Responds to NRC Re Violations Noted in Insp Rept 50-412/86-46.Corrective Actions:Damaged Cable Splices Will Be Replaced.Site QC Reviewing Similar Field Installations to Determine If Condition Exists in Other Cases
ML20212H581
Person / Time
Site: Beaver Valley
Issue date: 02/23/1987
From: Carey J
DUQUESNE LIGHT CO.
To: Ebneter S
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
2NRC-7-031, 2NRC-7-31, NUDOCS 8703060155
Download: ML20212H581 (3)


Text

T

'Af g

2NRC-7-031 (412) 6415200 Beaver Valley No. 2 Unit Project Organization Telecopy (412) 6415200 Ext.160 I,$,G Feb. 23, 1987 B

Shippingport. PA 15077 United States Nuclear Regulatory Commission Region I 631 Park Avenue King of Prussia, PA 19406 ATTENTION:

Mr. Stewart D. Ebneter, Director Division of Reactor Safety

SUBJECT:

Beaver Valley Power Station - Unit No. 2 Docket No. 50-412 Inspection Report 50-412/86-46

REFERENCE:

Letter dated January 23,1986 (S. D. Ebneter to J. J. Carey)

Gentlemen:

The above referenced letter transmitted a Notice of Violation as Appendix A. of this letter provides Duquesne Light Company's (DLC) re-sponse pursuant to the requirenents of 10CFR2.201 and the NRC's Notice of Violation.

DUQUESNE LIGHT COMPANY

' d.

3'. Carey Sr. Vice President LMR/ij r NR/LMR/IR/8646 Attachment cc:

Mr. P. Tan, Project Manager (w/a)

Ms. A. A. Asars, NRC Resident Inspector (w/a)

Mr. J. Beall, NRC Senior Resident Inspector (w/a)

NRC Document Control Desk (w/a) f&30601syg,ADOCKOsoo$$3g O

PDR 17 o\\

United States Nuclear Regulatory Commission

~~

Mr.-Steward D. Ebneter, Director Inspection Report 50-412/86-46 Page 2 COMMONWEALTH OF PENNSYLVANIA )

)

SS:

COUNTY OF BEAVER

)

On this h[dayof - Id.///dze

/h

, before me, a Notary Public in and for said Commonwealt[and County, personally appeared J. J. Carey, who being duly sworn, deposed and said that (1) he is Senior Vice President of Duquesne Light, (2) he is duly authorized to execute and file the foregoing Submittal on behalf of said Conpany, and (3) the statenents set forth in the Submittal are true and correct to the best of his knowledge, u

.J Yb

/

Notary Public

$HEllA 3. FATI0tt. 50TAff PusuC SHIPPilIGPcti805.SEMER COGER ET C0EEISS105 UPIRES SCT. 23. Im e-W. Penestich Asseowies of Genehe r

l l

[

e i

ATTACHMENT 1 NOTICE OF VIOLATION 86-46-01 10CFR50, Appendix B, Criterion V requires that: " Activities affecting quality shall be prescribed by documented instructions--and shall be acceplished in accordance with these instructions -."

Fi eld Construction Procedure No. FCP-431, Section 5.2.10 states that: " Cut edges, sharp corners and holes shall be deburred to provide smooth surfaces which will not danage cables."

Contrary to the above, on Decenber 10, 1986 Cable No. 2SISA0H301 in the low head safety injection pump No. 2 SIS *21A housing was identified by the NRC in-spector that had been danaged at the splice junction by the sharp edges of the f abricated stainless steel motor housing base plate.

This is a Severity Level IV violation.

Response

Inspection of installation of Raychem Heat Shrinkable Tubing resulted in the identification of danage to ' cable splices located in the low head injection punp (No. 2 SIS *P21A) motor lead housing.

The 3-Phase SKV type HTK cable spliced to the punp motor leads showed signs of danage from the sharp edge of the housing back plate.

The cable size and stiffness of the cable places the cable against the sharp metal edge when the motor lead housing cover is replaced.

The danage to these cable splices was addressed on N&D-38725, which has been dispositioned to increase the size of this motor tennination box, to replace the danaged splice kit, and to place edge dressing material on sharp edges.

Corrective action will be conpleted by February 23, 1987.

To detennine if this condition exists in other cases, Site Quality Control is currently reviewing all similar field installations.

This review is expected to be conpleted by March 16, 1987.

F o r further installations, N&D 38873 has been dispositioned and resulted in i