2) AQA-47388. Rev. 0; Report on Qualification of ASCO NP-1 Solenoid Velves (3) 0114301230. Rev. 0; Mild Environment Qualification of Exo sensors Inadequata Core Coolant Monitor. EDS Nuclear Inc.

In the specific data sheets, unless otherwise notad, the activation energy reference is fl.

l i

._q

,y

. G A -~y. ~~.;

.;;;a *

- - ~. ~.., _... _ _ _.

v

-~-3-.

'y't

' ~'

-. ; :a :s q _

/

./

f

z 14 6:: 9:7:

04 Q.

C;.'APCNE.'i T: &D RC4EA) &W3cA.

DO SDSCRS P/N: /C/DC/2l 3A/824 SUPPLIER: Se $&s<MLS /Mc SUP.*L:!R P/N: /Orha/2 i

DVIRONMENTAL QUALIFICATI0N

..~.

TliERMAL AGING Age Sensitive Camponent: #rh5e/ddWW M de:wat Activation Energy:

/. / e V [ # # A P E )

Max Aging Temperature:

23e *C Qualified Ltfe:

7#per4AS

  • 4oc4 Normal Operating Temp:

/Ji #

AA0!ATION Total Integrated Dose:

MX/d #AhAJ (b.* MM-M/ O J Fact 1ity:

848 /4 7'FdAl IF3r/4/ FEEJ'

[

Exo sensors P.O. #:

/ddr 7" Cate:

JGAfd /94/

l Qualification Level:

7.4X/d # #AA.rfge f)

  1. pa#

OPERATIONAL ASING Total No. Cycles Y4 Equivalent Age A//4 SEISMIC TEST Fac411ty:

AM

/V7C i

Exo Sensors P.O. f:

47J

'/

759 Date:

~4/8/

'/

8/4/

c Report No.:

Afr2 549-903 8 '/

  1. 7 3* $ V 8 - 9 / 9.1*- f LOCA SINULATION

~

fac111ty:

Af73

(

M7"3' St/d-9/95"-/)

l s-ie T m r.ture: ~a/o'e--

. Sample Pressure: 2 TugP:AR3*/ds

~ ~

i z

. ' - -. = -.

9

1 I

z t4 c: s: :

c:

i St/Ad W 4Mr'aued%C fSA /# W CCHPONENT: 52A l0d'Od2f" EX0.$EN50R$ P/N:

WLL W SorcQ M M SU79 LIER:

'OfC-/doct ~ OY (FR4/.tbudd*dLs t

I SUPPLIER PIN: OK'/& 23def:

C o d k ele:rie w.s / m# # # M '# NE ENVIRONMENTAL QUALIFICATION

~.

,.i THERMAL AGING

~ ~ " - -

85 tsr4r 8

~

Age Sensitive Component:

  1. . 78

~~-

Activation Energy:

27f*M Max Aging Temperature:

44 4,eengs Qualifted Life:

/4 M *A:

Norma 1 Operating Temp:

RADIATION Total Integrated Dose:

/Y/d #AWIWr M Faci 11ty:

PAnse.rr d fr1rn/ts aar M Exo Sensors P.O. M

  1. dtgr/

7"

/ Ve & Andst

//, / fd V Date:

fx#N [4r /F)

Qua11fication Level:

OPERATIONAL AGING M/4 Total No. Cycles Equivalent Age SEISMIC TEST hf'48 NNd Facility:

Exo Sensors P.O. #:

// #

Data:

/ffdV / 2.

/ f/Z M /3 fl Aeport No.:

7-i -

LOCA SIMULATION

.hacility:

/JNN. MNUiPMN ~

4 J /O *4 6 /7.ow l Sample Temperature:

72.7 A1/4 (/Prdy )

Sample Pressure:

9 i

z :s*,:: ::::

a COMPCNGT:

ETS EXO SDSCRS P/N: //dD#d/ [/g SUPPLIS:

INdfCG ENG/Af ggAJN'G SUPPLIG PIN:

/8 0 - 4028 (d*d w V. 73

/80 33/7)

ENVIRONMENTAL QUALIFICATION THFJtMAL AGING

' Age Sensitive Component:

gc 2Ws 88d/y h:N Activation Enery:

d.98 (Rff /)

Max Asing Temperature:

76# *#

Qualifted Life:

4d Og4FJ

/.2g *#

Normal Operating Temp: _ _ _

ItADIATION Total Integrated Dose:

4//d MA3 M

Faei1ity:

RAD /AT^ta) $7B" /L/ffR3 fe<.

2 Esa sensors P.O. f:

E-OJeo 4 l

Date:

,1l'Z/L f, /944

}

Qualification Level: _

2/ M ##4f (4p F)

( #W#',

$#~

WTIM MIM W)$4 Total No. Cycles Equivalent Age AV4 SEISMIC TEST 4ETL//t/7J Facility:

Exo Sensors P.O. #:

/f3 N A/4 /90/

Cate:

i Report No.:

Af74. SW8~f03S LOCA SIMULATION

~

O 24,.. n..,. Fact 11ty:

[

376 7

~ ' '

W4 ingy 7[Samp[j, emperature: _

J ~[no7S/6~~

2 S.N

~

2 ~,Samwy e Pressud:~ '

e,e j.

'*L o

u K_

, ;m

. s.

n-l

+3

. L'$

4........

4 C;M90nENT: b lDJ61O YA/,VG u

Ex0 SENSORS P/N: /8D$30 //4

$UPPLIER:.dufDM47'/c diuerry d MO 4

$UPPLIER P/N: g 7324948 g

v E. IRoto*EMTAL OUALIFICATION Ag-67%d

}{f i

W m

TliERMAL AGING 74

. Age SensitNe Component: 8M N##

Apha' ActivationEnergy:~~

d.9V (MINdP 21 -

[

Max Aging Tamperaturef 268 ##

.hg

~

@alified Life:

4 W#r.T Normal Operating Teep:

'//S *#

7,5, RACIATION) Total Integrated Dose:

f. A f X/d M4M

$ f..k.- ,s.. i Facility- %Q Ezo Sensors P.O. #: N/A - U S&OM ('.@, .. l.',' r Date: 7 %alification Level: (~ .,? E OPERATIONAL AGIIIS h>MMNOM Total No. Cycles Equivalent Age 484/*3 i 6 SEISMIC TEST n 54f =TWPL/L'A a N' Facility: [ *b[ [ ..? Exo Sensors P.O. #: A//4 l Date: Report No.: 484 - [7342 iIf ap $I LOCA SIMULATION anu Facility: 3y Su ##C/Eg.* ASM-f 7348 358,k5 o 40S#A: _ lip 'SmW14_Tamperaturei w ~ ^ ' ' Smole Pressure:

  1. D4%Fd

'$5h an 7sps. sank 4;$u l

  1. 2'O M
  • M M57 '70 Pressum, 4Te-I sz is i

1, i = .j m i TOs4 lhd f

z 14 4:: :: : n i catpcNCti: $E3:04C . c's UtA7:/ o ca stacas ?tN: I/SD?2c P / m: 6Cr/NC. $UPFUIR 7/N: lY ~l E.WITm C6A!. Ct!ACFTCAON l ._._11gspgu, AgI,1g Age sensitive ccmooneau 1//bd ~ Ac 1varfan Energy // C9Er. /) Max Agfng Temperattare: Scx3 *# Qualifted t.ffe:

  1. /d UcA43 Normal Operating Temp:

96 */ AADIATION Total taxesrated Gese: T.M7CANA 770NAL AlO796N c2 facility: Z47trtNAricNR Alarm wics" Ene sensors v.a. Is 4% oetas 2MuuMY /.*5/ 4Y27 #46.T / Qualiffcaston Level: WHATIONA4. ASING i Tetai me. cystes N/A famivalent Age SIZSEIC TIIT Faciltt/: _ A/7"S Eas Sensors 7.0. #: '/SP l Onta: Au4ust _ M8/ Racer: so.: 4 7./ 8 - 91 9 6~- I LCCA 3DULATIQlt l Fm:111ty: N7T samele 7emocrature:- J/C "#~ l sammte Pmsure:


4 0-DZ/d

-- - ^ l

  • ~. 5 l

73 -. - ~ l l i i {

u a m 4:: s::: Exo SEN5CES, INC. TM TOPY COVER 12.1is PI. EASE DELIVER T0: /M/### FROM: F F PuoEL PSe v'd /$4/fe #AJ EIO SENSORS, INC. , 6 a c o c e 's 75 r/a s p 1220-B SIMON CIRCLE ANAHEIM,CA 92806 gg ggy g (714) 632-6269 b DATE/ RIME TOTAL NUMBER OF PAGES 4 4 4g)7__93[- 443 8 EICLUDING COVR PAGE TELECOPY OPERATOR: DATE / TIME SENT: REMARKS: EA<k UP b/4 m To fuppadY tD 7Civ'$/ O A] cc Perssuda 744Nsbwcx AFD DTD 4~62 /A/ 5"/ W 4</ MedEd A/VA y/tGAL i PleAse rionm Mica 4rc devwe //wnfb/ 4 rr 4 //!doW /CCC/W QP 7W47 12MWSM/SS'od II0 INTERNAL TELECOPY DISTRIBUTION i l LOG

  • i l

COPY TO: INFO.ONLT/ ACTION REQUIRED i R. ALDRSON i J. FULLER G. GREEN L KWOK J.LEFF M. MOELING F.RUD R D. aM5 T. WHITEHEAD 4

z.te.:. 5.r. i i NENT NAME: RTD MATERIAL: EPOXY OTIVE ENERGY TEST TEMP TEST TIME QUALIFE (EV) (DES. C) (DAYS) (YEARS) 78 1:5 18.9 43.51134 S4sco og /d@ Gifo.Sude 6 SAN OU

  • 18 j3[

]99 ( 9. (,1 D syposade i (2/$b ^ (. Aging Summary Camponent: RTO Serial No: 012 The following data are summarized from the original temperature recordings: 9-22 thru 9-26-82 278-292*F 9-26 thru 9-28-82 290-295'F 2 28 thru 10-11-82 275-290'F Total Test Time: 454.25 hours (18.9 days) Minimum Test Temp: 275'F 'W

27 4.i:: 5:r: 0; s..iPCNENT NAME: PRESSURE TRAMEDUCER MATERIAL: EPCZY ACTIVE ENERGT TEST TEMP TEST TIME QUALIFE (EV) (DEG. c) (DATS) (TEARS) bM 0" #O .78 135 18.9 43.51134 bo sed ** I30'" . 72 lSr IF3 I9 y1is ^ ggpgum f(7M " Wu(6 t 5 Aging Summary Component: Pressure Transducer 5; rial No: 10624 The following data are summarized from the original temperature recordings: 9-22 thru 9-26-82 278-292*F 9 26 thru 9-28-82 290-295'F 9-28 thru 10-11-82 275-290*F Total Test Time: 454.25 hours (18.9 days) Minimus Test Temp: 275*F l l C.

A 774 e 'f"*?vf C Cc :oiser 3, 1996 ?'.1'd { i c b 3.#'I C e $ 1 L*': ? .c Li Salem auclear Ce mrat..nc se itt..c tinc c f 9utconw:ad ' c a... G-IGu riancocu s Bridge, NJ 080'i5 Aten: Mti-e av:ne . r i Genticmen: j The enclosed d -a t a c ac e: a g a a r :'. iries ca ; kup toforn.cten to sapoor t t h er extensiott of the q;a'ified life f r: r :rie prettsur e tr ansc:cet-i and A fD .n tne Exo 3.a n s a r s i n-s i tu h /drogen anal / 2er t t's ; a i l ed at he fa d it?m NFS, I I Using the indwr.r/.st c e.) t ed Ar rh r?n L uc eeiactaaships, the<ie c3ta wii1 ccnser,3ti.ely.upcor a cuali?ied ife of IL.6 vra.s at an } .,cm aetoc 9mp+ a :i.: a e r i ~3 : " F s55"C). - i?se o.aca were q2-h= red

- t e._ t s co icir; t ee u

.oa o v e s =, t. r e t e a,'.

.c er a a,d two RTC a o eur t r' t*

O a r t ij.1 (" 7.a

- 4 2 - -3 E o - - a /-2 4 7=

4 ::acr e J s a:1. x - s, si? : LJuJ..At"5

  • h i-8.[ t:Cr*t ?.

I '.~.' y a.'. .g Or F .J a '.1

e cv cPC.

freu? i*a: e ; n o a '. J orovide a h i2.3te..a c e w: t: ,0ur o m s.?

acert-

!. O s i3. 3?atus .3 ra tn? anaiyJTr". I 5 s cer e L t. TAG SD,5GPE. INE. M / Mb Fred P. R u d e i< 1 l ^J P 08A3Lity fis 5U ^ d.ir!? l l 1220 B SIMON CIRCLE ANAHEIM, CA 928% O (714) 632 8289 FAX NO. (714) 632 5272 TWX NO. 910-5911883 TELEX NO. 880430 i r

a COMPONENT: Pressure Transducer /SN 19624 EXO SENSCRS P/N: 1058025 SUPPLIER: Sell & Nowell CEC Civ. l SUPPLIER P/N: CEC 1000-0208; CEC-1000-04 (Transoucers are identical, eleccet=al connecitons are equtvalent). ENVTRONMENTAL QUALIFICA7?ON THERMAL AGING Age Sensitive Component: Epoxy Activation Energy: 0.78 Max Aging Temperature: 275'F Qualified Life: 40 years Normal Operating Temo: 194*F RADIATION Total Integrated Dose: ox10' RADS (Gammal Facility: Raetation Startliters Exo Sensors P.O. 2001-7 Date: Novemoer 11, 1982 Qualification Level: 2x10" RADS (Seta - Gamma) CPERATIONAL AGING Total No. Cycles: N/A Eouivalent Age: SEISMIC TEST Facility: Wyle Lacoratories Exo Sensors P.O. 1144 Date Novemoer 12, 1992 i Report No.: 58813 LCCA SIMULATICN Facility: Wyle Laucratories Samole Temoerature: 310*F (max) Samole Pressure 72.7 osia (max) t- ?3z

(.' CCMPONENT NAME: PRESSURE TEARSDUCER MATM Mf-: EPCET ACTIVE ENERGT TEST TEMP TEST TIME QUALIFE (EV) (DEG. C) (DAIS) (TEARS) .78 135 18.9 43.51134 Aging Summary Comoonent: Pressure Transducer Serial No: 10624 The following data are sunnarized from the original temperature recordings: 9-22 thru 9-26-82 278-292* F 9-26 thru 9-28-82 290-295'F 9-28 thru 10-11-82 275-290*F Total Test Time: 454.25 hours (18.9 days) Minimum Test Temp: 275'F B-3 l 1

l i COMPCNENT: RTD/SN 012 EXC SENSCRS P/N: 1050005PS SUPPLIER: Tayco Engineering SUPoLIER P/N: 190-3317 (Equiv. to 180-4029, difference is in diameter of housing, 3317 is 1/4"' 4028 is 1/8" cuoe). ENVtRONMENTAL QUAL!CICATICN THERMAL AGING Age Sensitive Component: Ecoxy Activation Energy: 0.78 (Ref. 1) Max Aging Temoerature: 275'F (135'C) Qualified Life 40 years Normal Operating Temp: 194*F RADIATION Total Integratec Dese: 6x10' RADS (Gammal Facility: Radiation Stortlizers Exo Sensors P.C. 2001-7 Date: Novemoer 11, 1992 Qualification Level: Exte* RADS (Beta + Gamma? CPERATIONAL AGING Total No. Cycles: N/A Ecutvalent Age: SEISMIC TEST Facility: Wyle Lacoratories Exo Sensors P.O. e: 1144 Date: Novemoer 12, 1992 Recort No.: 58813 LCCA SIMULATION Facility: Wyle Lacoratories Samole Temoerature: 310*F (maxi Samole Pressure: 72.7 osia (max)

  • O qi 3-9'

CMPONENT NAME: RTD MATERIAL: EPQXY ACTIVE ENERGY TEST TEMP TEST TIME QUALIFE (EV) (DES. C) (DAYS) (YEARS) .78 105 18.9 40.51104 Aging Sunnary Component: RTD Serial No: 012 The following data are summarized from the original temperature recordings: 9-22 thru 9-26-82 278-292*F 9-26 thru 9-28-82. 290-295'F 2-28 thru 10-11-82 275-290*F Total Test Time: 454.25 hours (18.9 days) Minimum Test Temp: 275'F i l l l l l l l (' g m-g-

  • b g

tr

CERTTFTCATION OF IRRADIATTON CUSTOMC4: Exc Sensers, Incorporated IRRADIATION RUN CATE: November 11, 1982 IRRADIdTION RUN NUMBER: EtD 2001-T mat uIALS PROCESSED: NO. CTMS. DESCRIPTION LOT MO. One Unit RTD Enclosure - DWG f1080007 which includes RTD M12 Press Xducer 110624 Radiatiod Starilizars, Incorporated cartifies that 7 this material received a tqtal integrated dose of 6 x 10 Rads at a rata of 5.3 x 100 Rads /per hour withis the accuracy of the dosimetry devices utili::ad. 9 O V W Cata //- //- F 2. B 4r m si.euisers incorporates, saat uorgan c1nse.Tusen, causende sases / Teessnene (714) TJo esti

COMPONENT: Pressure Transducer /SN 8276 EXO SENSCRS P/N: 1055025 SUPPLIER: Bell'S'Howell, CEC Dtv. SUPPLIER P/N: CEC 1000-0200; CEC-1000-04 (Transducers are teentical, electrical connections are equivalent). ~ ENVIPONMENTAL QUALIFICATION THERMAL AGING Age Sensitive Component: Epoxy Activation Energy: 0.78 Max Aging Temperature: 200*F Qualified Life 40 years Normat Operating Temp: 194*F RADIATION Total Integrated Dose: 4x107 RADS (Gamma) Facility: Radiacion Sterilizers Exo Sensors P.O. 3002-T Date: March 3, 1983 Qualificacion Level: 2x10" RADS (Beta + Gamma) OPERATIONAL AGING-Total No. Cycles: N/A Equivalent Age SEISMIC TEST Facility: Wyle Laboratories Exo Sensors P.O. 1144 Date November 12, 1982 Report No.: 58813 LOCA SIMULATION Facility: Wyle Laboratories /Exo Sensors, Inc. l Sample remperature: 310*F (max) Sample Pressure: 72.7 psia (max) Date: April 1e, 1984 to June 27, 1984 l l

y. i I 3't ; g i e COMPCNENT NAME PAE35UPE TRAN3DUCER MATE 9?Ar_ EPCXY ACTIVE ENERGY TEST TEMP TEST 't:ME QUAT _ I FE (EV> tDEG. C) (DAYS) (VEARS> .78 140 3.5 16.32137 78 138 8.100001 Ei.9258e a J Aging Sumary Component: Pressure Transducer Serial No: 8276 The following data are sununarized frem the original temperature recordings: 2-18 thru 2-22-83 300-302*F s 12-20 thru 12-29-83 280-284*F Total Test Time: 8.1 days Minimum Test Temp: 280*F s 'I a 9 p 5 s \\ s' s 1 1 s t 5 \\ l

COMPONENT: RTD/SN 044 EXO SENSORS P/N: 105D005PO SUPPLIER: Tayen Engineering SUPPLIER P/N: 180-3317 (Equiv. to 180-4020. difference is in diameter of housing, 3317 is 1/4"' 4 0 2 8 -i s 1/8" tube). ENVIPONMENTAL QUALIFICATION THERMAL AGING Age Sensitive Component: Epoxy Activation Energy: 0.78 (Ref. 1) Max Aging Temperature: 300*F (130*C) Qualified Life: 40 years Normal Operating Temp: 104*F RADIATICN Total Integrated Dose: 4x107 RADS (Gamma) Facility: Radiation Sterili:ers Exo Sensors P.O. 4001-T Date: April 4, 1984 Qualificacion Level: 2x10" RADS t8 eta + Gamma) OPERATIONAL AGIrlG Total No. Cycles: N/A Equivalent Age: SEISMIC TEST Facility: Wyle Laboratories Exo Sensors P.O. 1144 Date: November 12, 1982 Report No.: 58813 LOCA SIMULATION Facility: Wyle Laboratories /Exo Sensors. Inc. Sample Temperature: 310*F (max) Sample Pressure: 72.7 psia (max) Date: April 16. 1984 to June 27, 1984 ~'

  • ----vv

-wa w- .w-r-7w,, -y. ,7

--e F CCMFCNENT NAME RTD .'1ATERIAL EFOXV ACTIVE ENERGY TEST TEMP TEST 7:11E GuALICE (EV) (DEG. C) (DAYS) (YEAR 3) .7S L29 9.10C001 21.925E6 Aging Summary Component: RTD Serial No: 044 The following data are sununarized from the original temperature recordings: 12-20 thru 12-29-83 280-284*F Total Test Time: 8.1 days Miminum Test Temp: 280*F i e ~.*C' -*" '_ 3_ ~ ,, a) c :~, I e 1 f.) }

  • i 4

1 a,g 9, i

) i 1 CERTIFICATION OF IRRADIATION CUSTOMER: EXO SENSORS, INCORPORATED IRRADIATION RUN DATE: 03/03/83 IRRADIATION RUN NUMBER: EXO3002_T MATERIALS PROCESSED: NO.CTNS DESCRIPTION LOT NO. " PRESSURE TRANSDUCER S/N 82767 ' 1 hNS0TS 'S/N 887,871,869 FILM (3 EA) P/N 101A007P2 0-RING (3 EA) P/N 2 022 t Radiation Sterilizers Iricorporated certifies that this g material received an air equivalent dose of 40 Meads, based on a ' rate times time determination within.the precision of the dosimetry devices utilized. Certified by w TE Date., 04/83 N. .-na> m ac ,.e em, Radiation Sterilizers incorporated,1401 Morgan Circle Tustin, California 92680 / Telephone (714) 730-0611

^: l i ,.g y,., _m = _ 7 - - = - - JUN 2 2 1984 r

  1. .;.1.

f., CERTIFICATION OF IRRADIATION CUSTOMER: EXO SENSORS, INC. t IRRADIATION RUN.DATE: 4/4/84 . IRRADIATION RUN NUMBER: EXO4001-T MATERIALS PROCESSED: NO. CARTONS DESCRIPTION ITEM NUMBER l il ) 2 ...y..- 1 . CONTAINED: --3, %. RID p/n 180;-3317,. S/N 044 J,2"Seinidi:",~p/n"101D012, 's/N 942,939,924 N i ~ ' .PST SAMPLES . FLOW SWITCH 500!-316-BPX ..Q.-rings 2-236, 212-SIL70 (2 en.) 2-361,

2:353

.CBECK VALVE SS-4C-1/3 EXOSENSORS ' P.O. fE-0 300A-i. ...r. / RADIATION STERILIZERS, INC. CERTIFIES THAT THIS HATERIAL RECEIVED AN AIR o EQUIVALENT DOSAGE OF 40 MRads, AS CAICULATED ON A RATE TIMES TIME' BASIS, AT AN AVERAHE DOSE RATE OF 1.5 MRads/ HOUR. COBALT 60 WAS EMPLOYED AS THE . m..r... ;.SO,URC. E O.F. GAMMA ENERGY. .,a.. ... +..., - .a. es diNM9t. WORK PERFORMED WAS IN ACCORD WITH THE-PROVISIONS OF 10CFR50; (APPENDIX B .= .su m o .e .-~ ~ e g 5;j y N Q;j QCLAND 10.CF.R21.~~$. 4%, n : - 2:4.+.th T'",~ ~ 'N.- 'ei-it.a : +- * ~ ^ ga-y;.:.j: r.c i n -r ~ ~~c.c.y, y, 4 y:.? 3 .s ha-.. pyx....

.. u.. ':.. :w.; y -

_ 4'.s_ '+.g. - e !.S,, i..G:: - l a. - : CERTIFIED ~BY f Jh_ 6'E .k.g :'n.. 4 N GENE MANAGER j. DATE

_~ s *2 O / 9

}}DT .y m .,? s- .$kTE f 24-2Y n 2.% ..:'..=. . : 1,u.-..... ... r. . ::.- m ...;. :::._e - c..,... .-Q

.y " a-.

....:. :q., +. s -.... r..~ ++ c- , 4. ; u. q ;;;. ~...... .. t.... -. p,. w., .g g = e Radiation Stertilzers incorportted,1401 Morgan Circle. Tusen, Califomia 92880 / Telephone (714) 730-0611 e. 7-.

SUMMARY

QUALIFIED LIFE UPDATE PRESSURE TRANSOUCER & RTD

(. TABLE OF CONTENTS ~ PAGE 1.0

SUMMARY

1-1 1.1 ENVIRONMENTAL SPECIFICATIONS 1-2 1.2 COMPONENT PERFOPMANCE REQUIREMENTS 1-2 1.3 TEST SEQUENCE 1-4 1.* ACCIDENT PROFILE 1-4 2.0 TEST RESULTS 2-1 2.1 SEISMIC TEST 2-2 2.2 AGING 2-5 2.2.1 Thermal Aging 2-5 E.2.2 Radiation 2-6 2.3 LOCA SIMULATION 2-6 APPENDIX A - DRAWINGS APPENDIX B - DATA SHEETS APPENDIX C - WYLE TEST REPORT NUMBER 58813 i l APPENDIX 0 - WYLE TEST REPORT NUMBER 58909 1 l l i l i

.t.

l l l l t

(.. LIST OF FIGURES PAGE FIGURE 1-1 Containment Buileing Accicent Profile (typical) 1-3 FIGURE 1-2 Test Profile 1-5 FIGURE 2-1 Horstental Axis - Composite RRS's 2% Damping 2-3 FIGURE 2-2 Vertical Axis - Composite RRS's 2% Damping 2-4 4 LIST =OF' TABLES-PAGE ~ ~ ~ TABLE 1-1 TEST ARTICLE DESCRIPTION 1-1 TABLE 1-2 REQUIRED ENVIRONMENTAL LEVELS 1-2 TABLE 2-1 PRE AND POST SEISMIC PERFORMANCE COMPARISON 2-2 TABLE 2-2 IN CONTAINMENT COMPONENT AGING

SUMMARY

2-5 O it

l b 1.0

SUMMARY

This recort presents tne results of the design verification program con-ducted to qualify tne Bell and Howell Soutterec Strain Gage pressure Transducer (CEC 1000-0208 anc ecuivalent models), and the Tayco En-gineering Resistance Temperature Detector, RTD (190-3317 and equivalent models). Concurrent with the Qualification of tne RTD, tne Raychem Soec 4* Cable used in the PTD is also environmentally qualifisc. The tests and analyses were successfully comoletec in accord with the requirements of NUREG-0588; IEEE-323, 1974: IEEE-344, 1975;-AND other related in-dustry and government standaros. The test program results provide verification tnat these comoonents are capable of operating in an accioent environment, (in an aged condition) with sufficient margin to satisfy the requirements of 1E Safety Related' r Equipment. Each component tested has demonstrated a qualified life of ~ 40 years', with the baseline environment being 104 degrees F, and sea level ambient pressure. The description of the comoonents tested is shown in Table 1-1. t TABLE 1-1 TEST ARTICLE DESCRIPTION Item Description Drawing Numoer Serial Number 10624 Pressure Transducer 105B025 Rev MTD 1050005PS Rev 012 Raychem Cable 1050005P22 N/A The test program included all aspects of aging, radiation exposure, seismic testing, LOCA test, and post-LOCA operation. The details regarding specific test procedures are presented in the succeeding sec-tions of this report. These components were tested as cart of an in-situ hydrogen analyzer system where each performed tne system functions wnich are identical to tne sample system functions. Specifically, the cressure transducer, powered by the microprocessor, monitors samole pressure and provides an analog inout for converting partial pressure to concentration. The RfD monitors sample temDecature and provides data for temoerature compensa-tion. 0 1-1

l' l 1.1 ENVIRONMENTAL SPECIFICATIONS Tne environmental levels useo as a basts for the test profile are summart:ec in Table 1-2. TAELE 1-2 REQUIRED ENVIRONMENTAL LEVELS Parameter Normal Accident Temperature 70 - 120 Deg. F 210 - 300 Deq. F Pressure Atmospherte 14.7 - 70 psia b. u n Relative Humsdi y 50 - 100% ~ ~ ~ ~ 20 '-T 1007. J._g ff : Radiation (TID) o megaraos -- 200 Megarads Chemical Sprays None Borated Water pH 4.5 - 7.5 The required accident temperature - pressure profile is snown in Figure 1-1, Typical Containment Building Acetdent Profile. 1.2 COMPONENT PERFORMANCE REGUIREMENTS Eacn of the components is required to perform within the tolerances listed below in order for the Hydrogen Analy:er to accurately per-form its function of monitoring Hydrogen concentrations in the Con-tainment atmosonere. Pressure Transducer cerformance at any given temperature must maintain an accuracy of +/- 0.1 atm. Deviation of performance i as a function of varying temperatures is automatically cor-rected by the Analyzer Microprocessor. R3 performance as determined by the resistance change with temperature must maintain an accuracy of -/- 1.0 ohms. The Analy:er Microprocessor converts the resistance measure-ment into engineering units of temperature. Ravchem Soec 64 Cable must witn, stand the environments without causing pe*formance degradation ~in the instruments. m 5 1-2

l FIGURE 1-1 CONTAINMENT BUILDING ACCIDENT PROFILE (TYPICAL) i 55 ' X=@ s"i@i4!H'lHhWiditHliiHUl!!ilillllillllllbillilllliljlfijilllMillllIlllEUi$11 m -4=Segi titili;gitglifilll!nli!!.l!3ikiillihillhlliill i lllllllllEl llM 1ll1111111ll1111llll111lll lilli 1W1111ll1lll1N1 11 litiliiihtii!!iiia =: w 2,p:"c,it:gpg!,;mdg7"!jjjjjjj;]jgggjjjgll j]l[] gllllljg[yl[]llgl l((jj gl[ggjjjg ))]gggjg;lm-;n 3;;;;; .,qr . < :,, px;gipe;p;g;gjg!.nii!!ggigmtMM MIMMMkWWH E EMEN MeU4@i i LIFMi';;; ;dlWP idllGlEl!"i!LWilIF Imim Illll NHEllHBlliir!Illilthii" i

_,_Od
.g " ng':'"'"Un:!P!Mu!!!!!!Ill!IlMililllillHI IllmgMlllill llilll W l g m m !B W 9L MMM UlllEllilllllilMlil illMEliH9Lni i31b W

u 'i-J: t 1 m! d w S!L -Awn 2=-qm$kM;",dssmleggm liggglighq-g= 3 _ :;;n: n - Q %;iwilllHl; ~ ~ ~ lihiilittilillllMlllNMElli!!Illlllllli';TdGMain;5 j gggjggj;lggj;;;;;gg];lmi,ij w,g, ,,,;p;jggini,,,,,ay,,y, 1 em - T 1. C. Hi"1"'PMr"mEFl!VililN!$illljllHmilllE!iEllllHIHilllllllllilllllllimilllllliMillhai M E j At !!T uC NMC,1!!Lf"!!DM!Mit!!kirgilillil!!illfilllWillllMMh11M - - t 7% gey z;;pggnpgpMlllimin unmmumunmnniiMMMHHMlHMpMMMm>fl e,: g s y.a. _, _ ;-"v.:- qu,,3 mig!;il!!#dMlll2MiiFFilN!hillillisillilMilbiliiWillimi!!!c iic 3 MllligIEiEl1 i2Mi=:n m i i 2 '- 4%!WildliklllR![JHMihiEliNGiWilllilllhlllEh11fmilli-ihiij L - ir imighggt. -_._ !!s,ijl!!31dBEIDilE. u moty -3 Jr 7 1. i.m MllCll!!!dhiildiiTililiiiiiiiliilii!MIMilDMllEllll lh!!nilBlihillilliiga i* : ~

a Ju
E -- md i"

$!:lk!!ii:illiZ"!llGiM2!UiMIi!!Ni uitih 11:n11:11111201r 4 l l Wh i t R " E Miluil?mbdi!ipLMl!!iiliSimlhSiiidih. ti;IWlllLM fd i =M Jg;;;;;;;;32ar1!!!,iiWilillhiiilliMht410!IllilllhlDiliblilbillii tullhhihiUldill!!!!Illlilil@ i'i - i f in. 4.l: 1:H'Z:Gi,u!IM';t'wh!!!!!V:lkli !Eb tNHillti!!iimiilH2:lithlMiitulgs= sii 1... : :_:u Tri ns:w. 2 9

. cdr=L:!M :'P -@iG!'Wuliill"M%Id!Mi;lulil311lilMktihiE')llllillilli!UlE21ElllMitMfid!!i =

d i i ni= ass: m,"

g g;;g yppgig gingggg g g p 7 7 gygiig gg;g,.;

l iipeirapwm;ha,,= Jam;:cacmhimH;il;;riidilliliimlidillllilill m' i inilillliila, i im ilmig11;iiim;" E i' U;i!!!UlMlimIME pi.. Anhishi2HVa. dElIlW!!!HERREREDIRi! .,,c= -= m. I l-3

l I. : 1.3 TEST SEQUENCE l In accord witn~ tne recu:rements for cualification of equimment fer Nuclear Safety Relatec use, the cressure transducer anc RTD were excosed,to a series of envtronments which included: Acceincated thermal aging cycle, Exposure to gamma radiation, Seismic test, LCCA test. Between each of the environmental exposures,.a test _was perf5cmed - to verify that performance of the component had not degraded. In mic.and LOCA -tests. ' - ~" operating during_t,ne_seis- --addition the components were cowered and = _1. 4 ' ACCIDENT PROFILE The test profile (Figure 1-2) is configured to provide test tem-peratures above tne credicted accident crofile (Figure 1-1) to reduce actual test time. The basis for cetermining the ecuivalent test oeriod are the thermal acceleration relationships presented in the Arrnenius ecuations which relate activation energy (a reaction rate coefficient) with the temperature differences between actual test levels and specification levels, t The activation energy defines the rate at which materials react with their environment. For tne analyzer system, the lowest ac-tivation energy found ts 0.78 ev. Using actual temperatures and tne Arrhenius ecuations the ecutvalent test times are oetermined. The SCE requirements for 116 days of equivalent operation were achieved at the 29th day of testing. The LOCA test log in Appendix B shows the detailed cally corrected tabulation. The first 24 days of test time was accumulated at the Wyle Laboratories Norco Test Facility. The report by Wyle is included in its entirety in Apoendix D. At this time the test article was moved to the chamber facilities at Exo Sensors wnere the test was concluced after 56 days of.est time. During the test period. hvorogen was added to the test chamber to verify analyzer performance. These verification tests were per-formed on a weekly basis. System calterations were cerformed at 30 day intervals to re-align analvter performance. Out of tolerance readings occurred immediately following the LOCA transient, at wnich time a caltoratton was cerformed. Otner cal: orations at 30 days were sufficient tc maintain system accuracy. ~~

c..

1-4

f..$f; F CURE l-2 TEST PROFILE n*

~ i -- ~ liE= I h n j llll Mill 3!! !!WI!!! I!!!1li!I ll Illill!!Il.. I = l l 'H r dl N! h , f,'.'.Y.A. NdeseeTJ.ii assissessaan h . b b l t ' I' i N I 'g"Y ' if ii.' iiii II I ill! g llii th iiylljijjiddliiii!d $! !!ii :i : i %E A U, it ' I W P" i mi i 4Mu t r i r m... uniij i: ~3og.n n g; p NI .s;g: I g i..l..i }l l if-g I! t t'tilities:fiffff*f117 ' a :s J,] in.

t l l L

.ll&j I. li i e i. t 'l ]j ji } l lll l" { 'U h M" y,2 th h [jg l ] /Si! F11lQ f ayf L -l p j g l'"' i n "S p ni un u i, mr nomunerim o <ir. D M @.W ii / l J I;l!!! il IH '. l .i'i 5ht.!' im i L iti + en' s.w, mun a ww +=

hun.n'r w g.gt

'i W1 hi i t lil;Il Il lh, lil mi hr m e + k %n i. rii l i I I" W vk +' ""m o, "hm a n i i ci m "" m i m ni 4 . w Mi h&m il. i i M 9 W ~"" i e ! lb J I L II'gl im E tiuiti e r if - lit i i l l - N"4 5 5 # 4 M I #i! l lt i 1. Is I d! fi5 M"" N . C' L E' "illliliftf7 M l I t l iiii h ! N I B ~I .Pg hh Ij! [_ I l:i ll. m' I tlI ~ ' l i !!anomt a' re m' ' -s i b. ii i 'I l I; i f y 11 I..===i l l' !!!! I'll?r ig Ig i I"'r' - ' 11' ml 1 n ' li:l. y . qli'li! 'ilINIIll! Il M IUN i l liii lh ill !H 1,; I l g l l't "lI" P t i j 'i l W W i I W . M ,J i .l lil!g $ u !!!lI - N f a i: i-g N'iI, y .-.r. 1)T'Mttiil I !Rt ii ,D. N

P m' I

Ull Ni1.iisit6illH w i n.m. r n 7~ urnamm n i. ! ill, [ , l ,3

gj

.y . l {}((.l 'm Nil..I!!! '!\\ I dj ']il t ,.y a I 1 il i 11 !! 11 i. = 7 -Oi r- .g 22._7 ' 7_.* P mum.e g .m t _g.i 1-5 --,--,___,,,,-en- .--,-w-,-- -,,,,,m.

2.0 TEST RESULTS Botn ene pressure transducer anc RTD successfully massed through the test cycle. demonstrating cerformance within the spectf: cation limits. Data sneets for tnese tests are in Accendtx B of this report. The Dec-formance test procedures fer each of the components are also included to support the results. The taeulatton below summartzes the environmental levels for eacn of the tests. THERMAL AGING Baseltne Temperature................. 104 ceg. F ~Cimiting:Matertal/ Activation Energy (1) 7 _ =? . r .. Pressure-Transducer..............Ecoxy/.90ev ~ +. .. r R T D.._. c._......................... E c o x y /. 9 0 e v ^ _ Aging Temperature.................... 275 deg. F .._ -- -... _. D e t o n d : Aging.................... 18.9 days ~ Qualified Life (1).................... 40- years RADIATION Tyoe..................................Co-60 gamma Dose Rate............................ 5.3 megarads/hr Total Integrated Dose................ 60 megarads Equivalent TID.. beta & gamma......... 200 megarads SEISMIC Resonance Search, Sinusoidal..........See Report Five OBE's. 8: 4xial................... Excerpts From one SSE, Biaxta1......................Wyle 58813 LOCA Temoerature (max..................... 306 deg. F Pressure imax)....................... 70 osia Humidity............................. 100% steam Chemical Soray........................pH 4.5 - 7.5 I ....___..-._,.,,.._..1

.+ -

=:..= ::::.:.: ? m z -- - -- - - r ~ ____ ' References (1) EPRI NP-1558:'A Review of Ecuioment Aging Tneory & Technology, Project 09-1; Sept., 1998. ~ 2-1 ) r..., l 1 1

I... 2.1 SEISMIC TEST The components insted in Tacle 1-L were tested at tne Wyle Laboratortes otaxial setsmic test faciltty in Norco, CA. The com-ponents were configured in a tyctcal in-situ analyzer configura-tron. Tests were concucted in accorc with IEEE-344 1975. Prior to inittation of seismic testing. the analy:er performance was; verified.in accor= wtth. Procedure EXC-QTP-CAMS-20. Rev. O.

n. -

- __~~ ~ ';Tsit yydrogert nalyzer :mmmanentszwecelsecarately installed in a t A ~ .Z_... ..tes t fix tur_e: sin-a-mannerfreeresent Eng'Jthe end use-configuraeion. i[~ J- ~ ~ Th eZEoTap o s We.~- !t R S isiu sedjafQ egir o d uc ed and in Figures.2-1 and 2-2. =.= : u _. ,.:::::= = :: =::== =.:=-. w = = ~~ ~ i Arislyzst =coegat1anEaytevidenced-b9.ithe. analog outout;;recerding wer'e satisfactory during'lal1 phasesTof.the seismic test. Deviation ~~~ from. nominal output did net.~. exceed 0.05 volts and no alarms were inttiated as a result ofEtheJ testing. Data after setsmic snowediall performance to be within specifica-tions. Soecific compartsons.are snown in Table 2-1. TABLE 2-1 PRE AND POST SEISMIC *ERFORMANCE COMPARISON l Lamtts l Parameter l Pre-Test Post-Test 2 5VDC H2 Concentration 0.2 VDC 0.2 VDC 0 Analog Output 0.1*/. H2 0.2% H2 0.5% H2 Display 0 Pressure 0.9 atm 0.9 atm 21 atm Temperature

  • 57-F 74*F N/A
  • NOTE:

Reflects Ambient Condttiens Fihal inspeciton'and-tist ~ sneluced a ft.nettonal test. All system ~ op'erations~wererw i t h rn? s.;p ec.if.i c a

t. 'o n. '

TT k. d h- ~ =z . w meam -.- i^~ C T- ~

533. _-._-.f ?. =- : ::- a= ---

~ - =.= =. = ~ -.. -. - ^ 5;3.. _ = _ - - ~ K ': ~~~ -~~.:.:;_ _ L^** ~ ~ t::.; v.- ~L=~____ ~.. _ -~~ -= " ~;33 3;. _ L -.._ Z.'~ J.L . s . ~ 2.. - ' :~ ~ ~ ~ ._,._.;.~~~~. . - *. T T_'"'**"~ '. ' _ - ~ ~ ._- ~ .. e ;.-..,

n. -,... -.

~ he%% % MN N P' 2-2

.... - - - ~ ~ ~.. - _ -.. - _ - - - _ _ ~. - _ _ _-._.. _ ~ _. _.. _. -.. _ f 54813 asponT NC l M M SM M & SWWWWs3 Sepp, 2-4 6 NM N N pg m.ma REV A FI G tE 2-1 EORZ3 tar 54, AX:s - COMPCSITE RR5'S 1 24 Damping i 4 . e e ,e. . e a, . e e, e...,, 1 i g T s CK. aww._ A h 0 .~..~. e.+ n. i.m, g ~.: ^ _ :jL 3 J..~' ^ 't 3 i f gg j COMPOSITE RRS g 4'. 3 e I e 4 O r 2e 3 L 1: N GENERIC RRS 9 8 ? ei. 4 l l' I 3 1 ).~, ' :~: ~ ' f _ d S

=

55 '. b'.

  • ~.

l g."...~.,'.'. j

e...C ( ~'. -.

c ,g, ( ~ ' *.* 'g. s. ....-]* l h -~ l _- .....~.~.l~_ ..as' Ices i . _ los. 2 se 2-3 '"- l .s. . - -,. - -. - ~ ~ - -. em..

4 4 I 58813 o neous um M useneseus sammeneammesaseuvuemeus 2-5 wumswcremances moscosacam REV A ) 1 FIGmtt 2-3 vrartcaz. Axis - couros=z nas's 2t camping I .i i ... r.... m. l, 4 ,. l. I 1I., e' i l i 1 I i l i '..1. i .4 h... j,' 'lI .l..l., ..,I I ,I ] J i .i .i .,,.i..... ( /A 8 I i g i h a' j i a I j 1 i COMPOSITE RRS 4 l i i \\ l l 1 GENERIC RRS \\ ? j t, 8 ,i i 8 I l L t I i I s l 5 l ..1, l I i.I i.I. l l l . 5.a : m. 2-4 l..

2.2 AGING The major aspects of,agtng for the in-containment hydrogen analy:er components revolve arounc tnree constoerations, namely accelerated enorm41 agtng, accelerated operattonal aging, anc radiation ex-posure. Tne in-contatnment components are cefined in Exo Sensors crawing numeer 195D005. Hycrogen Sensor Calibration Assemoly. The bants for defining the aging environments included the specifica-tion recuirements for temoerature and ractation, and the coera-tional cycling of the inotvioual components antteipated over the i life of the comoonent. The pressure transducer anc RTD aging status at the time of tne loca test are shown in Taele 2-2. l TABLE 2-2 IN CONTAINMENT COMPONENT AGING

SUMMARY

EXO SENSORS DRAWING NO. 1980002, REV. B Component Name l Ecuivalent Age Radiation Level i Pressure Transducer 24.1 years l 60 Megarads RTD 24.1 years 60 Megarads i 2.2.1 Thermal Acino 1 The masts for thermally acceterating the aging of components by controlled exoosure to temperatures aoove the normal opera-tional levels is presented in the 1980 EPRI Report, "A Review of Ecuipment Aging Theory and Technology." Section 4, Theories of Aging, presents the rationale bentnd the two major industry practices for determining accelerated aging conditions; namely the Arrhenius Model and the 10 cegree C rule (whien is a special. simplified version of the Arrhenius Model). l l The Arrhenius Model aging is based on estimating material stress over a limited range of conditions and a ceterioration or failure, based on the physical or chemi-i cal processes taking place. The stress factor for non-i metallic materials used in these relationsnios is the Ac-tivation Energy of tne material. The general form of the 1 ocuations acclied to thermal aging is as follows: 4 Arenenius Model: L=BE*'** (Ti-7.1/10 10 degree C: aq= C2 i where L = time to reach a specified endocint or lifettme. B = Constant (usually determined experimentally). l 2-5 ,,----.--,nn,_, ,-v.-,nn,v--n.n,.n,v, .-,,,.,-,---n-w,,,,-

activation energy (eV) o = Soltzman's constant (0.00008617 eV/K) k = 1 I = Absolute temperature (V) The specific reaction rate oc/dt = C - constant determined by experiment The aging calculattons are summarized in Appendix B of this report. 2.2.2 Radiation Components were exoosed to a Cobalt-60 gamma source until tne prescribed radiation levels were acnteved. These levels of 40-60 megaraos of gamma exceed the specifica-tson levels of the total beta and gamma spectrum ex-Docted, and serve to provice a significant margin for operation. 2.3 LOCA SIMULATION i The LOCA simulation is described in detail in Aopendix C. in the Wyle Test Report. Analycer evaluation during tnat period showed the following cerformances uoan stanili:ation of chamoer temperature at 270*F and 39 osig, hydrogen was adoeo to the chamoer for verification of analy:er per-formance. Performance verification tests were performed showing overall analyzer peaformance for the 60 day period remained within specified limits of +/- 0.2% of actual hydrogen concentration sn-dtcating all components were within operational specifications. I t i 2-6 i

= ? ,I a .a.,pp er.a-

  • f 5

4'. ) =-- f s f I f ] o r j h s% 5 i m 5 t I, 5 I e s -c,-- ,,,-----r,--wg-w+-,.,,,wna,n-, ,,nw ,n,m ,-~=w"m w'w~~~w~ ~ ~ - ww'-- v* n w- - ~- ---vw-~-*'*-< - - ~ - - - * * -

,, m n a e m E i m g e$' x a e ,w % n }m g (8 t = c a, g 1 Q E i l f M e P s ~ ({ t i l h[ s v g:j;i; a i l t j n e . m. ~ l s t g l k, k N

  • o4 1 4

!! { l g H B k l i g, R t s y [ ij ..k! $9 %'k)l!Ilill!lh!11 7 lll

r-- I ..L. si } gjl M, 9 Tid__ll $, d i u I S t M l 5.f! 3 Ind l a s t - o I % h' q b l g\\I ~~ I,- I f ifh e i 3 i 1 'a i- ! !I! U R j [h j l f

i. !

+1 -e y l,

i in Ar

% !d l' pd $ )., l l '3 N ih,l o. 4,. -f 4 3 % p w.s d $$ h g) M... Q 8',y sfij pah U g.1[ !Mk".l} y l__.._. g g _l N1 t h 3!:$hgs.WA 1 -p= i / h...iEnA;;JJwg .~ u p / / b f$.f I 5 6 kr}itO P U L t i J l 3 If h h ;h m. G md 8 4; W. y,, a p. th y m = y p, p 5g,.. ..m. , n n ,E e u s. n p. j.j gle si s ii a l J lg { / i s @;; p < r

  • h II N

3;yl 3 l3r ss 4.p r Il ol1 I ' i eh. u..; 2 3-f r a. 1 d* 5 / / y

  • D.a. W p*

l e U, p 3 j 1 k, f,p u f I k $ M.f$n,b.i] I i o NI$j N MJ a: 30_El1his g p

s['

1 ..n a ll tdh u s

48) ; *44 4

<q f} d-g ~ r s ti s / / ..f.) / b- / ^ ..,u. .w,,. ,,.w.. m**~'

    • ~-'
  • no.

c es,. .o

  1. -+

e. . - -... -. ~ - - - w ~'**^]~ .c.S u r- ,;.47. ---.,,.7-. --2 q.i c:. j~ j 7 ;q 7, g, ,,_,..,,,,____,._____.___,-_-.,w_..,.,.-_m.m, .,.,_m y- .-_.._------..---.,,,.mr.,. 5-_.____ y

RTD ENCICSURE WIRE LIST FROM CONDUCTOR I.D. TO (CONNECTOR ) E Sens r (+) WE/BLK 1 2 E Sans r (-) WE 2 2 RTD (+) WE/BLK 3 RTD (+) WH/BLK 4 RTD (-) WE 3 RTD (-) WE 6 P ~ t (-) WE ,8 P t Ground GND P -B (+) WE/BM 9 t P -C (-) WE 10 t G1, G3 only --em neouse I nei t =n3 use y " L =,- y A- - = se. "'"") Ai,emh men an== o,.. u = c esses =euu= m"i R7~D KMC40$UAt ~ f s

== = um w assaav e 4 y l a = =. -.. m ,es .:pA q u '.m '/,ro,,y 3 = ,as x - m,n-s ,m =. - t=- I=== 2 oc a g I

g g aivess s m . sn e.uamem ~ ~ ~ ~ 4 .nemme l

s,.-

i.it a.. ies *is 0 s'.. ii.. sp.g ( .. s I N r, s. 4 .I s Og i 'j i..A..e 's Aiest.e.g.e ss) I: 'l 'O' Cat r g .F -) m .31 ~ i II[ d I t.i I. * % A tif.! 1 .s.*- i. j ' $m ] *

  • I "' 8 '* "

\\ g .g,g 8 F-1 4 / N t-i .1 A ): l l e/._ -. 7-( 7 ...r i-(. t ' fy. 6...'vaast) ,,,,g.. f ...3.*.* .:.n a., n. - . l' O l.4 . O. s bis '.i < !).. I A i \\ .....sst...:. .Ios:..et ..... a... i 0 ,,u s' r I I l wn Itet AC.t-( l l wHilEIN ACn l l buGfAllC DIAGRAM.. S 1 1 I -l 1 r,,l L. l le ..... m it..... E..Es * "** * "wu 1% .IP.a 803 I se . (s *

  • J. ag,,ih J

.q Q Ou ll.lj[ !.*n.:. gr.iar., y.. * * - TLI 4. I FAII?;l,UCh., A batch AC.be.. a 9 M. 6Z.'.45 ems Ares 888 81 5 .uus se e g C 50422 ite-!!?7 siriria une C/ F. i..e E Te51..

  • er a 4

1 3 t 2 I i

9 l J h l S 8 Of v4See S 4 e. 3 AI .. i-5 I .I . st

  • 4..

i ) 1 a i e l t i i 1 l .a 1 i k ntB1044/il Ed h'A>ikibt} 'et lost b a s' 4 LEAvi .%210 ,}** l e qgq'.'s k_ I

e. x l

c. I 5 i i I .p...-803 ?gDO.- n . r is<. - - . n., q ? I g I* ) 1 l -. --...vna s t ~ .._n,,.. g l3 ':i < =, i l ; I. -[ l g4l l l l?" e. eseuwi==

= = =

woo *== asse or esanassats - - - - - - - t *s si / ss M A umass ee eemes so.se esse c. I

    • 's*"**

NarNg 994) ea s v roIi.'ist MM esa me a** Gen *e (iilEC =.r a,,;-.

. :~'

% - m... se OUTLINE l ~~ m'n w'~' '%,,2rn za 4-PLATINUM RESISTANCE A . :u u nt" n:.sa r ?., an-4 TEM,PERATlK TRANSDUCER ..s.,, y ww.r sa. m i c 50422 180 -4028 a eCa68 2/ # htdaad east hsg 3y l 4 l 3 t 2 1 1 4

1 i I e A.*

..! t..e. *4 y t.:

r o 5 0 e t.- s

i ,- l s, th APPENDIX B This appendix provides summaries of data for the pressure transduccr and RTD used in the LOCA simulation. Radiation Certificates 7 Detailed recorder charts supporting these data are available for reviev ac'Exo Sensors upon request. s. 6 O e e a 9 / 4 9 3-l " ~ ' m-ow m ,aw ---sw,--n-,- m-wm-----tw-wr-__mgw-g -m- +-,mm-+mw -vp-mr*pgm-w--m vme w-yww,---mae--y v-m,m-m

, ~ ~ v. COMPONENT: Pressure Transducer /SN 19624 Ex0 SENSCRS P/N: 105B025 SUPPLIER: Bell L Mowell. CEC Div. SUPPLIER P/N: CEC 1999-0208; CEC-1000-04 (Transoucers are identical, electrical connections are equivalent). ENVIACNMEN*AL QUALIFICATION THERMAL AGING Age Sensitive Component: Epoxy Activation Energy: 0.78 Max Aging Temperature 275'F Qualified Life 40 years Normal Operating Temps 194*F RADIATION Total Integrated Dose 6x10' RAQS (Gamma) Facility: Radtation Sterilizers 4 Exo Sensors P.O. 2001-7 Date NovemOer 11, 1982 Qualification Level 2x100 RADS (Seta - Gamma) OPERATIONAL AGING Total No. Cycles: N/A Eouivalent Age SEISMIC TEST Facility: Wyle'Lacoratories Exo Sensors P.O. 1144 Date November 12, 1982 Report No.: 58813 LOCA SIMULATION Faciltty: Wyle Laboratories Sample Temperature 310*F (max) Samole Pressure: 72.7 psia (max) 23-2 ..._.__,e.

s o s I N. g t I ( COMPONENT NAME: PRESSURE TRANSDUCER MATERIAL: EPOET ACTIVE ENERGT TEST TEMP TEST TIME QUALIFE (EV) (DEG. C) (DAYS) (TEARS) i .78 135 18.9 43.51134 3 s i s 1 t Aging Sunnary Component: Pressure Transducer Serial No: 10624 The following data are sunnarizeo f ra the original temperature recordings: 9-22 thru 9-26-82 278-292*F 9-26 thru 9-28-82 290-295'F 9-28 thru 10-11-82 275-290*F Total Test Time: 454.25 hours (18.9 days) Minimum Test Temp: 275'F l l t 3-3 c u

COMPONENT: RTD/SN 012 EXO SENSCRS P/N: 105D005P8 SUPPLIER: Tayco Engineering SUPmLIER P/N: 180-3317 (Ecuiv. to 180-4028, difference is in diameter of housing, 3317 is 1/4"' 4028 is 1/8" tuce). ENUTRONMENTAL QUAL!FICAT!CN THERMAL AGING Age sensitive Component: Epoxy Activation Energy: 0.78 (Ref. 1) Max Aging Temoerature: 275*F (135'C) Qualified Life: 40 years Normal Operating Temp: 104*F RADIATION Total Integratec Dose: 6x197 RADS (Gamma) Facility: Radiation Sterilizers Exo Sensors P.O. 2001-7 Date: November 11, 1982 Qualification Level: 2x198 RADS (Beta + Gamma) OPERATIONAL AGING Total No. Cycles: N/A Eculvalent Age: SEISMIC TEST Facility: Wyle Laboratories Exo Sensors P.O. 1144 Date: November 12, 1982 Report No.: 58813 LCCA SIMULATION-Facility: Wyle Laboratories Samole Temperature: 310*F (max) Sample Pressure: 72.7 psia (max) f.(T-I sY

GMPONENT.NAME: RTD MATERIAL: EPOXY ACTIVE ENERGY TEST TEMP TEST TIME QUALIFE (EV) (DEG. C) (DAYS) (YEARS) .79 105 18.9 40.51104 Aging Sumary Component: RTD Serial No: 012 The fr.:;. wing data are sussiarized from the original temperature recordings: 9-22 thru 9-26-82 278-292*F 9-26 thru 9-28-82 290-295'F l 2-28 thru 10-11-82 275-290*F ( Total Test Time: 454.25 hours (18.9 days) Minimum Test Temp: 275'F m 3-5

COMPONENT 3 Electrical Caole EXO SENSORS P/N: 115D330P113; P114: P115 SUPPLIER: Raycnem SUP* LIER P/N: Spec 44 Wire ENVIRONMENTAL QUALIFICATION (In conjunction with RTD) THERMAL AGING Age Sensitive Component: Polyalkene Insulation Activation Energy: 1.10 (Ref. 1) Max Aging Temperature: 275'F Qualified Life 40 years Normal Ocerating Temp: 194*F RADIATION Total Integrated Dose 6x10' RADS (Gamma) Facility: Radiation Sterilizers Exo Sensors P.O. 2001-7 Date: Novemeer 11, 1992 Qualification Level: 2x10" RADS (Beta + Gamma) OPERATIONAL AGING Total No. Cycles: N/A Equivalent Age: SEISMIC. TEST Facility: Wyle Laboratories Exo Sensors P.O. 1144 Date: November 12, 1982 Report No.:' 50813 LOCA SIMULATION Facility: Wyle Laboratories Sample Temperature: 310*F (max) Sample Pressure 72.7 psia (max) kW G h-(j

i \\ i I i Aging Summary Component: Raychem Cable (With RTD) Serial No: N/A The following data are sunnarized from the original temperature recordings: 9-22 thru 9-26-82 278-292*F 9-26 thru 9-28-82.290-295'F 9-28 thru 10-11-82 275-190*F Total Test Time 454.25 hours (18.9 days) Minimum Test Temp: 275'F e NE s 3-7 ..1... .m _m c e 4

CERTIFICATION OF IRRADIATION CUSTOMER: Exo Sensors, Incorporated IRRADIATION RUN DATE: November 11, 1982 IRRADIdTION RUN NW18ER: E2D 2001-T MATERIALS PROCESSED: NO. CTMS. DESCRIPTION LOT NO. One Unit RTD Enclosure - DWG #1080007 which includes RTD #012 Press Xducer #10624 Radiation Sterili::ers, Incorporated cartifies that 7 this material received a tgtal iritegrated dose of 6 x 10 Rads at a rata of 5.3 x 100 Rads /per hour within the accuracy of the dosimetry devices utilized. O W 1 Onta //- //- P.'I. 1 3 -:ir n' Hilation Stortilzers incorporated,14o1 Morgan Circle.Tustin, Cattfornia 92880 / Telephone (714) 730-0811 }.; l

zsa rrsr zos d'. j$# ' B47~? rw-,' c .s rtep Azc:=t.wi lf'C tt.S, L. ) c; ,o :,; 4-t4-84 /000 0 7c; .C D /0:7 O Job ' 47c.o /st:0 0 /.SC Co /S2f' +.1; ::r= 3/O

  • l9.-57

/533 + 2Sstae 508 .52 - s* 7 /9s/ 27z.5 45,j $-t 7 /c /D.? C-6 i , ;; ~: :.,

  • C/

5,' 200, ~ 'a =- S? l5':10 ic;? 205.1 10. c-2 irse. j : :.- //d.t) 24/.:/..i- /. ' 5 /3.. f .r ! ] 2 3Q .%i o .~4 (#7.0 ..9

/fi.;,'OVE N%Y Hr6M

,"D.*!<0 i 4 c.. w,:.ii.d k - ic ,5,,i;,,,, <. />1 f a, >,. z. ~ -% /w &1u /, -- f. - - An. ci sn v. snc-awer.w('a:r n,;;. c-, ine ;;e,,,d. m....- f _. _ _'y g.,,,,,, e. ) Q } ?';s?c'g ' ff2p..p.) f 'y ff ; f

re s on : - r,

.s

g - 2.- toen n.= r w ~hm 7, m ; A's M t/= '~3 fr /= Rics:vad Q'o an<l:) p.srG 5-// 54 ( f 22.) o '# 6.d E-l.7 ..-l 5 b 24 (~f7 2-) /80 sb.i S-t6 c[od 25 ( /M.9) /e/ 60 5-13 082A 24 (loy7) /8/ / 25 l 27 /61.3) /Ea A. 20 i 5-12 N '/[* 2i ((It2.z) /f/

f. zf

\\ C-t 9 /000 s~-20 Zf (*/tt,.o.) l?/ ~ [ ~L/ //bd 36 (/192) /Eu 40 5-z2- //Do 3I (j23.G). /2/ 5 22 //Sc Ol% erd &t o*Cf6 The!N Atddl Oni, A<iid*CE 77 it P. 5:2 ::. mo fasina rasr wi,w zp...n paao r>,uww.. .5- & 2l00 Al (125. fa). !30 5 - z'5 09co ?.2 (/z7. d) { / --5 }-7W Og([ l 3CO + (.?aA!T3%;LLEl'. c>ICt.r2)* C 2d 5 b~ l .S.+u ~ p e w a Rx enes e ew-n.c w e w f e e n c e rrosv.: f /7f S-/ /70c Ik f. z. l ~': !5 (l3. v)l /Ec

.' ? w.m

/.* d tre? mn va c-3 C'I@ i 0.5bll (.. 3 C *.50 ..i /j~r - ! ? ' 4J lc co 3r 0 9.! *; !e 01;.t) ?c

c. - S 1E00 36 (fat..s);

~ & fa I?ec 59 a~ e- .?%: st . rs.v;; i-t

c. -r 53 tir.6

.c a.~ _,10. g.a a.:. I l l u t. je - t. .(.C J i f-f / L., - (.:.L*.<& V t'C 0 7 ! ! Q.,,,: - / [<.) -~ I ~ a. w.a., 5 2 2 : ! } ? eg: 'A. a. : e .' C I.-- ~ 1. c. i l Lr**- 19 ' ry ', yi .!,;.ii'c 4.it. 4.1 V: f i

  • ~ ~

5 j? 0 &:'" 50 - 5 :.G !l

  • ?

v. 'ac a l n o ... ~ m t 3-10 i i

e 6 August, 1984 ENGINEERING. INC. Exo Sensors, Inc. 1220-B Simon Circle Anahien, CA 92805 Attention: Mr. Jerry Fuller Engineering Mgr.

Subject:

Material Certification

Reference:

Tayco P/N's 180-3317 and 180-4028 Gentlemen, This letter will serve to advise you that all raw materials used in the fabrication of the two referenced part numbers 'are identical with the exceptions of those materials listed below. COMPONENT 180-3317 180-4028 Stem 304 CRES 316 CRES Thermal transfer PQ Heat Sink Compound Dow Corning 340 medium per TMS-1015 per TMS-1006 Braze alloy (not used) AMS-4777 I The TEI specifications for the two thermal transfer mediums are to be found attached. Two copies of the outline drawings for each of the two models will be found enclosed. If you have any questions or comments concerning this matter please contact me directly. Sincerely, }!s/}NWs ~~ Hal' McAllJ. ster Program Manager a r. , s ~ HM/mh ~3 il zee.

  • P,0. SQX 19
  • LONG SEACM
  • CAblPQRNIA 90402 + TELEPHONE (213) 437 0387 441 E AST P O U RTM STR E ET

.nv. c---

tzc DMeurt me e = na = w. e - ca eues.= esa rwesi.e.n.s.is.== sesems @ BELLsHOLUELL 26 August 1983 RECEIVFD i AUG2 919g3 om sensor 1220B Simcn Circle

Anaheim, N14+amia 92806-Attention: Jerry Fuller Gentlemen:

The CEC 1000-0208 pressure traraAime we have been s'-lim to you is a W4 84ed cC1000-04. The CEC 1000-04 is our se=naard high temperature (75 to 400'F) gramd strain gage prescure transducer. The #434 cation is ccmfined to the outer housing of the electrical connector j to provide an NPr fenele thread m the electrical ccmnector to facilitate the external ccnnection in your applicatim. Other then the physical a:mfiguration of the electrical ocnnector, the GC1000-0208 is the sans tran=^ tam as the C2r1000-04. Hope you will find the above informaticn helpful, if you have any further questions, please feel free to contact me. sincerely, a-l sr. produce m,4-e m/rp i cc: G. & ,+ p-/ 2, m - - - -. -. - + - - -


r-

t D e p 4 I ' e(".8#is.'- g l 4 . ~ _. + +m. d ww &v 3 a e_ Wye,.m.w. 3, = p..% - + .,g NSM*#4 N - .M&M%P "M t N e... -g ' - Q -b W a ,-#+,* A 7 N J7

  • _e O

6 m s e m%w s.rt.4i ywa y *L 8._ p '* ", _ ,.i+ ( l>t,~,, no 4 wS w_'4 y ', 3,

  • 1=..3.-

3 i. --ss.*-= 4+ = -...~ .i ~ {*[(Mp 95? see ms e S, 4 ' h 'f- ,e Y $ $5r 4

  • NW h.

~%* k/ %g g g ^ 7=% 'bOf ^ " ' Wg - eem.,#u,sr ,.r.h. 4.. ~. be e,m ,4m j

  • * ' ' ' ~ ~

a e, ep.'% W"&, h "**Y

    • , 7 4 : x p "r - g t.*.,
  • p g

Y \\.^ 2,'

  • wYh* M *+.L:

U;;7~:M nts i we, .c.- ; ^+4 4 m 14 r_-.4 dip A = s, V b 4.- 4 4 'L '396f 'td * ,.s-. .~~~.~~n.~

E .r TEST REPORT 58813 naronta ND 58813 soswnnesmrricasaavsremsoaour Gun.oswo. WEEfMN OreRAnosa.M0 ECD PACIIJIY COstrnACT YOun P.O.NO. EXD SENSCRS, INC. 116 - Page Report 23041 Alcalde Drive Laguna Eills, California 92653 3 January 1983 m c WJZON A 19 April 1983 SEZSEZC TEST 2NG .W avrentzw tar.TamavTnar 8252EE AED TfarvurnsTCS ASSMBLT rest EID SEMERS, 23C. [n _%,%g r-l I

  1. p g@

w -em DEFA2tnsINT / STATS or cAuroantA 1 COUNTY OF RIVERstDs J"" N //s,2 m DErr, w-= Itav c. Mv7iet ,m.m.,e e,,,,,,, J (AT. Anderson

        • ""***a,=

Tm : in.- ,,e i, ,, as m. es er ,,,, mi, m 7e '33YENmNEER _ P. Knou JgV gg 7 w, ~ r.z. 8, V " "

  • Glozman agmMIER V

1 > a, y:Jerreen.4. es., c W c= % ,, c.s,,,, , i, 83 was m. mm erm V e -.o m / CATHERINE C KETY g[M tm acnnser rueuc-cAurcatessA N AEEURANCE_ I nutaset tetism W-867A i = mus As. p. 1ses )_ 1 1 ~~' - _, _ _ _}}