ML20211N806

From kanterella
Jump to navigation Jump to search
Suppls Re Util Compliance W/Gdc 17.Motor Protection Can Be Achieved by Administratively Controlling Torque Switch Setting.Torque Switch Limiter Plates No Longer Required
ML20211N806
Person / Time
Site: Surry  
Issue date: 02/24/1987
From: Stewart W
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
IEB-85-003, IEB-85-3, NUDOCS 8703020228
Download: ML20211N806 (2)


Text

,

VINGINIA I$LECTHIC AND l'OWEH COMPANY Ricnwoxo,VIHOINIA 20261 W.L.STEWANT Vacu Passtomwr wuci.mim o r= =^'"""

February 24, 1987 United States Nuclear Regulatory Commission Serial No.86-736 Attention: Document Control Desk N0/ ALM:jmj Washington, D.C.

20555 Docket Nos.

50-280 50-281 License Nos. DPR-32 DPR-37 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNIT NOS. 1 AND 2 GENERAL DESIGN CRITERIA 17 In our letter dated December 9, 1985, Serial No.85-707, we stated that Surry Power Station was in compliance with General Design Criteria 17, consistent with your safety evaluation dated October 6, 1982. The modifications and operating restrictions that were identified in our letter of March 31,

1982, Serial No.

175, have been implemented.

However, during the course of performing Motor Operated Valve (MOV) testing for compliance with IEB 85-03, we determined that one of these previously completed modifications (torque switch limiter plates) was no longer required.

The limiter plates were provided to physically prevent the torque switch (TS) from being raised above the setting that corresponds to the 80% rated voltage torque output. This was intended to ensure that the torque switch would operate to de-energize the motor after the valve had performed its intended function during extended low voltage conditions. We have now determined that motor protection can be achieved by administratively controlling the the same torque switch setting. Such administrative measures are similar to those already implemented at North Anna Power Station and discussed in our December 23, 1985, Serial No.

85-750B, and May 2, 1986, Serial No.86-198 letters.

If you have any questions or need additional information, please contact us.

Very truly yours, A

kN}

l

/

W. L. Stewart 8703020228 870224 PDR ADOCK 05000280 l li G

PDR 0

1 1

. _.. _ _ _ __~

4 -

cc:

U. S. Nuclear Regulatory Commission 101 Marietta Street, N. W.

Suite 2900 Atlanta, GA 30323 Mr. W. E. Holland NRC Senior Resident Inspector Surry Power Station Mr. Chandu P. Patel NRC Surry Project Manager PWR Project Directorate No. 2 Division of PWR Licensing-A F

1 4

i 4

4' t

1 l

... -.