Responds to NRC 860718 Request for Review & Comments on BNL Draft Rept on Intersys Locas.Rept Accurate & Objective. Caution in Use of Historical Experience Recommended.Comments Encl
ML20210U303
Person / Time
Site: Quad Cities  
Issue date: 10/01/1986
From: Wojnarowski J
COMMONWEALTH EDISON CO.
To: Zwolinski J
Office of Nuclear Reactor Regulation
References
2175K, NUDOCS 8610090481
Download: ML20210U303 (3)


Text

.. "

.-s

} Commonwealth Edison 72 West Adams Street. Chicago, Illinois 7 Address Reply to: Post Othce Box 767 (M Chicago, Illinois 60690 - 0767 October 1, 1986 Mr. J. A. Zwolinski, Director BWR Project Directorate #1 Division of BWR Licensing U.S. Nuclear Regulatory Commission Washington, DC 20555

Subject:

Quad Cities Station Units 1 and 2 Comments on BNL Draft Report on Inter-System LOCA's NRC Docket Nos. 50-254 and 50-265

Reference:

July 18, 1986 letter from J. A. Zwolinski to D. L. Farrar.

Dear Mr. Zwolinski:

The referenced letter requested our review and comments on the subject draft report on Inter-system LOCA's prepared by Brookhaven National Laboratory. The attachment to this letter provides our comments.

In general, we believe the Brookhaven work to be accurate and objective (assuming the incorporation of our attached comments). However, caution should be exercised in the use of historical experience. Maintenance and test procedures are plant specific.

Industry awareness to the events cited in the report should reduce their probability of recurrence.

It must be noted that several of the occurrences in fact demonstrated the plant personnel's abilities to recognize that something was wrong, and take corrective action. Commonwealth Edison is available and willing to assist Brookhaven in the analysis of these occurrences to assure correct failure data and fault free modeling.

If you have any questions regarding our comments or desire our further assistrace, please contact this office.

Very truly yours, M

J. R. Woj rowski j

Nuclear Licensing Administrator 1m Attachment cc:

R. Bevan - NRR 0

0 21~15K 8610090481 861001 g

PDR ADOCK 05000254 i

P PDR

COMMENTS ON DRAFT LETTER REPORT FIN A-3829 INTERFACING SYSTEMS LOCA AT BWR'S GENERIC ISSUE #105 MAY, 1986 Page Section 2-8 Table 2.1 Quad-Cities has a head spray steam condensing mode of RHR.

2-8 Table 2.1 Quad-Cities has two contaminated condensate storage tanks of 350,000 gallon capacity each.

A-46 A.3.1.1 Only the 1001-47 and 50 valves are interlocked CLOSED on reactor pressure.

The 1001-43 valves may be opened with reactor pressure > 100 psig.

A-47 A.3.2.2 Relief valves in parallel with RV-22A and B are

(

RV-166A and B with a one-inch line (not RV-165A and B with a four-inch line).

Setpoint is 450 psig.

A-48 A.3.3.2 The vessel head spray line relief valve will be available due to the normal ~20% OPEN position of the 1001-58 control valve.

The RHR heat exchangers relief valves are also available, although they are one-inch valves.

A-49 A.3.3.2 A resulting LOCA of sufficient size to affect the jet pumo riser AP Indication to isolate both recirculation loops is extremely unlikely.

The low pressure pipe would break, the leakage would be past the check valve and two closed M0's, and still be large eno. ugh to affect jet pump riser AP?

A-50 A.3.5.2 The two-inch relief valve is set at 475 psig, not 375 psig.

t l

A-50 A.3.5.2 The vulnerable piping is from tha upstream isolation valves back through to the stop check valves - 1402-8A and 8B - not the pump.

A-50 A.3.6.1 The HPCI injection line description should reflect addition of safe shutdown pump injection line.

(Also change Figure A.3.d.)

05608

.. j

.Page 2 A-51 A.3.6.2-In order to have an interfacing LOCA, the feedwater check valves must fail in addition to i

the CLOSED MOV 2301-8 and check valve 2301-7.

A-49

-A.3.4.2 In order to have an interfacing LOCA, the feedwater check valves must fall as well-as the-check valve A0 1301-50 and normally CLOSED MOV 1301-49.

A-56 Table A.3.1 Valve stroke operability, timing quarterly.

A-56 Table A.3.1 Relief valve capacity:

RV-44 (not 144), one and l

one-half inch at 150 psig.

Delete the other four relief valves.

j A-57 Table A.3.2 Surveillance requirement for check valve is "None".

Add to relief valve capacity the RV 166A and 1668 valves - one-inch at 450 psig and change RV-59 to one-inch at 408 psig.

A-58 Table A.3.3 Add to relief valve capacity the RV 166A and 166B valves - one-inch at 450 psig and change RV-59 to l

one-inch at 408 psig.

i A-57, A-58, Delete any " power failure position" indicating l

A-59, A-60, CLOSED for all check valves.

Check valves respond i

A-61, A-62, to system process pressures - they don't " fall A-63 CLOSED".

a

-A-60 Table A.3.5 Surveillance requirement is refueling outage LLRT.

A-61 Table A.3.6 Relief capacity:

RV-28A and 288, two-inch at 475 psig - not 375 psig.

I A-63 Surveillance requirement is refueling outage LLRT.