ML20211B507
| ML20211B507 | |
| Person / Time | |
|---|---|
| Site: | Vogtle |
| Issue date: | 05/29/1986 |
| From: | Foster D GEORGIA POWER CO. |
| To: | Grace J NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| References | |
| REF-PT21-86, REF-PT21-86-239-000 GN-930, PT21-86-239, PT21-86-239-000, NUDOCS 8606110713 | |
| Download: ML20211B507 (2) | |
Text
r DU6 Georgia Power Company Post Office Box 282 l
Waynesboro, Georgia 30330 Telephone 404 554 9%1, Ext. 3360 404 724 8114. Ext. 3360 L
, J":: 4 M0:30 Georgia Power
- o. o.ro,e, gPres ent the smthem 6,xtrc sgrem May 29, 1986 United States Nuclear Regulatory Commission Region II File: X78G03-M107 l
Suite 2900 Log:
GN-930 101 Marietta Street, Northwest Atlanta, Georgia 30323
Reference:
Vogtle Electric Generating Plant-Units 1 and 2; 50-424, 50-425; Derating Factors for Cable Ampacities in Closed Tray; Letter GN-897, dated May 6, 1986 Attention: Mr. J. Nelson Grace In our previous correspondence on this subject, Georgia Power Company described a potentially reportable condition whereby ampacity derating for power cables routed in solid bottom cable tray with unventilated cover was not specifically addressed in applicabla calculations and design criteria.
A field walkdown was conducted to determine if any unventilated tray covers had been installed either for debris protection or for Regulatory Guide 1.75 separation barriers on power cable tray.
The walkdown determined that no tray covers had been installed.
Since no defective condition was identified as a result of the field walkdown, l
Georgia Power Company has concluded that this concern is not reportable pursuant to the requirements of 10 CFR 50.55(e) or 10 CFR 21.
To prevent future concerns, design drawings are being modified to require engineering approval prior to the installation of unventilated tray cove *s on solid bottom cable tray susceptible to ampacity derating l
concerns.
In addition, the applicable calculation and design criteria will be revised to address ampacity derating for power cable in closed tray.
This response contains no proprietary information and may be placed in the NRC Public Document Room.
Yours,truly, f i
{
/D
- 0. Foster' REF/DOF/tdm Distribution on Page Two 8606110713 860529 PDR ADOCK 05000424
}O S
PDR hT
'l
s 'e Page Two xc:
U. S. Nuclear Regulatory Commission Document Control Desk Washington, D. C.
20555 J. H. Miller R. A. Thomas L. T. Gucwa J. P. O'Reilly D. R. Altman C. W. Hayes G. F. Head P. R. Bemis G. A. McCarley R. E. Conway J. A. Bailey D. S. Read J. T. Beckham
- 0. Batum Sr. Resident (NRC)
R. H. Pinson G. Bockhold C. S. McCall (OPC)
P. D. Rice C. E. Belflower J. E. Joiner (TSLA)
B. M. Guthrie J. F. D'Amico D. C. Teper (GANE)
D. E. Dutton E. D. Groover NORMS