_ _ _. _ _.

..v

.e N.R.C. OPERATING DATA REPORT DOCKET NO.

50-316 DATE 01/02/87 COMPLETED BY A.Tetzlaff TELEPHONE 616-465-5901 OPERATING STATUS

1. Unit Name D. C. Cook Unit 2
2. Reporting Period DEC 86-l notes l
3. Licensed Thermal Power (MWt) 3411 l l
4. Name Plate Rating (Gross MWe) 1133 l l
5. Design Electrical-Rating (Net MWe) 1100 l l
6. Maximum Dependable Capacity (GROSS MWe) 1100 l

'l

7. Maximum Dependable Capacity (Net MWe) 1060 -----------------------
8. If Changes Occur in Capacity Ratings (Items no. 3 through 7) Since Last Report Give Reasons _
9. Power Level To Which Restricted. If Any (Net MWe)
10. Reasons For Restrictions. If Any:

~

~~

This Mo.

Yr. to Date Cumm.

11. Hours in Repor(sing Period 744.0 8760.0 78888.0
12. No. of Hrs. Rt.astor Was Critical 744.0 5560.5 54589.3
13. Reactor Reserve Shutdown Hours 0.0 0.0 0.0
14. Hours Generator on Line 744.0' 5389.7 53243.3
15. Unit Reserve Shutdown Hours 0.0 0.0 0.0
16. Grous Thern. Energy Gen. (MWH) 2039056 14420594 165691204
17. Gross Elect. Energy Gen. (MWH) 666600 4531450 54218040
18. Net Elect Energy Gen. (MWH) 639201 4335567 52234836
19. Unit Service Factor 100.0 61.5 69.7
20. Unit Availability Factor 100.0 61.5 69.7
21. Unit Capacity Factor (MDC Net) 81.1 46.7 64.5
22. Unit Capacity Factor (DER Net) 78.1 45.0 63.0
23. Unit Forced Outage Rate 0.0 3.4 14.7
24. Shutdowns Scheduled over Next Six Months (Type,Date,and Duration):

Technical _Sp_e_c_ification required surveillance outage March, _1987, estimated 2-week _ durationn

25. If Shut Down At End of Report Period, Estimated Date of Startup:
26. Units in Test Status (Prior to Commercial Operation):

Forcast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

/

B703160301 B70106 PDR R

ADOCK 05000316

?DR

~

g AVERAGE DAILY POWER LEVEL (MWe-Net)-

DOCKET NO.

50-316 UNIT TWO DATE 01/02/87 COMPLETED BY A.Tetzlaff TELEPHONE 616-465-5901 MONTH DEC 86 AVERAGE DAILY AVERAGE DAILY DAY POWER LEVEL DAY POWER LEVEL 1

857 17 856 2

857 18 858 3

859 19 860 4

862 20 857 5

859 21 855 6

860 22 859 7

858 23 861 8

858 24 860 9

856 25 860 10 861 26 862 11 858 27 859 12 859 28 862 13 859 29 860 14 862 30 860 15 861 31 859 16 858 k

e IBGCKEI NO.

50-316 INTSINIIIM)WNS ANItF8MvtM REinirlM)NS INT NAteE D.C Cook - Unit 2 prig 1-6-87 cot 8PIETE8tRY

_.B. A. Svensson Rgyg)gyggppgggg December,1986.

TEtArettweE 616/465-5901

't 1 kensce Eg h

$E 3

} {E r mese A C.weetilve N e-Ilme k

3 Atesam see g2

{

ac Ewas

{T gb ah sE -

jiR g Iterene a en u rsevens Recmecence H

g 6

There were no unit shutdowns or NONE power reductions during the month.

The unit operated at a nominsLSO%

power limit administrative'ily im--

posed to minimize steam generator tube degradation.

i 1

3 4

I~: l'.=tcJ Reassion:

Seesles=l:

Enlistde G. Insesucel.wis 5: Sal.cduirJ A 1,,

^^ Faelmeilsplabel I temusal few recpmae6.m of llasa R taatssenmenceen Tsas 2 Blamaal Scsame.

Entey $4ecces few liensee r Rciactieng 3 Aasenesensec Sa:am.

liveses Nep.=e il l'RI l' ele INIINI G-In Itegistasemy Reueicseine 4 Helece IEarlanel illfill i Orceasaw isaenang & ikenw I massieseast =e l' Adesenkenaspe 5

G Oye:ase.neal la== llisplant blidies I Saene S. mice


refill II Ostics IEnytaisil

t.

^ =

  • DOCKET NO:

50-316 UNIT NAME:

D. C. Cook Unit 2 COMPLETED BY:

W. H. Kirchoff TELEPHONE:

(616) 465-5901 DATE:

January 8, 1987 PAGE 1 of 1 MONTHLY OPERATING ACTIVITIES - DECEMBER, 1986 HIGHLIGHTS:

The unit operated the entire month at the nominal 80% power-limit, which has been administratively imposed tx) minimize steam generator. tube degradation.

Gross electrical generation for the month of December was 666,600 MWH.

SUMMARY

There were no significant operating events during the month.

DOCKET NO.

50 - 316 UNIT NAME D. C. Cook - Unit No. 2 DATE 1-9-87 COMPLETED BY Be A. Svensson TELEPHONE (616) 465-5901 PAGE 1 of 1 MAJOR SAFETY-RELATED MAINTENANCE DECEMBER, 1986 I&C-1.

NLP-151, Pressurizer pressure level channel I indication was found reading 29% different from the other two channels of pressurizer pressure level indications.

A leak was found on the instrument line for NLI-151 which has a common sensing line with NLP-151. The leaks were repaired, the level transmitter reference leg was refilled and the NLP-151 transmitter calibrated and returned to service with level in-dication within required limits.

L i

)

4 I

I I

s I

l i

J