Responds to Violations Noted in Insp Repts 50-348/86-11 & 50-364/86-11.Corrective Actions:Flammable Matl Removed from Auxiliary Bldg Hot Machine Shop & Cable Blocking Fire Damper Returned to Operable Status
ML20212K210
Person / Time
Site: Farley, 05000248
Issue date: 08/05/1986
From: Mcdonald R
ALABAMA POWER CO.
To: Verrelli D
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
NUDOCS 8608190249
Download: ML20212K210 (3)


Text

r.

Malling Address Al:bama Power Company 600 North 18th Street Post office Box 2641 Birmingham, Alabama 35291 Telephone 205 783-6090 R. P. Mcdonald Senior Wce Presidant Flintridge Building AlabamaPbwer the sout"e'wwi't 5;sien August 5, 1986 Docket No. 50-348 Docket No. 50-364 Mr. D. M. Verrelli

~

U. S. Nuclear Regulatory Comission

^ I-Region II

~~

101 Marietta Street, N. W.

Suite 3100 l

Atlanta, GA 30323

SUBJECT:

J. M. Farley Nuclear Plant NRC Inspection of May 14 - June 10, 1986 RE:

Report Number 50-348/86-11 Report Number 50-364/86-11

Dear Mr. Verrelli:

This letter refers to the violations cited in the subject inspection reports which state:

"During the Nuclear Regulatory Comission (NRC) inspection conducted on May 14 - June 10, 1986, violations of NRC requirements were identified.

The violations involved adherence to fire protection procedures. In accordance with the " General Statement of Policy and Procedure for NRC Enforcement Actions," 10 CFR Part 2, Appendix C (1985), the violations are listed below:

A.

Technical Specification 6.8.1 requires that procedures shall be established, implemented, and maintained. Administrative Procedure 35, General Plant Housekeeping and Cleanliness Control, requires I

in Section 5.1 that flamable liquids will not be stored in or adjacent to the auxiliary building, diesel generator building and service water structure.

Contrary to the above, on May 16, 1986, combustible liquids were found stored and unattended in the hot machine shop located in the auxiliary building.

This is a severity Level V violation (Supplement I) applicable to Units 1 and 2.

B.

Technical Specification 3.7.12 requires that all fire barrier l

penetrations, including fire dampers in fire zone boundaries protecting safety related area shall be functional at all times.

M Dy e

i t G

i

_ leo

~

s

~Mr. D. M. Verrelli August 5, 1986 Page 2.

Contrary to the above, at 8:55 a.m. on May 21, 1986, Unit 2 fire damper penetration 05-139-06, located between the electrical 1

penetration room and the piping penetration room was not functional due to a sound powered telephone cord blocking the closure of the damper.

h is is a Severity Level V violation (Supplement I)."

Admission or Denial W above violations occurred as described in the subject report.

Reason for Violation ne first violation was caused by personnel error in that there was a failure to properly control flansnable materials.

he second violation was caused by personnel error. %e on duty shift supervisor was aware that a fire damper was inoperable but failed to establish the required fire watch.

Corrective Action Taken and Results Achieved 1

A.

ne fla==ahle material was removed from the hot machine shop on May 16, 1986. No additional flanunable materials were found.

B.

Se cable blocking the closure of the fire damper was inunediately removed and the fire damper returned to operable status.

Corrective Steps Taken to Avoid Further violations i.

A.

A flanunable materials storage cabinet will be placed in the hot l

machine shop to store flanunable materials. A discussion on the control of flamm=ahle materials will be presented during a monthly safety meeting.

B.

he appropriate individual has been counseled. We fire dampers in i

the electrical penetration room of both Unit 1 and 2 have been clearly labeled as fire barriers.

i Date of Full Compliance A.

September 30, 1986 B.

Complete l

l l

I

.,,...,n-,,,,-..-.,-,,__,.-,

.,,--w.,-._,-,,,__,_,,,,

n.-

Mr. D. M. Verrelli August 5, 1986 Page 3 Affirmation I affirm that this response is true and couplete to the best of my knowledge, information, and belief. The information contained in this letter is not considered to be of a proprietary nature.

Yours very ly, R. P. Mcdonald RPM:emb f