ML20211D240
| ML20211D240 | |
| Person / Time | |
|---|---|
| Site: | Perry |
| Issue date: | 08/19/1999 |
| From: | Jeffery Wood CENTERIOR ENERGY |
| To: | Underwood M OHIO, STATE OF |
| References | |
| PY-CEI-OEPA-031, NUDOCS 9908260215 | |
| Download: ML20211D240 (2) | |
Text
O L.
l C
E Perry Nuclear Power Plant
~"
P. otuo 4408 l
John K. Wood Vwe Preskient, Nuclear 443pggg4 pg,; 449.gggggy August 19,1999 PY-CEI/OEPA-0318L Attention: Ms. Marie Underwood Ohio Environmental Protection Agency Northeast District Office 2110 E. Aurora Road l
Twinsburg, Ohio 44087 Ladies and Gentlemen:
This letter is submitted in accordance with the National Pollutant Discharge and Elimination System (NPDES) permit number 3IB00016*ED, Part III, Item 12.C. On August 18, a telephone notification was made to report an NPDES permit noncompliance. The following information fulfills the permit requirements.
- 1. The limitation which has been exceeded.
Chlorinated water bypassed the permitted discharge point (entered a storm drain).
- 2. The extent of the exceedance.
Approximately 200 gpm for 40 minutes of water containing 1 ppm chlorine.
- 3. The cause of the exceedance.
[o Equipment malfunction - valve leakage.
- 4. The period of the exceedance, including exact dates and times.
The incident began on 8/17/99 at 09:10 and ended on 8/17/99 at 09:50.
- 5. If uncorrected, the anticipated time the exceedance is expected to continue.
Not applicable. Chlorination terminated. Valve isolated to allow for chlorination until valve l
repairis accomplished.
l D
D 9908260215 990819 PDR ADOCK 05000440 S
PDR l
O 6
PY-CEI-OEPA-0318L Augus't 19,1999 Page 2 of2
- 6. Steps being taken to reduce, eliminate, and/or prevent recurrence of the exceedence.'
- a. The valve will remain isolated until it is repaired.
- b. Other similar valves will be inspected.
Ifyou have questions or require additional information, please contact Ms. Donna Tizzano at (440) 280-5514.
Very tmly yours,
[ 3 4%Z.
DGT:sc cc:
NRC RegionIII NRC ResidentInWor NRC Project Manager NRC Document Control Desk (Docket No. 50-440)
,