Public Service Electric and Gas Company Corbin A. McNeill, Jr.

Public Service Electric and Gas Company P.O. Box 236, Hancocks Bridge, NJ 08038 609 339-4800 S:;nior Vice President -

Nucisar April 16, 1987 NLR-N87066 United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 BI-MONTHLY BAILEY FAILURE REPORT HOPE CREEK GENERATING STATION DOCKET NO. 50-354 Pursuant to commitments contained in the Public Service Electric and Gas Company (PSE&G) letter to the NRC dated October 15, 1986, attached please find the Bailey 862 Solid State Logic Module (SS LM ) Bi-Monthly Failure Report for the Hope Creek Generating Station (HCGS).

This report covers both lE and non-lE modules and summarizes inservice failures per month by class, assembly type and failure type.

With respect to the last two month period, February 1987 - March 1987, 3 Bailey 862 SSLM failures were identified that had an affect on the circuit in which they were used.

These failures are discussed in the attached Bi-Monthly Report.

Should you have any questions on this transmittal, do not hesitate to call.

Sincerely, R

i Attachment e

8704270485 870416 PDR ADOCK 05000354

\\

g R

pop

Document Control Desk 2

4/16/87 C

Mr. G. W. Rivenbark Licensing Project Manager i

Mr. R. W. Borchardt Senior Resident Inspector Mr. W.

F.

Kane, Acting Regional Director USNRC, Region I i

l i

l I

BAILEY 862 S0 LID STATE L0GIC M0DULE BI-MONTHLY FAILURE REP 0RT H0PE CREEK GENERATING STATION APR1L 15,1987 4

-o

HOPE CREEK GENERATING STATION BAILEY SOLID STATE LOGIC MODULE FAILURES POR FEBRUARY AND MARCH, 1987 3 Modules Failures - There were 3 SSLM failures which occurred in the two-month period beginning February 1,.1987 through March 31, 1987.

Projected Reliability 0.79% per year failure rate

1) Based upon data from February and March 1987, with 2 and 1 failures respectively, for a total population of 2258 modules.
2) The projected annual failure rate is based upon bi-monthly data as presented in a letter from C. A.

McNeill, Jr. to Dr.

T.

E. Murley, dated October 15, 1987 (NLR-N86148).

c

R; cord 0:

02-1 Assembly:

BC652 Location: 12 4 S/N: 0809 Fail Date:

02/05/87 Work Order Number 8701280210 System:

HYDROGEN RECOMBINER (GS)

Class: 1E Description of Failures INPUT BUFFER 2 FAILED TO THE HIGH STATE (TURNED ON)

Affect on Systems THE MAIN CONTROL ROOM RECEIVED A FALSE " VALVE GS-HV-5055B CLOSED" INDICATION.

Time in LCO: LCO NOT ENTERED Found During: NORMAL OPERATION

==============================================================

Record #:

02-3 Assembly:

AC653 Location:

8-3-12 S/N: 1023 Fail Date:

02/24/78 Work Order Number:

8702230062 System:

REACTOR AUXILIARIES COOLING (ED)

Class: NON-1E Description of Failure:

MEMORY "A" FAILED DRIVING THE OUTPUT TO THE " LOW" STATE.

Affect on Systems THE CONTROL CIRCUIT OF VALVE 1-ED-HV-2537A WAS DRIVEN INTO " LOCKOUT" CAUSING THE VALVE TO CLOSE.

VALVE 1-ED-HV-2537A CONTROLS WATER FLOW TO ONE OF THE RACS HEAT EXCHANGERS.

Time in LCO: LCO NOT ENTERED Found Durin NORMAL OPERATION

  • ================================================g:==========================

t 4

4

(

1 Rscord #:

03-1 Assembly:

CC652 Location:

1 5 S/N: 1266 Fail Date:

03/12/87 Work Order Number:

8703120249 System:

4.16 KV ELEC DISTRIBUTION Class: 1E Dascription of Failure:

INPUT #4 FAILED "HIGH" PROVIDING AN ERRONEOUS BREAKER TRIP SIGNAL.

Affect on System 4.16 KV INFEED BREAKE" 52-40301 TRIPPED FREE FOLLOWING A CLOSE ATTEMPT.

t t

1 I

Time in LCO: LOO NOT ENTERED Found During: NORMAL OPERATION

========:======================================================

.- -. = - -

BALEY LOGC MODULE FALURES For the period - APRIL 86 thru March 87 14 -

13 -

12 -

11 10 gw 10 -

tr 3

9 -

b 8 -

L.

O y -

b 6

6 In 6 -

3 5

5 5 -

Z 4

4 4

-E 3

3 -

2 -

1 3

0 0

APR MAY JUN adL AUG SEPT OCT NOV DEC JAN FEB MAR O

INSERVICE FAILURES

)

- -