. Mr. Oliver D. King ley, President August 31, 1999

)

(.

Nucle:r Generation Group -

C:mmonwelith Edison Company

. Ex;cutiva Towers W;st lil l

[

.1400 Opus Place, Suite 500 l

Downers Grove, IL 80515 i

l L

SUBJECT:

REQUEST FOR APPROVAL OF DEFUF. LED STATION EMERGENCY PLAN AND EXEMPTION FROM CERTAIN REQUIREMENTS OF 10 CFR 50.47,

. EMERGENCY PLANS"- ZION NUCLEAR POWER STATION, UNIT NOS.

1 AND 2 (TAC NOS. MA5253 AND MA5254)

L

Dear Mr. Kingsley:

The Commission has issued the ' nclosed exemption for the Zion Nuclear Power Station e

(ZNPS) in response to your application dated April 13,1999, and supplemented by letters dated July 8, July 19, and August 30,1999, in which you requested an exemption from certain l

portions of 10 CFR 50.47(b) and 10 CFR 50.47(c)(2). The exemption was requested to allow

- Commonwealth Edison Company to discontinue offsite emergency planning activities and to reduce the scope of onsite emergency planning because of the substantially reduced risk to public health and safety resulting from the permanently shutdown and defueled condition of

- ZNPS. The specific requirements from which exemption is granted are identified in your submittals and the enclosed safety evaluation.

I Also, the staff has completed its review of the ZNPS defueled station emergency plan (DSEP) submitted with your application and finds that the plan provides an appropriate level of emergency preparedness at the ZNPS in its shutdown and defueled condition. The plan provides reasonable assurance that adequate protective measures will be taken in the event of a radiological emergency at the ZNPS. Therefore, the staff concludes that the ZNPS DSEP provides for an acceptable emergency preparedness program and, upon receipt of the enclosed exemption, Commonwealth Edison Company may implement the plan.

Sincerely, Original Signed By Dino Scaletti, Senior Project Manager Decommissioning Section l

Project Directorate IV & Decommissioning Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-295 DISTRIBUTION:

and 50-304 Docket.

DScaletti RScholl(SE)

PUBLIC CPederson, Rlli DJackson

Enclosures:

1. Exemption PDIV&D Reading OGC GHubbard
2. Safety Evaluation SRichards G. Hill (2)

MHart MMasnik ACNW MReinhart cc w/encis: See next page EPeyton THiltz EWeiss i

  • See arevious concurrences JStaudenmeier DBarss RGallo

...__a

- - - - - - +

,=

OFF PDIV/PM C

PDIV-2/LA C

POfV/SC' C

PDIV/D*

c OGe*

D/DL,PK EPdY MMasnik SRichards AHodgnon JZwo I

NAME DScalletl j

8 8 /18 /99 2

OFFICE SPLB/Bc' SRxB/BC*

SPSB/BC*

IOLB/BC*

NAME JHannon JWermiel RBarrett RGallo f

DATE 8 / 25 /99-8 /18 /99 8/19 199 8 /23 /99

[

l DOCUMENT NAME: G:\\PDIV-3)ZionWp exemption letter.wpd

}

OFFICIAL RECORD COPYDmuMENT NAME: G:\\PDIV-3)Zioniep exemption letter.wpd FICIAL RECORD COPY 9909070079 990831 PDR ADOCK 05000295

[

F PDR

Mr. Oliver D. Kingsley, Prosident Nuclear Generction Group Commonwecith Edison Company Executive Towers West 111 1400 Opus Place, Suite 500 Downers Grove, IL 60515

SUBJECT:

REQUEST FOR APPROVAL OF DEFUELED STATION EMERGENCY PLAN AND EXEMPTION FROM CERTAIN REQUIREMENTS OF 10 CFR 50.47,

" EMERGENCY PLANS"- ZION NUCLEAR POWER STATION, UNIT NOS.

1 AND 2 (TAC NOS. MA5253 AND MA5254)

Dear Mr. Kingsley:

The Commission has issued the enclosed exemption for the Zion Nu ear Power Station (ZNPS) in response to your application dated April 13,1999, andy pplemented by letters dated July 8 and July 19,1999, and a telephone conference call summary dated August 10,1999, in which you requested an exemption from certain portions of O'CFR 50.47(b) and 10 CFR 50.47(c)(2). The exemption was requested to all Commonwealth Edison Company to discontinue offsite emergency planning activities an o reduce the scope of onsite emergency planning because of the substantially re ced risk to public health and safety resulting from the permanently shutdown and def led condition of ZNPS. The specific requirements from which exemption is granted re identified in your submittals and the enclosed safety evaluation.

Also, the staff has completed its review the ZNPS defueled station emergency plan (DSEP) submitted with your application and fi s that the plan provides an appropriate level of emergency preparedness at the Z S in its shutdown and defueled condition. The plan provides reasonable assurance t at adequate protective measures will be taken in the event of a radiological emergency at th NPS. Therefore, the staff concludes that the ZNPS DSEP provides for an acceptable e ergency preparedness program and, upon receipt of the enclosed exemption Com onwealth Edison Company may implement the plan.

I Sincerely, i

Dino Scaletti, Senior Project Managerf pc g.

Project Directorate IV & Decommissioning y*( c:

Decommissioning Section g

y( ) l Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket os. 50-295 DISTRIBUTION:

and 50-304 Docket DScaletti RScholl(SE)

PUBLIC CPederson, R ll DJackson E closures: 1. Exemption PDIV&D Reading OGC GHubbard

/

2. Safety Evaluation SRichards GHill(2)

MHart MMasnik ACNW MReinhart cc w/encis: See next page EPeyton THiltz EWeiss

  • See previous concurrences JStaudenmeier DBarss RGallo io recewe a copy or inis cocument. macate v in me oox k

OFF PDfV/PM

,e PolV-2/LA C

PDIV/sC*

C PDIV/D*

C OGC D/DLPM kk Dscanetikh

'P MMasnik sRichaFos JZwolinski NAME c

DATE 8 / U/99 8/M 9 8 /18 /99 8/23 /99 8 /)_]99 8/

/99 i o recewe a copy or inis 05cD?nTnt, inacate v in ine oox OFFICE sPLB/BC ' )

h sRxB/Be*

sPsB/BC*

?OLB/BC*

NAME JHannon(

lg JWermiel RBarrett RGallo DATE 8[lI/99 /

8 /18 /99 8/19 /99 8 /23 /99 DOCUMENT NAME: G:\\PD1 -3\\ Zion \\ep exemption letter.wpd FFICIAL RECORD COPYDOCUMENT NAME: G.\\PDIV-31 Zion \\ep exemption letter.wpd OFFICIAL RECORD COPY

Mr. Oliver D. Kingsley, President l

Nuclear Generation Group Commonwealth Edison Company l

Executive Towers West lli 1400 Opus Place, Suite 500 l

Downers Grove,IL 60515

SUBJECT:

REQUEST FOR APPROVAL OF DEFUELED STATION EMERGENCY PLAN AND EXEMPTION FROM CERTAIN REQUIREMENTS OF 10 CFR 50.47,

" EMERGENCY PLANS'- ZION NUCL POWER STATION, UNIT NOS.

l 1 AND 2 (TAC NOS. MA5253 AND 5254)

Dear Mr. Kingsley:

i The Commission has issued the encio exemption for the Zion Nuclear Power Station (ZNPS)in response to your ~

dated April 13,1999, and supplemented by letters dated July 8, and July 13,1999, in which requested an exemption from certain portions of l

10 CFR 50.47(b) and 10 CFR 50 7(c)(2). The exemption was requested to allow Commonwealth Edison Com y to discontinue offsite emergency planning activities and to reduce the scope of onsite e ergency planning because of the substantially reduced risk to public health and safety re Iting from the permanently shutdown and defueled condition of ZNPS. The specific req ' ements from which exemption is granted are identified in your submittals and the en sed safety evaluation.

Also, the staff has mpleted its review of the ZNPS defueled station emergency plan (DSEP)

L submitted with yo r application and finds that the plan provides an appropriate level of emergency pre redness at the ZNPS in its shutdown and defueled condition. The plan provides reas able assurance that adequate protective measures will be taken in the event of a radiologi emergency at the ZNPS. Therefore, the staff concludes that the ZNPS DSEP provides f an acceptable emergency preparedness program and, upon receipt of the enclosefexemption Commonwealth Edison Company may implement the plan.

Sincerely, l

/

Dino Scaletti, Senior Project Manager Decommissioning Section Project Directorate IV & Decommissioning Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-295 DISTRIBUTION:

l-and 50-304 Docket DScaletti RScholl(SE)

PUBLIC CPederson, Rill DJackson-l

Enclosures:

1. Exemption PDIV&D Reading OGC GHubbard
2. Safety Evaluation SRichards GHill(2)

MHart MMasnik ACNW MReinhart cc w/encis: See next page EPeyton THiltz EWeiss JStaudenmeier DBarss RGallo i

so-

_u or s= = _._,_ - v si naison h

C PDIV/D C

OGC D/DLPM i

OFF PDfV/PM C

PDN-2AA C

b#

E h

SRichards 5&

Jz oiiniki NAME j

@ jggqg h MmAIMummmmmeJMunemenss's4.".- 2.'==

H 80M OFFICE SPLB/BC SRxB/BC C

SPSB/BC C

IOLB/BC JWormd RBarrett N

RGallo NAME JHannon DATE 8/

/99 8 / /Y/99 8 /N/99 8/

/99 DOCUMENT NAME: GVDN 3\\ Zion %p enompton letter.wpd OFFICIAL RECORD COPYDOC

-3\\ Zion %p exemption letter.wpd

Mr. Oliver D. Kingsley, President Nucisar Generation Group Commonweellh Edison Company Eascutive Towers West 111 1400 Opus Place, Sune 500 Downers Grove,IL 60515

SUBJECT:

REQUEST FOR APPROVAL OF DEFUELED STATION EMERGENCY PLAN AND EXEMPTION FROM CERTAIN REQUIREMENTS OF 10 CFR 50.47,

1 AND 2 (TAC NOS. MA5253 AND MA5254)

Dear Mr. Kingsley:

The Comrmssion has issued the enclosed exemption f the Zion Nuclear Power Station

- (ZNPS) in response to your appiscation dated April 1,1999, and supplemented by letters dated July 8, and July 13,1999, in which you requested exemption from certain portions of 10 CFR 50.47(b) and 10 CFR 50.47(c)(2). The emption was requested to allow Commonwealth Edison Company to discontin offsite emergency planning activities and to reduce the scope of onsite emergency plan ng because of the substantially reduced risk to public health and safety resulting from t rmanently shutdown and defueled condition of ZNPS. The specific requiremerets from ich exemption is granted are identified in your submittals and the enclosed safety ev ustion Also, the staff has completed its r iew of the ZNPS defueled station emergency plan (DSEP) submitted with your application finds that the plan provides an appropriate level of emergency preparedness at t ZNPS in its shutdown and defueled condition. The plan

- provides reasonable assura that adequate protective measures will be taken in the event of a radiologicalemergency the ZNPS. Therefore, the staff concludes that the ZNPS DSEP provides for an accepta emergency preparedness program and, upon receipt of the enclosed exemption C monwealth Edison Company may implement the plan.

Sincerely, Dino Scaletti, Senior Project Manager Decommissioning Section Project Directorate IV & Decommissioning Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-295 DISTRIBUTION:

and 50-304 Docket DScaletti RScholl(SE)

PUBLIC CPederson, Rlli DJackson

Enclosures:

1. Exemption PDIV&D Reading OGC GHubbard
2. Safety Evaluation SRichards GHill(2)

MHart MMasnik ACNW MReinhart cc w/encis: See next page EPeyton THiltz EWeiss JStaudenmeier DBarss RGallo

__ v.i..

OFF PDIV/PM C

PDIV-2/LA C

PDfV/SC C

PDIV/D C

OGC D/DLPM NAME.j E

MMasnik SRichards JZwolinski

@Isr db.4dShnemW l h

e ^ #

E==

/

OFFICE SPLB/BC SRXB/BC SP loLB/BC RBa W f NAME JHannon JWormiel -

RGallo DATE 8/

199 8 /- /99 8[M l 8/

/99 DoCuMEM NAME: GN

Mr. Olever D. Kingsley, President Nuclear Generation Group Commonwealth Edson Company Eancutive Towers West til 1400 Opus Place, Suite 500 Downers Grove, IL-60515 i

SUBJECT:

REQUEST FOR APPROVAL OF DEFUELED STATION EMERGENCY PLAN AND EXEMPTION FROM CERTAIN REQUIREMENTS OF 10 CFR 50.47,

1 AND 2 (TAC NOS. MA5253 AND MA5254)

Dear Mr. Kingsley:

i The Commission has issued the enclosed exemption for the on Nuclear Power Station

. (ZNPS) in response to your appiscation dated April 13,1

, and supplemented by letters dated July 8, and July 13,1999, in which you requested an e ption from certain portions of 10 CFR 50.47(b) and 10 CFR 50.47(c)(2). The exe ion was requested to allow Commonwealth Edison Company to discontinue o rte emergency planning activities and to reduce the scope of onsite emergency planning cause of the substantially reduced risk to

. public health and safety resulting from the pe nently shutdown and defueled condition of ZNPS. The specific requirements from whi exemption is granted are identified in your submittals and the enclosed safety evalua '

I Also, the staff has completed its rev' of the ZNPS defueled station emergency plan (DSEP) submitted with your application and ds that the plan provides an appropriate level of emergency preparedness at the Z S in its shutdown and defueled condition. The plan provides reasonable assurance at adequate protective measures will be taken in the event of a radiological emergency at NPS. Therefore, the staff concludes that tha ZNPS DSEP provides for an acceptable e ergency preparedness program and, upon receipt of the enclosed exemption Com alth Edison Company may implement the plan.

Sincerely, i

Dino Scaletti, Senior Project Manager Decommissioning Section Project Directorate IV & Decommissioning Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-295 DISTRIBUTIO,N_:

and 50-304 Docket DScaletti RScholl(SE; PUBLIC CPederson, Rlli DJackson

Enclosures:

1. Exemption PDIV&D Reading OGC GHubbard
2. Safety Evaluation SRichards GHill(2)

MHart MMasnik ACNW MReinhart cc w/encis: See next page EPeyton THiltz EWeiss JStaudenmeier DBarss RGallo _

so.

_ e - or was --- __,__ - v mwuaus OFF POlV/PM C

PDfV-2AA C

PDIV/SC C

PDfV/D C

OGC D/DLPM E

MMesnk SRichards JZwolinski NAME j

,g,,,,g,,,,,,,

.,g,1 8i

/w 8

g OFFICE SPLB/BC SRxB/BC SPSB/BC IOLB/BC

_j NAME JHannon JWormie RBarrett RGallo DATE 8I

/99 8//h/99

.M 8/

/99 8/

/99 DOCUMENT NAME: G:PDIV-3\\ZionWp exempton totterfwpd CCFFEE RMsSJD COPYDOCUMENT NAME: G:PDIV-3\\ Zion \\ep exemption letter.wpd

Mr. Oliver D. Kingsley, President i

I I

Nuclear Generati::n Group Commonwealth Edison Company Executive Towers West til 1400 Opus Place, Suite 500 Downers Grove,IL 60515

{

SUBJECT:

REQUEST FOR APPROVAL OF DEFUELED STATION EMERGENCY PLAN AND EXEMPTION FROM CERTAIN REQUIREMENTS OF 10 CFR 50.47,

" EMERGENCY PLANS"- ZION NUCLEAR POWER STATION, UNIT NOS.

1 AND 2 (TAC NOS. MA5253 AND MA5254)

Dear Mr. Kingsley:

The Commission has issued the enclosed exemption for th ion Nuclear Power Station (ZNPS) in response to your application dated April 13,19, and supplemented by letters dated July 8, and July 13,1999, in which you requested an e mption from certain portions of 10 CFR 50.47(b) and 10 CFR 50.47(c)(2). The exe tion was requested to allow Commonwealth Edison Company to discontinue o site emergency planning activities and to reduce the scope of onsite emergency planning cause of the substantially reduced risk to public health and safety resulting from the pe anently shutdown and defueled condition of ZNPS. The specific requirements from whi exemption is granted arc identified in your submittals and the enclosed safety evalu ion Also, the staff has completed its revi of the ZNPS defueled station emergency plan (DSEP) submitted with your application an inds that the plan provides an appropriate level of emergency preparedness at the PS in its shutdown and defueled condition. The plan provides reasonable assuran that adequate protective measures will be taken in the event of a radiological emergency at e ZNPS. Therefore, the staff concludes that the ZNPS DSEP provides for an acceptable mergency preparedness program and, upon receipt of the enclosed exemption Co onwealth Edison Company may implement the plan.

Sincerely, Dino Scaletti, Senior Project Manager Decommissioning Section Project Directorate IV & Decommissioning Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-295 DISTRIBUTION:

and 50-304 Docket DScaletti RScholl(SE)

PUBLIC CPederson, Rlli DJackson

Enclosures:

1. Exemption PDIV&D Reading OGC GHubbard
2. Safety Evaluation SRichards GHill(2)

MHart MMasnik ACNW MReinhart cc w/encis: See next page EPeyton THiltz EWeiss JStaudenmeier DBarss RGallo i o. _. _ m -, or me www... --- -- v m me aux oFF PDIV/PM C

PDIV-2AA C

PDIV/SC c

PDIV/D C

OGC D/DLPM b - _-f Edykt MMasnk SRichards JZwohnski NAME j

[

OFFICE SPLB/Bc SRXB/BC SPSB/BC Ic BC NAME JHannon JWermiel RBarrett R

og DATE 8/

/99 6/-

/99 8/

/99 8/

/99 DOCUMENT NAME: G:\\PDIV-3\\Zonwp exempton letter.wpd

/

OFFICIAL RECORD CoPYDOCuMENT NAME: G:\\PDIV-3\\ Zion /tWtA,23fep exetiption letter.wpd r6T%%r@Mr@ lot 5uM5W

F s

paa RE4g p

UNITED STATES

- ;g j

NUCLEAR REGULATORY COMMISSION WASHINGTON, D.C. 30686-4001 August 31, 1999 Mr. Oliver D. Kingsley, President Nuclear Generation Group Commonwealth Edison Company Executive Towers West lil 1400 Opus Place, Suite 500 Downers Grove, IL 60515

SUBJECT:

REQU' EST FOR APPROVAL OF DEFUEL$D STATION EMERGENCY PLAN AND EXEMPTION FROM CERTAIN REQUIREMENTS OF 10 CFR 50.47,

" EMERGENCY PLANS * - ZION NUCLEAR POWER STATION, UNIT NOS.

1 AND 2 (TAC NOS. MA5253 AND MA5254)

Dear Mr. Kingsley:

The Commission has issued the enclosed exemption for the Zbn Nuclear Power Station (ZNPS) in response to your application dated April 13,1999, and supplemented by letters dated July 8, July 19, and August 30,1999, in which you requested an exemption from certain portions of 10 CFR 50.47(b) and 10 CFR 50.47(c)(2). The exemption was requested to allow Commonwealth Edison Company to discontinue offsite emergency planning activities and to reduce the scope of onsite emergency planning because of the substantially reduced risk to public health and safety resulting from the permanently shutdown and defueled condition of ZNPS. The specific requirements from which exemption is granted are identifieHf in your submittals and the enclosed safety evaluation.

Also, the staff has completed its review of the ZNPS defueled station emergency plan (DSEP).

submitted with your application and finds that the plan provides an appropriate level of emergency preparedness at the ZNPS in its shutdown and defueled condition. The plan provides reasonable assurance that adequate protective measures will be taken in the event of a radiological emergency at the ZNPS. Therefore, the staff concludes that the ZNPS DSEP provides for an acceptable emergency preparedness program and, upon receipt of the.

q enclosed exemption, Commonwealth Edison Company may implement the plan.

]

Sincerely, Dino Scaletti, Senior Project Manager Decommissioning Section Project Directorate IV & Decommissioning Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-295 '

and 50-304

Enclosures:

1. Exemption
2. Safety Evaluation cc w/encls:. See next page I

Commonwealth Edison Company.

cc w/encis:

Mr. David Helwig lilinois Department of Nuclear Safety Senior Vice President Office of Nuclear Facility Safety 4

Commonwealth Edison Company 1035 Outer Park Drive 1400 Opus Place, Suite 900 Springfield,IL 82704 Downers Grove,IL 60515 Dr. Cecil Lue-Hing, Director Mr. Gene H. Stanley Research and Development PWR Vice President Metropolitan Sanitary Commonwealth Edison Company District of Greater Chicago 1400 Opus Place, Suite 900 100 E. Erie Street Downers Grove, IL 60515 Chicago,IL 60611 Mr. Christopher Crane Phillip Steptoe, Esquire BWR Vice President Sidley and Austin Commonwealth Edison Company One First National Plaza 1400 Opus Place, Suite 900 Chicago,IL 60603 Downers Grove, h 60515 U.S. Nuclear Regulatory Commission Mr. R. M. Krich ~

Zion Resident inspectors Office Vice President - Regulatory Services 105 Shiloh Blvd.

Commonwealth Edison Company Zion,IL 60099 1400 Opus Place, Suite 900 Downers Grove, IL 60515 Regional Administrator U.S. NRC, Region 111 DCD - Licensing 801 Warrenville Road Commonwealth Edison Company Lisle, IL 60532-4351 1400 Opus Place, Suite 400 Downers Grove, IL 60515 Mayor of Zion Zion,IL 60099 Mr. R. Starkey, Decommissioning Plant Manager Karl Nollenberger, County Administrator Zion Station Lake County Administrator's Office 101 Shiloh Blvd.

18 N. County Street,9* Floor Zion, IL 60099-2797 Waukegan, IL 60085-4334 Mr. R. Godley, Regu'atory Assurance Manager Zion Station 101 Shiloh Blvd.

Zion, IL 60099-2797 Ms. Pamela B. Stroebel Senior Vice President and General Counsel Commonwealth Edison Company P.O. Box 767 Chicago, IL 60690-076

,